You are on page 1of 29

Lo t 2 5-2 7, Trun g Tam Ro ad , Tan Ta o I nd ustry Z on e,

Ta n Tao A W ard, Bi n h Ta n Dist ric t, HCM Ci ty, Vi et Nam


Te l: + 84 2 8 3 75 4 56 78 Fax: + 84 2 8 3 75 4 56 79
ASIA REFIGERATION INDUSTRY COMPANY W e bsite : www. arico . com.vn
Owner: ARC BINH DUONG CORPORATION Ho Chi Minh City, October 28th, 2020
Project: ARC BINH DUONG COLD STORAGE WAREHOUSE
Số: 153R7/BG/ARC/20.10
QUOTATION
(Phase 1)
Dear: BOARD OF DIRECTOR - ARC BINH DUONG COORPORATION
Address: Lot G7, Road Number 6, Song Than 2 Industrial Zone, Di An Ward, Di An District, Binh Duong Province, Vietnam
Tel: (+84) 283 822 7280 Fax:
With reference to your inquiry, we are pleased to submit our best quotation for the supply as follow:
I. Commodities and prices

ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Freezing Storage - Room 1 (9480 pallets) -


phase 1: 105.71mL x 15.17mW x 30.20mH
- Freezing Storage - Room 2 (9480 pallets) -
phase 1: 105.71mL x 15.00mW x 30.20mH
- Buffer Area (Frist Floor) -phase 1,2:
55.75mL x 20.70mW x 3.50mH
- Picking/Repacking Area (Second Floor) -
COLD STORAGE CABINET phase 1: 26.30mL x 60.12mW x 4.00mH
A. (m2) 30,941 2,345,040
(FOR PHASE 1) - Chill Storage - Room 7 (Third Floor):
26.30mL x 60.12mW x 6.90mH
- Chill Storage - Room 8 (Fourth Floor):
26.30mL x 60.12mW x 6.90mH
- All utility room (machine room, electrical
room, MDB room, generator room) have
height 4.4m
(Please check layout drawing for reference)

1/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]
Insulated panel for Wall and
Ceiling for ASRS Cold storage,
1. lot 1 - 1,160,993
buffer room, picking room,
chill storages
- Panel thickness: 200mm
- Foam PIR
- Both sides cover by colorbond steel with
Wall, panel for Freezing storage Zinc-Aluminum coating, Standard color is
Greenpan
1.1 1,2 - ASRS system (-25oC) & RAL9002, thickness 0.6mm m2 9,217 51.39 473,685
(Arico)/Vietnam
buffer room at axis 12A to 12E - Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 200mm


- Foam PIR
- Both sides cover by colorbond steel with
Ceiling panel for Freezing Zinc-Aluminum coating, Standard color is
Greenpan
1.2 storage 1,2 - ASRS system (- RAL9002, thickness 0.6mm m2 3,175 51.39 163,163
(Arico)/Vietnam
25oC) - Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 125mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Partition for Freezing storage 1,2 - Greenpan
1.3 RAL9002, thickness 0.6mm m2 3,235 38.55 124,717
ASRS system (-25oC); (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

2/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall panel for Ante-room (-10oC Greenpan
1.4 RAL9002, thickness 0.6mm m2 140 34.59 4,828
÷ 0oC) (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Ceiling panel for Ante-room (- Greenpan
1.5 RAL9002, thickness 0.6mm m2 48 34.59 1,665
10oC ÷ 0oC) (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall panel for buffer area - Frist Greenpan
1.6 RAL9002, thickness 0.6mm m2 460 34.59 15,914
Floor (+5oC) (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

3/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Add ceiling
Zinc-Aluminum coating, Standard color is
Ceiling panel for buffer area - Greenpan insulation for
1.7 RAL9002, thickness 0.6mm m2 1,566 34.59 54,176
Frist Floor (+5oC) (Arico)/Vietnam request on
- Joint locking system without cam-lock
October 08th
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall panel for Picking/Repacking Greenpan
1.8 RAL9002, thickness 0.6mm m2 460 34.59 15,914
Area - Second Floor (+5oC) (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Add ceiling
Ceiling panel for Zinc-Aluminum coating, Standard color is
Greenpan insulation for
1.9 Picking/Repacking Area - Second RAL9002, thickness 0.6mm m2 1,566 34.59 54,176
(Arico)/Vietnam request on
Floor (+5oC) - Joint locking system without cam-lock
October 08th
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

4/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall panel for Room 7 - third Greenpan
1.10 RAL9002, thickness 0.6mm m2 785 34.59 27,169
floor (+5oC ÷ +15oC) (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Add ceiling
Zinc-Aluminum coating, Standard color is
Ceiling panel for Room 7 - third Greenpan insulation for
1.11 RAL9002, thickness 0.6mm m2 1,566 34.59 54,176
floor (+5oC ÷ +15oC) (Arico)/Vietnam request on
- Joint locking system without cam-lock
October 08th
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall panel for Room 8 - fourth Greenpan
1.12 RAL9002, thickness 0.6mm m2 797 34.59 27,558
floor (+5oC ÷ +15oC) (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

5/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Ceiling panel for Room 8 - fourth Greenpan
1.13 RAL9002, thickness 0.6mm m2 1,566 34.59 54,176
floor (+5oC ÷ +15oC) (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Panel for covering the column in
Zinc-Aluminum coating, Standard color is
Freezing storage 1,2 - ASRS Greenpan
1.14 RAL9002, thickness 0.6mm m2 720 26.91 19,382
system; Ante-room (13 columns, (Arico)/Vietnam
- Joint locking system without cam-lock
each column height 30.2m)
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Panel for covering the column in Zinc-Aluminum coating, Standard color is
Greenpan
1.15 buffer room) (21 columns, each RAL9002, thickness 0.6mm m2 319 26.91 8,590
(Arico)/Vietnam
columns height 4m) - Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

6/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Panel for covering the column in
Zinc-Aluminum coating, Standard color is
Picking/Repacking Area - Second Greenpan
1.16 RAL9002, thickness 0.6mm m2 319 26.91 8,590
Floor (21 columns, each columns (Arico)/Vietnam
- Joint locking system without cam-lock
height 4m)
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Panel for covering the column
Zinc-Aluminum coating, Standard color is
chill storage 7 at thirth floor) (21 Greenpan
1.17 RAL9002, thickness 0.6mm m2 559 26.91 15,032
columns, each columns height (Arico)/Vietnam
- Joint locking system without cam-lock
7m)
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Panel for covering the column in
Zinc-Aluminum coating, Standard color is
chill storage 8 at fourth floor) (21 Greenpan
1.18 RAL9002, thickness 0.6mm m2 567 26.91 15,247
columns, each columns height (Arico)/Vietnam
- Joint locking system without cam-lock
7.1m)
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

Filling foam gap between column


and covering panel (13 columns Greenpan
1.19 PUR manual injection 30-32 kg/m3 lot 1 11,110.43 11,110
in cold storage 1, anter room, (Arico)/Vietnam
each column height 30.2m)

7/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Panel cover beam of anteroom in Zinc-Aluminum coating, Standard color is
Greenpan
1.20 freezing storage (first, second, RAL9002, thickness 0.6mm m2 209 34.59 7,237
(Arico)/Vietnam
third, fourth floor) - Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102
- PUR manual injection 30-32 kg / m3
Insulation work for bracing beam - Cover bracing beam: Stainless steel 304,
Greenpan Update
1.21 and foam for filling in the bracing 0.5mm thickness lot 1 4,491.21 4,491
(Arico)/Vietnam October 28th
beam at I1÷I12-axis - Cover length: please check reference
document

Insulated panel for Wall and


Ceiling for utility room:
2 machine room, electrical lot 1 - 105,904
control room, generator room,
pump room, WC…
- Panel thickness: 100mm
- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall, partition panel for Cargo lift Greenpan
2.1 RAL9002, thickness 0.6mm m2 131 34.59 4,536
first floor (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

8/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall, partition panel for Cargo lift Greenpan
2.2 RAL9002, thickness 0.6mm m2 103 34.59 3,570
second floor (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall, partition panel for Cargo lift Greenpan
2.3 RAL9002, thickness 0.6mm m2 168 34.59 5,801
thirth floor (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall, partition panel for Cargo lift Greenpan
2.4 RAL9002, thickness 0.6mm m2 168 34.59 5,801
fourth floor (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

9/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall, partition panel for Cargo lift Greenpan
2.5 RAL9002, thickness 0.6mm m2 97 34.59 3,356
fifth floor (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Ceiling panel for Cargo lift fifth Greenpan
2.6 RAL9002, thickness 0.6mm m2 32 34.59 1,098
floor (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall, partition panel for dock Greenpan
2.7 RAL9002, thickness 0.6mm m2 318 26.91 8,553
houses (Arico)/Vietnam
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

10/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Wall panel for stair near cargo lift Zinc-Aluminum coating, Standard color is
Greenpan Update
2.8 at first floor, second floor, thirth RAL9002, thickness 0.6mm m2 409 26.91 11,002
(Arico)/Vietnam October 28th
floor, fourth floor and fifth floor - Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Wall panel for passenger lift Zinc-Aluminum coating, Standard color is
Greenpan
2.9 room at second floor, thirth floor, RAL9002, thickness 0.6mm m2 185 26.91 4,968
(Arico)/Vietnam
fourth floor and fifth floor - Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Wall panel for: pump rooom, Zinc-Aluminum coating, Standard color is
2.10 store, change room, operating RAL9002, thickness 0.6mm Vietnam m2 212 26.91 5,708
room at cos 0.2 - Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

11/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
2.11 Wall panel for WC at cos 3.4 RAL9002, thickness 0.6mm Vietnam m2 98 26.91 2,631
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall panel for machine room at
2.12 RAL9002, thickness 0.6mm Vietnam m2 257 26.91 6,914
fifth floor
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall panel for electrical control
2.13 RAL9002, thickness 0.6mm Vietnam m2 198 26.91 5,330
room
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

12/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Ceiling panel for electrical control
2.14 RAL9002, thickness 0.6mm Vietnam m2 413 26.91 11,113
room
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall panel for MDB room fifth
2.15 RAL9002, thickness 0.6mm Vietnam m2 35 26.91 955
floor
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Ceiling panel for MDB room fifth
2.16 RAL9002, thickness 0.6mm Vietnam m2 94 26.91 2,529
floor
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

13/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall panel for generator room at
2.17 RAL9002, thickness 0.6mm Vietnam m2 135 34.59 4,672
fifth floor
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Ceiling panel for generator room
2.18 RAL9002, thickness 0.6mm Vietnam m2 68 34.59 2,355
at fifth floor
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall panel for condenser room,
2.19 RAL9002, thickness 0.6mm Vietnam m2 200 26.91 5,388
at fifth floor
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

14/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall, ceiling panel for cover
2.20 RAL9002, thickness 0.6mm Vietnam m2 247 26.91 6,657
passenger lift
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 50mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Panel for covering the column in
2.21 RAL9002, thickness 0.6mm Vietnam m2 40 26.91 1,084
office at first floor
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102

- Panel thickness: 100mm


- Foam PIR
- Both sides cover by colorbond steel with
Zinc-Aluminum coating, Standard color is
Wall panel for cargo room at fifth Detail October
2.22 RAL9002, thickness 0.6mm Vietnam m2 54 34.59 1,884
floor 28th
- Joint locking system without cam-lock
- Density of insulating foam: 40-42 kg/m3
- Thermal conductivity: 0.02 W/m.K
- Fire Resistance Class: Class B1- DIN4102
Floor insulation sheet (For two
3 lot 1 - 315,784
phases)

15/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]
- Extruded Polystyrence (XPS) thickness:
50mm x 6 layers
- Thermal conductivity: 0,03 W/mK ± 10%
Floor insulation sheet for
- Density: 38 kg/m3 ± 5%
3.1 Freezing storage 1,2 - ASRS Vietnam m2 3,219 29.77 95,823
- Size Tolerance: ± 5%
system (-25oC)
- Compressive strength at 10% deformation:
300 kPa ± 10%
- Water absorption per unit volume ≤ 1%
- Extruded Polystyrence (XPS) thickness:
50mm x 4 layers
- Thermal conductivity: 0,03 W/mK ± 10%
Floor insulation sheet for buffer - Density: 38 kg/m3 ± 5%
3.2 Vietnam m2 1,566 19.85 31,090
area - first floor (+5oC) - Size Tolerance: ± 5%
- Compressive strength at 10% deformation:
300 kPa ± 10%
- Water absorption per unit volume ≤ 1%
- Extruded Polystyrence (XPS) thickness:
50mm x 4 layers
- Thermal conductivity: 0,03 W/mK ± 10% Add floor
Floor insulation sheet for
- Density: 38 kg/m3 ± 5% insulation for
3.3 Picking/Repacking Area - Second Vietnam m2 1,566 19.85 31,090
- Size Tolerance: ± 5% request on
Floor (+5oC)
- Compressive strength at 10% deformation: October 08th
300 kPa ± 10%
- Water absorption per unit volume ≤ 1%
- Extruded Polystyrence (XPS) thickness:
50mm x 4 layers
- Thermal conductivity: 0,03 W/mK ± 10% Add floor
Floor insulation sheet for Room 7 - Density: 38 kg/m3 ± 5% 2 insulation for
3.4 Vietnam m 1,566 19.85 31,090
- third floor (+5oC ÷ +15oC) - Size Tolerance: ± 5% request on
- Compressive strength at 10% deformation: October 08th
300 kPa ± 10%
- Water absorption per unit volume ≤ 1%

16/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]
- Extruded Polystyrence (XPS) thickness:
50mm x 4 layers
- Thermal conductivity: 0,03 W/mK ± 10% Add floor
Floor insulation sheet for Room 8 - Density: 38 kg/m3 ± 5% insulation for
3.5 Vietnam m2 1,566 19.85 31,090
- fourth floor (+5oC ÷ +15oC)) - Size Tolerance: ± 5% request on
- Compressive strength at 10% deformation: October 08th
300 kPa ± 10%
- Water absorption per unit volume ≤ 1%
- Extruded Polystyrence (XPS) thickness:
50mm x 6 layers
- Thermal conductivity: 0,03 W/mK ± 10%
Floor insulation sheet for
- Density: 38 kg/m3 ± 5% Phase two floor
3.6 Freezing storage 3,4 - ASRS Vietnam set 3,211 29.77 95,603
o - Size Tolerance: ± 5% insulation
system (-25 C)
- Compressive strength at 10% deformation:
300 kPa ± 10%
- Water absorption per unit volume ≤ 1%
Insulated door and dock
4 Lot 1 143,584
system
Clear opening dimension: 1,500W x 2000H
(mm)
D1 - High speed door for ASRS Frame: gavalnized steel. Not on Arico's
4.1 BMP / Italia set 0 4,242 -
cold storage 1,2 Opening speed 2.5 m/s, closed 1 m/s Scope
Heating kit, safty kit, automatic repair
Operation: Automation
Clear opening dimesion: 1,500W x 2,000H
(mm)
Door Frame: Reinforce PVC
D2 - Vertical Sliding Door for Blade thickness: 121mm, duoble gaskets Not on Arico's
4.2 Globe/Italia set 0 8,067 -
ASRS cold storage 1,2 heating cable in frame Scope
Application: Cold storage -25oC inside, -5oC
outside
Operation: Automation
Clear opening dimension: 9,00W x 2,000H x
100T (mm.)
D3 - Access Door for freezing INTERCOLD-
4.3 0.5mm colorbond sheet both sides set 11 706 7,766
storage 1,2 ARICO/Viet Nam
Door Hinged Mechanism origin: EU
Operation: Manual

17/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]
Clear opening dimension: 9,00W x 2,000H x
100T (mm.)
INTERCOLD-
4.4 D31 - Access Door 0.5mm colorbond sheet both sides set 14 706 9,884
ARICO/Viet Nam
Door Hinged Mechanism origin: EU
Operation: Manual
Dimension: 1,200W x 2,200H x 100T (mm.)
0.5mm colorbond sheet both sides INTERCOLD-
4.5 D4 - Access Door for buffer area set 4 882 3,528
Door Hinged Mechanism origin: EU ARICO/Viet Nam
Operation: Manual
OH2 - Overhead sectional door
Dimesion: 2,400W x 2,700H
4.6 for dock position and inlet/outlet INKEMA/ Spain set 12 2,682 32,184
Operation: Electric
forcelift
Dimesion: 2,400W x 2,700H
OH1 - Aluminum roller door for Operation: Electric
4.7 Vietnam set 11 585 6,435
dock Material: Aluminum
Motor: Taiwan
Application: container truck
Dimension: 2,200W x 3,000H
4.8 DL- Dock leveler INKEMA/ Spain set 11 3,645 40,095
Material: steel painted according to the
manufacturer's standard color
Application: container truck
4.9 DS - Dock Shelter INKEMA/ Spain set 11 3,972 43,692
Dimension: 3,600W x 3,800H

Update
Accessories for installing cold October 28th,
5 Lot 1 238,031
storage light not on
scope of Arico
Pressure balance valve in and out of the
5.2 Pressure relief valve. Fermod / France set 78 330 25,740
cold storage when temperature fluctuations.

5.3 Alarm bell Electric - Set outside the cold strorage Asia set 4 21 84
5.4 Thermometer Led type three line Asia set 3 99 297

18/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

Including:
- Main power supply cabinet: Power supply
for electrical equipment such as: pressure
relief valve, door heating resistance, dock
equipment and power socket socket panels.
Update
- 1 main power panel, 18 power socket
October 28th,
panel (8 for robot services, 2 for
5.5 Electrical work for cold storage ARICO / Viet Nam sys 1 12,438 12,438 light and light
anteroom services, 2 for air cooler
power not on
services, 6 for dock ultilities)
scope of Arico
- Cable ladder, trunking / cable tray:
gavalnized steel.
- Power cables are supplied from the main
power supply cabinet to the electrical
equipment of cold storage.

Including:
- Plasstic mushroom head bolt with
stainless steel core.
- HPDE vapor bariers for floor insulation.
- Support system for ceiling panels
Sub-material for installing the (turnbuckle, steel cable...)
5.6 Viet Nam lot 1 199,472 199,472
panel cabinet - Color bond steel U channels for foot of wall
panels,
- Aluminum V angle
- Silicon, sealant, alumium rivet 3.2,
polyurethane foam for filling of slits of the
panels
Fee of tranportation, labor for
installation work project
6 380,744
management for cold storage
cabinet item
Including:
Cost of transportation, customs
- Local tranportation charge for imported
6.1 clearance and unloading goods ARICO lot 1 17,477 17,477
equipment
at the construction site
- Loading goods at construction site
Cost of cranes for installation Crane, truck, forklift for installing panel with
6.2 ARICO lot 1 49,075 49,075
work heigh of 35 meters

19/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

6.3 Cost for finishing installation work Cold storage installation labor ARICO lot 1 278,702 278,702

6.4 Design cost - Designing the warehouse cabinet ARICO lot 1 6,264 6,264
- Temporary office, temporary storage
- Submit the sample.
- Supervising construction, organizing
acceptance
6.5 Project mangement fee ARICO lot 1 29,226 29,226
- T&C
- Operating manual
- Handing over
- Warranty 12 months
REFRIGERATION SYSTEM
ITEM (FOR PHASE 1 AND
B. 1,267,836
READY DESIGNING FOR
INVESTING IN PHASE 2)
1 Screw compressor Lot 1 389,734 389,734.2

Single-stage screw compressors - One running, one standby (100% spare


1.1 MYCOM/Japan Unit 2
running at low stage capacity)
- Model MCN 250SB (E )
- Cooling capacity 625.1 kW (Te = -32°C/Tc = -2°C)
- Shaft power 121.9 kW (Te = -32°C/Tc = -2°C)
- Motor 160 kW (2 Pole/ 3Ph/ 380V) ABB
- Refrigerant NH3
Inverter motor, IP55, IE3
- Motor Type
Frequency Range: 25Hz ~ 60Hz
- Starting method Inverter
Increase
Single-stage screw compressors - One running, one standby (100% spare
1.2 MYCOM/Japan Unit 2 capaicty for chill
running at high stage capacity)
room input
- Model MCN 200L
- Cooling capacity 1,387.2 kW (Te = -2°C/Tc = +35°C)
- Shaft power 258.7 kW (Te = -2°C/Tc = +35°C)
- Motor 315 kW (2 Pole/ 3Ph/ 380V)

20/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]
- Refrigerant NH3
Inverter motor, IP55, IE3
- Motor Type ABB
Frequency Range: 25Hz ~ 60Hz
- Starting method Inverter

1.3 Antivibration for compressor Application for compressure with heavy load Asia set 1
Increase
One running, one standby (100% spare
2 Evaporative Condenser Arico/Vietnam Lot 1 161,489 161,489 capacity c/w
capacity)
compressor
Stainless steel condenser Arico/Vietnam unit 2
- Capacity 1,850 kW
- Condensing Temp. / Web bulb
+35oC / +28oC
temp.
- Fan motor 3 kW x 8 sets
- Pump 3 kW x 02 sets, 2100 lpm/pump
Coil, water basin, casing: Stainless steel
- Material
304
Guntner
3 Air cooler Lot 1 243,709 243,709
(Germany)/Indonesia
- Model: S-AGHN 080.2J325220/412
- Cooling capacity: 150 kW
- Blow down type for specializing in
automation cold storage
- Tubes: Stainless steel
Air cooler for freezing storage 1,2
- Fins: Aluminum unit 4
- ASRS system (-25oC)
- Casing: Galvanized Steel, Powder coated
RAL 9003
- Defrost methode: hot gas
- Double tray with 20 mm insulation
- Fans: 5.5 kW x 4pcs

