40 1997 ASHRAE Fundamentals Handbook (SI)

The CLTD/SCL/CLF method is a one-step, hand calculation pro- SYNTHESIS OF HEAT GAIN AND COOLING LOAD
cedure, based on the transfer function method (TFM). It may be CONVERSION PROCEDURES
used to approximate the cooling load corresponding to the first three
modes of heat gain (conductive heat gain through surfaces such as Exterior Roofs and Walls
windows, walls, and roofs; solar heat gain through fenestrations; This method was developed by using the TFM to compute one-
and internal heat gain from lights, people, and equipment) and the dimensional transient heat flow through various sunlit roofs and
cooling load from infiltration and ventilation. The acronyms are walls. Heat gain was converted to cooling load using the room trans-
defined as follows: fer functions for rooms with light, medium, and heavy thermal char-
acteristics. Variations in the results due to such varying room
CLTD—Cooling Load Temperature Difference constructions and other influencing parameters discussed in the
SCL—Solar Cooling Load TFM description are so large that only one set of factors is presented
CLF—Cooling Load Factor here for illustration. All calculations for data tabulated were based
on the sol-air temperatures in Table 1. The inside air temperature
The following sections give details of how the CLTD/SCL/CLF was assumed to be constant at 25°C (cooling system in operation 24
technique relates to and differs from the TFM. The sources of the h/day, seven days a week). The mass of building and contents was
space cooling load, forms of equations to use in the calculations, “light to medium.” For application of CLTD/SCL/CLF techniques,
appropriate references, tables, are summarized in Table 29. refer to McQuiston and Spitler (1992).

Table 29 Procedure for Calculating Space Design Cooling Load by CLTD/SCL/CLF Method
External Cooling Load Power
Roofs, walls, and conduction through glass
qp = PEF CLF (15)(16)(17)(50)
q = UA(CLTD) (41)
U = design heat transfer coefficient for roof or wall from Chapter P = horsepower rating from electrical plans or manufacturer’s
24, Table 4; or for glass, Table 5, Chapter 29 data
A = area of roof, wall, or glass, calculated from building plans EF = efficiency factors and arrangements to suit circumstances
CLTD = cooling load temperature difference, roof, wall, or glass
CLF = cooling load factor, by hour of occupancy, Table 37
Solar load through glass
Note: CLF = 1.0 with 24-h power operation and/or if cooling off at night or
q = A(SC)(SCL) (43) during weekends.
SC = shading coefficient: Chapter 29
SCL = solar cooling load factor with no interior shade or with Appliances
shade, Table 36.
qsensible = qinput FU FR (CLF) (18)(46)
Cooling load from partitions, ceilings, floors or
q =UA(to – trc) (8) qsensible = qinput FL (CLF) (19)(46)
U = design heat transfer coefficient for partition, ceiling, or floor,
from Chapter 24, Table 4
A = area of partition, ceiling, or floor, calculated from building qinput = rated energy input from appliances—Tables 5 through 9, or
plans manufacturer’s data
tb = temperature in adjacent space FU, FR, = usage factors, radiation factors,and load factors from the
FL General Principles section
trc = inside design temperature (constant) in conditioned space
CLF = cooling load factor, by scheduled hours and hooded or not;
Internal Cooling Load Tables 37 and 39
People
Note 1: CLF = 1.0 with 24-h appliance operation and/or if cooling off at
qsensible = N(Sensible heat gain)CLF (44)
night or during weekends.
Note 2: Set latent load = 0 if appliance under exhaust hood.
qlatent = N(Latent heat gain) (45)
N = number of people in space, from best available source. Ventilation and Infiltration Air
Sensible and latent heat gain from occupancy—Table 3,
or Chapter 8; adjust as required qsensible = 1.23Q (to − ti) (25)
CLF = cooling load factor, by hour of occupancy, Table 37
Note: CLF 1.0 with high density or 24-h occupancy and/or if cooling off at
night or during weekends. qlatent = 3010Q (Wo − Wi) (23)
Lights
qel = W Ful Fsa (CLF) (9)(46)
qtotal = 1.20Q (ho − hi) (20)
W = watts input from electrical plans or lighting fixture data
Ful = lighting use factor, as appropriate Q = ventilation from ASHRAE Standard 62; infiltration from
Fsa = special allowance factor, as appropriate Chapter 25, L/s
CLF = cooling load factor, by hour of occupancy, Table 38 to, ti = outside, inside air temperature, °C
Note: CLF = 1.0 with 24-h light usage and/or if cooling off at night Wo, Wi = outside, inside air humidity ratio, kg (water)/kg (dry air)
or during weekends. Ho, Hi = outside, inside air enthalpy, kJ/kg (dry air)