Professional Documents
Culture Documents
9.75
(247.7)
I2 (+) 1A
I2 (+) 5A
I2 (-) V Bus A
V Bus B PMG A
I1 (+) 1A V Bus C
V Bus N PMG B
I1 (+) 5A
TB6 PMG C
I1 (-)
SHLD 1
SHLD 1
SHLD 2 TB3
14.00
SHLD 2 TB1
(355.6)
EXC (+)
EXC (-) 4
ControlNet
Address
Combination TB2 BAT (+)
BAT (-)
FLT
5
Generator RD RLY
CH GND
TB7
Manufactured by VREF (+)
VREF (-)
1/4 - 20 Ground
B as le rE lec ric SHLD 3
Stud (2 Places) R
Factory
SHLD 3 Test
A-COM Port
DANGER EX-D (+)
HAZARDOUS VOLTAGE CAN CAUSE SHOCK, BURNS, OR DEATH. EX-D (-)
1) DISCONNECT AND LOCK OUT ALL POWER SOURCES AND,
2) SHORT ALL CURRENT TRANSFORMER SECONDARIES BEFORE SERVICING.
LS (+)
MORE THAN ONE LIVE CIRCUIT. SEE DIAGRAM.
LS (-)
ADVERTISSMENT: CET EQUIPEMENT RENFERME PLUSIEURS CIRCUITS SOUS TENSION, VOIR LE SCHEMA SHLD 4
8.25
(209.6)
ControlNet 1.5
Connections
1407-CGCM
CAT
CO
COMBINATIONGENERATOR
NTROL MODUL
FORHAZ. LOC. 3PA7
LI STEDIND.CON.T EQ.
Notes:
C
CN
B
UL
CO
R
MM
H SOT FRN
SFRN
SER
B
CN
A
REV
A
CLASSI DIVI SI ON 2, GROUSPA, B,C,ORD
THISEQUIPME
TEMPERA
NTISSUITABL
E E xnL I ICT3
TUREI NDEX * T3
II 3G
DEM
EFORUSE IN
Redundanc
6.26
y Port
(159.0)
.
CURRENTSEN
VO
FAULT &REDUNDANCYOUTPUTS
PM
GENERA
EXC
DC SUPPLYINPUT
G POWERINPUT
LTAGEADJUSTI NPUT
+/- 10 VDC
0.5A@24VDC
0-15ADC
UTS
MA
DEIN
U.S.A.
Ground Studs
Electical Connections CGCM connections are dependent on the application and excitation
scheme. All inputs or outputs may not be used in a given installation.
Incorrect wiring may result in damage to the unit. Check the part
number to insure that you have the correct unit before connecting and
applying power.
The CGCM terminals should be connected with copper wire rated for
a minimum of 600 volts. General appliance wire is acceptable. The
wire need not be rated for temperatures beyond 70°C (158°F).
CGCM terminals are located on the front, bottom, and right panel of
the unit. The nine-pin connector on the bottom of the unit is used for
communications between CGCMs in a redundant system. Suggested
torque for terminal screws is 9 inch-pounds (1.0 Nm).
Notes: