Professional Documents
Culture Documents
5.1 INTRODUCTION
The CLISIS remote tilting table can be installed in a room that has been officially
approved for the operation of radiological equipment of the same class.
In addition, proper operation of the unit can be achieved only if the environmental
characteristics specified in the following sections are strictly observed.
WARNING:
In order to properly install the CLISIS remote tilting table, the use of special
accessories for the installation might be necessary. The accessories to be used
depend on the room constructions and should be ordered before the installation
starts.
The unit has been designed to operate in a room respecting the following
environmental conditions:
1. The construction and load capability of the ceiling are sufficient for the
installation of the unit.
4. Sufficient consideration has been given to the room layout with respect to
minimum clearances between walls and the equipment as specified in the unit
manual.
5. Carefully evaluate the best fixation system to be use for the ceiling rails as
described in the following layout example.
The minimum allowed room height, with standard 20 mm base spacer is 2550 mm as shown in the
following figure.
In case the unit must be installed using a different base spacer, the room minimum height
requirement must be increased of the same quantity.
4200
LEGEND:
1. CLISIS 90/20 TABLE
2 2. GENERATOR POWER CABINET
3. CLISIS OPERATIVE LIMIT
4. CONTROL DESK TABLE
5. CLISIS CONSOLE
6. ROOM POWER ELECTRICAL BOARD
7. ANTI-X GLASS 1200x800 (suggested)
8. 18" LCD MONITOR ON TROLLEY
4800
3
1 7
8
DOOR MICROSWITCH
4
RADIATION HAZARD LAMP
SP.
5 ROOM EMERGENCY SWITCH H=1700mm
6
Modifiche
4200
Cable exit for Clisis.
6mm thickness
removable floor cover.
"A" Detail
Cable exit
for cabinet FLOOR LEVEL
260
6
80
Totally inspectionable
Under Floor conduit.
4800
200
("A" Detail)
15
cables exit is as shown in the drawing.
350
1250
OVERFLOOR PLATE
AREA = 1.75mq
PLATE WEIGHT = 220Kg
4800
MAXIMUM LOAD = 1500Kg
MAXIMUM LOAD ON BOLTS = 300Kg
BOLTS M12x35 CL 8.8
"SLM12" ANCHORS - FISCHER
1400
SEE "C" DETAIL
"C" DETAIL
SP.
Modifiche
4200
LEGEND:
1. CLISIS 90/20 TABLE
2. GENERATOR POWER CABINET
2
3. CLISIS OPERATIVE LIMIT
4. CONTROL DESK TABLE
5. CLISIS CONSOLE
6. ROOM POWER ELECTRICAL BOARD
7. ANTI-X GLASS 1200x800 (suggested)
4500
7
1
8
4
DOOR MICROSWITCH
6
Modifiche
"A" Detail
Cable exit for cabinet FLOOR LEVEL
260
6
80
Totally inspectionable
Under Floor conduit.
4500
("A" Detail)
200
Modifiche
4200
Clisis underfloor plate at
Place the underfloor plate so that the Room floor floor level fixed and covered Floor coating
Room floor
coating
cables exit is as shown in the drawing. coating with the same floor material. free zone.
80
515
Clisis Support
Area.
Floor coating
890
free zone.
Clisis Support Area. "B" detail
Floor coating free zone.
890
UNDERFLOOR PLATE
SUPPORT AREA = 0.45mq
4500
515
SP.
Modifiche
The CLISIS remote tilting table must be completed with a special set of cables that
allows the proper operation of the additional accessories.
Because each installation has its own typical layout, in this section are detailed the
lengths of the standard cables supplied with the systems, showing also the correct
way to route the cables.
In case during the design of the room layout, it is necessary to modify the standard
length of a group of cables, it is responsibility of the installer to clearly specify this
configuration change.
In this section has been also added the system interconnection diagrams for the
most complete configuration supported by the CLISIS table. Such drawings show all
physical connections between the internal parts of the CLISIS remote tilting table
and the system itself with other accessories.
For additional information the installer must refer to section 7 of this manual.
WARNING:
Before starting the installation, it is necessary for the installer verify that all
accessories or interface cables are present and delivered in the lengths
defined during the room layout design phase.
The CLISIS remote tilting table must be fixed to the floor using three different methods:
This fixation method is allowed when the floor of the room is strong enough to bear the entire
system weight on the base surface as shown in the following figure:
70 70 70
N°8 CLISIS BASE
30 340 70 FIXATION
25
CLISIS BASE FIXING
LOADING AREA = 0.45mq
UNIT WEIGHT = 1100Kg
400
515
Clisis Base TOTAL LOAD = 1300Kg
MAXIMUM LOAD ON BOLTS = 300Kg
30 620
N°8 - Ø15 HOLES
890
FLOOR
FLOOR
NB: IF CONCRETE IS
4 CLASS Rc > 25N/mm 5 4
IMPORTANT NOTICE:
It is responsibility of the installer to select the fixation method that grants the
correct unit anchoring in function of the constructive characteristics of the floor
itself.
In order to meet the requirements if the EN60601-1 regulation it is also necessary that the
installer interpose between the floor and the unit base the 20 mm spacer p/n SXAA014 as
shown in the previous figure.
