RATING : 40 / 50 MVA 66 / 11.

5 kV
CUSTOMER: M/s. MUNDRA SOLAR TECHNOLOGY LIMITED , DISTRICT KUTCH, GUJARAT, INDIA
PROJECT NAME: 2GW WAFER & INGOT PLANT, MUNDRA, KUTCH
W.O.No.: 5964 Date & Rev.No.: 21.11.2022 & R0
LOAD LOSS CALCULATION FOR 40 / 50 MVA ,
66 / 11.5kV TRANSFORMER

LOAD LOSS CALCULATION (@ NORMAL TAP)

Load Loss Calculation = 3 x I2R + Eddy Current Loss + Stray Loss

where,

Resistance ( R ) @75 °C = 0.2812 ohms at normal tap on HV and 0.00271 ohms at LV


Current ( I ) = 252.525 amps at normal tap on HV and 2510.219 amps at LV
Eddy Current + Stray Loss = 19.5 kW (approx.)
Stray Loss = 7 kW

Load loss Calculation = 3 x ((252.525 x 252.525 x 0.2812) + ( 2510.219 x 2510.219 x 0.00271))


+ 19500

= 124.52 kW

Load loss calculated is 124.52 kW which is lower than the guaranteed loss of 125 kW(max) @ the rated tap

ADD COVER SHEET IN AS BUILT


DRAWING

Categories:

 Cat-I Approved. Good for Manufacturing/Construction/Fabrication

AMIT Digitally signed  Cat-I* Approved with minor comments. No resubmission is required.
by AMIT
To be incorporated in As-Built. Good for Manufacturing/
AGRA
AGRAWAL
Date:
2022.11.28
Construction/ Fabrication subject to incorporation of comments.
WAL 16:27:37
+05'30'

Reviewer
 Cat-II Approved. Released for Manufacturing/fabrication/construction
subjected to incorporation of comments. Modification as
Noted. Resubmission is required.

Amit  Cat-III Not Approved

Asha
Digitally signed by


Amit Asharfilal
Date: 2022.11.28
17:22:45 +05'30'
Cat-IV For Information & Records

rfilal
Approver Note: “Approval of this document does not absolve the Contractor/ Supplier/
Fabricator from fulfilling Contractual obligations in any way”

Prepared By: SS Checked By: RP Approved By: RP

ALL INFORMATION IN THIS DOCUMENT IS CONFIDENTIAL AND SHOULD NOT BE USED WITHOUT PRIOR CONSENT OF INDO TECH TRANSFORMERS
LIMITED