21/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Model: AGHN 080.2E/27


- Cooling capacity: 45 kW
- Suspended ceiling type
- Tubes: Stainless steel
Air cooler for buffer area - frist
- Fins: Aluminum unit 4
floor (+5oC)
- Casing: Galvanized Steel, Powder coated
RAL 9003
- Attached Streamer for increasing air throw
- Fans: 1.4 kW x 2 pcs

- Model: AGHN 080.2E/27


- Cooling capacity: 45 kW
- Suspended ceiling type
- Tubes: Stainless steel
Air cooler for Picking/Repacking
- Fins: Aluminum unit 3
Area - second floor (+5oC)
- Casing: Galvanized Steel, Powder coated
RAL 9003
- Attached Streamer for increasing air throw
- Fans: 1.4 kW x 2 pcs

- Model: S-AGHN 080.2E/27


- Cooling capacity: 60 kW
- Suspended ceiling type
Air cooler for Room 7 - third floor - Tubes: Stainless steel Increase
- Fins: Aluminum unit 3 capacity for chill
(+5oC ÷ +15oC)
- Casing: Galvanized Steel, Powder coated room input
RAL 9003
- Attached Streamer for increasing air throw
- Fans: 1.4 kW x 2 pcs

22/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]

- Model: S-AGHN 080.2E/27


- Cooling capacity: 60 kW
- Suspended ceiling type
Air cooler for Room 8 - fourth - Tubes: Stainless steel Increase
- Fins: Aluminum unit 3 capacity for chill
floor (+5oC ÷ +15oC)
- Casing: Galvanized Steel, Powder coated room input
RAL 9003
- Attached Streamer for increasing air throw
- Fans: 1.4 kW x 2 pcs

Iincluded:
- 02 fans (fan & motor) for ASRS air coolers.
Spare part set for air cooler fan lot 1 Spare part fans
- 02 fans (fan & motor) for chill room air
coolers
Accessories Extend air duct for ASRS air cooler. lot 1

4 Liquid pump Teikoku/Japan Lô 1 25,553 25,553


Liquid pump for low pressure 2 pumps (one for phase 1, 1 standby)
4.1 unit 2
receiver (-32oC) ready for install one more for phase 2
Flow rate 200 LPM
Head 43 mH
Motor 4.5 kW (3 phase/380V/50Hz)

Liquid pump for low pressure One running, one standby (100% spare
4.2 unit 2
receiver (-1oC) capacity)
Flow rate 200 LPM
Head 36 mH
Motor 3.7 kW (3 phase/380V/50Hz)
Designing and manufacturing according to
5 Pressure vessel ASME standard. Complying with TCVN ARICO/ Viet Nam Lot 1 35,460 35,460
8366:2010.
Low pressure receiver at -32oC
Low pressure receiver at -2oC
High pressure receiver

23/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]
Thermosyphone receiver
Economizer tank
Air purger
Oil receiver
- Gas valve package for refrigeration
system
Danfoss (Denmark),
- All stop valves using SVA with CE
origin according to
certification
6 Gas valve the supplier's Lot 1 111,120 111,120
- Use ICF valve unit for liquid supply unit
manufacturing
for low pressure, air coolers
partition
- Duo safty vavle for high pressure
receiver
Power supply and control
7 ARICO/ Viet Nam Sys. 1 117,598
system
7.1 Main control panel ARICO/ Viet Nam sys. 1 95,215 95,215

PLC, Touch screen HMI displays, modul,… Siemens

ABB, Schneider,
Inverter for the screw compressors set 4
Danfoss or equivalent

MCCB, CB, Thermal relay ABB, Schneider,…


Ammeter, voltmeter, transformer Selec, Omega
Intermediate relay, flow switch Omron, Koino
Switch, light , push button IDEC, Schneider
Electrical enclosure: powder coated steel Viet Nam
Distribution electrical enclosure: Inox Viet Nam
Accessories: cable, termino,… Viet Nam
- To be able to connect with SCADA system
Supervisory Control and Data of whole project.
7.2 sys. 1 17,150 17,150
Acquisition (SCADA) System - To display, control, monitoring/recording
for refrigeration system and temperatures
Development & Runtime
SCADA Software Siemens
Funtion: local cotrol and supervision on PC

24/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]
Communication module,
communication cable
Digital Input and Output; Signal
cable
Controller & display of
temperature, pressure;
communication card
LCD 24ER 23.8inch
Computer screen (PC) Res: 1920x1080, HDMi HP unit 2
IPS, LED backLight
- Intel core i5
CPU - 8GB RAM DDR4, 1TB HDD, DVDRW, HP
Intel HD Graphics
Printer Color LaserJet M154A HP
UPS 1000VA, LCD 230V APC

Temperature monitoring and Connection, mornitoring, control complete Included in item


7.3 sys. 1 -
control system with main control panel and SCADA 7.1
- ASRS room 1: 9 sensors
Change the
- ASRS room 2: 9 sensors
number of
- Buffer room 5: 4 sensors.
Dixell/Eliwell sensor accoring
- Picking room 6: 3 sensors.
the meeting on
- Chill storage 7: 3 sensors.
October 07th
- Chill storage 8: 3 sensors.
- System synchronize with main control
panel and SCADA.
- Included 19 NH3 sensor: each air cooler
Add 17 gas
Refrigeration leak detection have one and two at Machine room. Included in item
7.4 sys. 1 - detector for air
system - Have two level alarm: 7.1
cooler
+ First level: warning to system and
technician to check the leak.
+ Second level: shut down the system.

25/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]
Axial EC fans.
- Operating point at standard speed: 20,000
m3/h, 200 Pa.
Ziehl Add 4 booster
7.5 Booster fan - EC motor for IE5 efficient class. pcs 4 1,308 5,234
Abegg/Germany fans
- Speed control c/w with control panel
according "booster temperature sensor".
- Each ASRS room have two booster fans
Material and accessories for
8 installation referigeration ARICO/ Viet Nam Lot 1 106,019
system
8.1 Piping system lot 1 20,497 20,497
Seamless steel pipe, ASTM A106
GrB/ASTM A 53B Standard, SCH80 for
pipes of size ≤ 40A.
Refrigeration piping and fitting Seamless steel pipe, ASTM A106 China, Taiwan
GrB/ASTM A 53B Standard, SCH40 for
pipes of size > 40A
Using a minimum of 20A pipes
Pipe fitting: Ebow, tee, reducer according to Charming
ASTM A234, SCH40 (Taiwan)/Viet Nam
SeAh zinc coated pipe for section in cold SeAh, Hoa Phat, Binh
Condensate drainage pipe for air
storage Minh / Viet Nam or
coolers
UPVC pipe for the outside of cold storage equivalent

8.2 Insulation work for piping system lot 1 17,232 17,232


ORIKEN, TOSOH,
Insulation material Polyurethane foam
IVICT
Covering pressure vessel Inox 304, 0.3mm thickness Taiwan, Korea
Covering the piping system Inox 304, 0.3mm thickness Taiwan, Korea
Accessories for insulation work:
Viet Nam
rive, drill,…
8.3 Cable and trunking lot 1 36,497 36,497
1 core power cable CV Cadivi, LS, Taisin
Multicore power cable CVV Cadivi, LS, Taisin
Cadivi, Taisin,
Control cable CVV
SanJing

26/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]
Conduit wire PVC pipe Viet Nam
Trunking, cable ladder Gavalnized steel trunking with cover Viet Nam
8.4 Refrigerant, oil lot 1 15,459 15,459
Refrigerant Amonia (NH3) Indonesia/ India kg 7,000
Oil Semi-synthetic oil: CPI/Total liter 2,496
SS400 Steel or equivalent
The platform for air cooler
Hot-dip galvanized
8.5 maintanance work in freezing set 4 1,692 6,766
Guaranteed for 2 people mantainance
room 1,2
manipulation
Auxiliary supplies, installation
8.6 accessories for refrigeration Viet Nam lot 1 9,568 9,568
system
Supports for piping system and
U-shaped, V-galvanized steel
equipment
Rails Round steel, galvanized steel thread
Welding stick , screw, rivet,…
Fee of tranportation, labor for
installation work project
9 77,153
management for refrigeration
system item
Including:
- Local tranportation charge for imported
Cost of transportation, customs
equipment
9.1 clearance and unloading goods ARICO lot 1 3,229 3,229
- Loading goods at construction site
at the construction site
- Crane fee for moving the equipment up to
4th floor
Cost of cranes, cranes for Kato Crane for installing refrigeration
9.2 ARICO lot 1 7,533 7,533
installation system
Refrigeration system installation labor
9.3 Cost for finishing installation work ARICO lot 1 55,422 55,422
X - ray 5% for piping
9.4 Design cost - Designing the refrigeration system ARICO lot 1 3,746 3,746

27/29
ID Description Technical specifications Brand/ Origin Unit Qty. Unit price Amount Note

(USD) (USD)
[1] [2] [3] [4] [5] [6] [7] [8] = [6] * [7] [9]
- Temporary office, temporary storage
- Submit the sample.
- Supervising construction, organizing
acceptance
9.5 Project mangement fee ARICO lot 1 7,223 7,223
- T&C
- Operating manual
- Handing over
- Warranty 18 months
Total price 3,612,880 (USD)
Special discount 3.5%
Total price afer discount 3,486,430 (USD)
VAT 10% 348,643 (USD)
Total price, including VAT 3,835,073 (USD)
In words: US Dollars Three Million and Eight Hundred Thirty Five Thousand and Seventy Three only.
II. Payment Term:
* We proposed the payment terms as below:
1/ Advance payment: 40% of total contract value as down payment after signing the contract.
2/ Second payment:
* Up to 80% total contract value will be paid after the main equipment regrouping to at site( not including import equipment): Panel PIR, Insulated door, Control Panel,
pressure vessel, gas pipe, insulation material, cable, lighting system
* Up to 90% total contract value will be paid after the imported equipment regrouping to at site: Compressors, Air Cooler, Evaporative condenser, gas valve, dock equipment
The whole second payment can be paid for each delivery.
3/ Third payment: Up to 95% total contract value will be paid before T&C and hand-over.
4/ Final payment: Payment of the remaining value of the contract value to be made days since T&C and hand-over. We will give you Payment Guarantee 5% of total contract
from Bank before guarantee of construct
* All Payment will be transferred by VND with the exchange rate at the moment of transferral to:
ARICO
Lot 25-27, Trung Tam Road, Tan Tao Industrial Zone, Tan Tao A Ward, Binh Tan district, Ho Chi Minh City, Viet Nam.
BANK
VIETINBANK - 6 Branch, HCMC
Floor 1A, 1B, Floor 2, Floor 11, Building 635B, Nguyen Trai Street, District 11, District 5, HCMC. Vietnam
Account No.: 116.000.187.479
III. Delivery Time and Work Location and Warranty term
1/ Implementation time schedule of the contract: Completing the installation work and acceptance test in 7-9 months, from the date of advances payment
Does not include public holidays.
2/ Site location: Lot G7, Road Number 6, Song Than 2 Industrial Zone, Di An Ward, Di An District, Binh Duong Province, Vietnam

28/29
3/ The equipment we will provide is 100% new.
4/ Warranty term: the Warranty period for the Works described in this Offer is 18 months from the date of Acceptance but not more than 22 months from finishing installtion
work, whichever comes first. The Warranty covers replacement free of charge (excluding carriage and installation) of any parts found to contain any defects in workmanship
and material that certified by the third party selected by the Buyer and the Seller, and not liability for any defects caused by not comply with guidance from the instruction
of manufacture. Handling and local duty costs for warranty are borne by the client. The Warranty does not cover any consequantial damage or loss.
IV. Validity
This offer is valid for 30 days from the date of this quotation.
VI. Exclusion:
1/ All concrete works relevant to the floor and foundation for the execution of the mentioned equipment. Concrete floor finishing for cold storage; Len wall and vent warehouse
background. Frame for wall panel of ASRS cold storage
2/ The steel frame have to be strong enough for supporting ceiling, wall panel; air coolers; frame and platform of Blow Down air coolers; the piping system of refrigeration system
3/ Expenses for dismantling and re-assembling basic construction items, which become entangled in the process of transporting equipment and supplies to the location of
installation and construction;
4/ Supply main power cable to control panel of refrigeration system.
5/ Reinforced steel frame for wall panel, steel pillar / steel frame to protect cold storage door.
6/ Supply additional water to the evaporative condenser
7/ Supplying electrical, water supporting testing and commissioning work
8/ Cost of using the system with the local registry (if any)
9/ Any other items not specifically included in this quotation.
We hope that our offer will meet your requirements and look forward to hearing from you soon. If you need any further information, please do not hesitate to contact us.
Thank you very much for your co-operation.
CUSTOMER'S ACCEPTANCE ASIA REFRIGERATION INDUSTRY COMPANY