This the preferred fixation method to be used when the floor depth is enough to allow the
installation of the Mecall base plate SXAA04. In this case the base plate must be immured
into the floor as detailed in the following figure:
80
UNDERFLOOR PLATE
515
1330
50
1200
CLISIS BASE FIXATION
1
Clisis underfloor plate at floor 2 4
13
level fixed and covered with Floor coating
Room floor Room floor 3
the same floor material. free zone.
coating coating 5
FLOOR
15
50
80
sez. A - A
IMPORTANT NOTICE:
It is responsibility of the installer to grant the correct anchoring of the base plate in
function of the constructive characteristics of the floor itself.
80
UNDERFLOOR PLATE
515
1330
50
CLISIS BASE FIXATION
1200 1
2 4
13
Floor coating 3
Clisis underfloor plate at floor free zone.
level fixed and covered with 5
Room floor Room floor
the same floor material. 6
coating 20mm spacer coating
FLOOR
15
50
80
This fixation method is recommended when the floor depth is not enough to allow the
installation of the under floor installation plate and/or the floor of the room is not strong
enough to bear the entire system weight laying on the table base. In this case the installer
must use the optional over floor installation plate p/n SXAA03 to distribute the weight on a
larger surface and to offer a better and easier fixation to the floor as detailed in the following
figure:
1400
50 OVERFLOOR PLATE
50 195 810
50
Clisis Base
N°8 FLOOR FIXATION
1150
3
15
FLOOR 5
FLOOR
15
NB: IF CONCRETE IS
4 CLASS Rc > 25N/mm
1 - N°1 SCREW TCCE UNI5931 CL8.8 M12X35
2 - N°1 SPRING WASHER Ø 12
1 - N°1 SCREW TSCE UNI5933 CL10.9 M12X90 3 - N°2 PLAIN WASHER Ø 12
2 - N°1 WASHER Ø i 10.25 Ø e 30 5p.7 sv.90° 4 - CLISIS BASE
3 - OVER FLOOR PLATE 5 - OVER FLOOR PLATE
4 - N°1 BOSS FISCHER SLM 12
IMPORTANT NOTICE:
It is responsibility of the installer to grant the correct anchoring of the base plate in
function of the constructive characteristics of the floor itself.
1400
50 OVERFLOOR PLATE
50 195 810
50
Clisis Base
N°8 FLOOR FIXATION
1150
N°8 - M12 HOLES
LOADING AREA = 1.75mq
N°8 CLISIS BASE PLATE WEIGHT = 220Kg
FIXATION TOTAL LOAD = 1500Kg
MAXIMUM LOAD ON BOLTS = 300Kg
13
2
3
15
FLOOR 5
6
FLOOR
NB: IF CONCRETE IS
15
All the control electronics of the CLISIS remote tilting table has the 0V grounded.
It is consequently clear that a grounding error in the installation or a ground
connection made with a cable of inadequate section may degrade both reliability
and safety level of the unit.
1. Check that the central ground terminal in the examination room has the
characteristics specified in the safety norms of the country. In particular a
ground resistance lower than 2 is suggested.
2. Connect the CLISIS central ground terminal directly to the central ground
terminal of the power distribution box by means of a 4 mm² singe conductor
if the distance is less than 10 m. The cable section must be increased
proportionally in case of higher distances.
3. Connect all CLISIS ground internal cables only to the central ground terminal
of the unit located in the upper side of the power cabinet as shown in the
following figure. Make sure that the brass fixation screws has been properly
tightened
4. Do not add other ground connections that might involve sections of the
system, in order to avoid the possibility to cause ground loops.
The CLISIS remote tilting table requires the connection to a single-phase line with
the following characteristics:
The standard configuration of the units includes the 400V 3-phase insulation
transformer. In case the line voltage is different from the standard one, the installer
refer to section 5.8 for further information.
If possible, it is also a good norm to apply the following rules for the line connection:
1. The input line must be totally independent from any other lines that might
create interference.
2. The main line cable is laid in conduit separate from the cable conduit.
3. The section of the line cables must be minimum 4.0 mm.
4. In case the input line characteristics does not match the requirements it is a
good practice to install a line conditioner.
The input line cable must be connected at the CLISIS power cabinet line terminals,
as detailed in the following figures.
The CLISIS line input must be protected by means of a safety switch, calibrated
for a maximum leakage current of 30 mA.
The input line can be disconnected from the unit turning in OFF position the line
switch mounted on the front panel of the power cabinet as shown in the following
figure:
The room power distribution box must be designed not only to meet the technical
requirements previously specified but also to comply with the requirements of the x-
ray generator and of the image processor (for more details see the related service
documentation). In particular, the general requirements of the room input line is:
In any dangerous situation, or in case a movement can not be stopped, the operator
must hit immediately one of these switches. The power circuit of the CLISIS table is
immediately switched off, but all other units will continue to operate normally.
The emergency switch must be re-enabled only if the operator is absolutely sure
that the danger condition has been removed.
IMPORTANT NOTICE:
D
M
MA
TE
A
N
G S
EM Y
ENT S
D
EM
MA
A
T
N
G S
EM Y
ENT S
D
M
MA
TE
A
N
G S
EM Y
ENT S
D
EM
MA
A
N
T
GE S
ME N T S Y
D
MA
EM
A
T
N
G S
EM Y
ENT S
The line voltage input can not be selected by installer. In fact the primary winding of
the CLISIS insulation transformer is voltage specific and can not be adapted.
In case the line voltage is different from 400V, it is necessary that the unit is factory
configured for the line ordering one of the following options: