You are on page 1of 35

AVERAGE ILLUMINATION CALCULATION SHEET

GENERAL INFORMATION:
PROJECT IDENTIFICATION: UNIT A
AVERAGE MAINTAINED ILLUMINANCE: 150 LUX
LUMINAIRE DATA:
MANUFACTURER:
CATALOG NUMBER: ITEM NO. 25
LAMP DATA:
TYPE AND COLOR: RAPID START, COOL WHITE
NUMBER OF LAMPS/LUMINAIRE: 1
TOTAL LUMENS/LUMINAIRE: 3675

LENGTH OF THE ROOM = 7.8000 m


WIDTH OF THE ROOM = 5.0500 m
HEIGHT OF THE ROOM =4m

hCC = 0m

hRC = 3.2m

hFC = 0.8m

I. DATA:
1. AVERAGE MAINTAINED LUMINANCE: 150 LUX

2. LUMINAIRE DATA: ITEM NO. 25


DESCRIPTION: 1-50 W, 230 V, 60 HZ, COOL WHITE,
FLUORESCENT LAMP

3. AREA ATMOSPHERE:VERY CLEAN

4. ROOM SURFACE REFLECTANCES:


CEILING, ρC = 80 %
WALL, ρW = 50 %
FLOOR, ρF = 20 %
5. OPERATION CHARACTERISTICS: 8 HOURS

6. CLEANING CYCLE: ANNUALLY

II. CALCULATION:

1. DETERMINING CAVITY RATIOS:

CEILING CAVITY RATIO, CCR:

L+W
CCR= ∙5 hcc
L xW

7.8+5.05
CCR= ∙5 (0)
7.8 x 5.05

=0

ROOM CAVITY RATIO, RCR:


L+W
RCR= ∙5 hrc
L xW

7.8+5.05
RCR= ∙5 (3.2)
7.8 x 5.05
= 5.2196

FLOOR CAVITY RATIO, FCR:


L+W
FCR= ∙5 hfc
L xW

7.8+5.05
FCR= ∙5 (0.8)
7.8 x 5.05

= 1.3049

2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρcc:


% BASE REFLECTANCE, ρC = 80 %
% WALL REFLECTANCE, ρW = 50 %
CEILING CAVITY RATIO, CCR = 0
ρCC = 80 %
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρfc:
% BASE REFLECTANCE, ρF = 20 %
% WALL REFLECTANCE, ρW = 50 %
FLOOR CAVITY RATIO, FCR = 1.3049
ρFC = 18 %

4. OBTAIN COEFFICIENT OF UTILIZATION, Cu:


ρCC = 80 %
ρW = 50 %
RCR = 5.2196
CU = 0.53902

INTERPOLATION:
5−5.2196 0.55−Cu
=
5−6 0.55−0.50

= 0.53902

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD:


Item # 25

THE LIGHT DISTRIBUTION CURVE IS SEMI-DIRECT


% EXPECTED DIRT DEPRECIATION FACTOR = 8%
RCR = 4.4
RSDD = 94%

6. LAMP LUMEN DEPRECIATION FACTOR, LLD:


LLD = 86.67 %

INTERPOLATION:
6−8 87−LLD
=
6−12 87−86
= 86.67 %
7. LAMP BURN-OUT FACTOR (LBO):
LBO = 100%

8. LUMINAIRE DIRT DEPRECIATION FACTOR (LDD) AT EVERY 12


MONTHS CLEANING CYCLE, CLEANING CYCLE IS CLEAN,
MAINTENANCE CATEGORY II.
LDD = 93 %

9. TOTAL LIGHT LOSS FACTOR (LLF):


LLF = (RSDD) (LLD) (LBO) (LDD)
= (94%) (86.67%) (100%) (93%)
= 75.766914%

10. TOTAL NUMBER OF LUMINAIRES, N:


N = (ILLUMINANCE) (AREA OF THE ROOM)
(LUMENS/LUMINARE) (Cu) (LLF)
= (150) (7.8 x 5.05)
(3675) (0.54) (75.77%)

= 3.9367 LUMINAIRES

L∙N
11. C =
√ W
7.8(3.94 )
=
√ 5.05
C = 2.47 ≈ 3

N
R=
C
3.94
=
2.47
R = 1.60 ≈ 2

XL = (L/R) = (7.8/1.60) = 4.88m


XW= (W/R) = (5.05/1.60) = 3.16m

12. ACTUAL ILLUMINANCE:


ILLUMINANCE = (N) (LUMENS/LUMINAIRE) (Cu) (LLF)
(AREA OF THE ROOM)
= (4) (3675) (0.54) (75.77%)
(7.8 x 5.05)
= 152.69 LUX

GENERAL INFORMATION:
PROJECT IDENTIFICATION: UNIT 1A, 2A, 3A, 4A
AVERAGE MAINTAINED ILLUMINANCE: 150 LUX
LUMINAIRE DATA:
MANUFACTURER:
CATALOG NUMBER: ITEM NO. 5
LAMP DATA:
TYPE AND COLOR: RAPID START, DAYLIGHT
NUMBER OF LAMPS/LUMINAIRE: 1
TOTAL LUMENS/LUMINAIRE: 6400

LENGTH OF THE ROOM = 5.1000 m


WIDTH OF THE ROOM = 3.4000 m
HEIGHT OF THE ROOM =4m

hCC = 0m

hRC = 3.2m

hFC = 0.8m
I. DATA:
1. AVERAGE MAINTAINED LUMINANCE: 150 LUX

2. LUMINAIRE DATA: ITEM NO. 5


DESCRIPTION: 1-20 W, 230 V, 60 HZ, DAYLIGHT, PIN LIGHT

3. AREA ATMOSPHERE:VERY CLEAN

4. ROOM SURFACE REFLECTANCES:


CEILING, ρC = 80 %
WALL, ρW = 50 %
FLOOR, ρF= 20 %

5. OPERATION CHARACTERISTICS: 8 HOURS

6. CLEANING CYCLE: ANNUALLY

II. CALCULATION:

1. DETERMINING CAVITY RATIOS:

CEILING CAVITY RATIO, CCR:

L+W
CCR= ∙5 hcc
L xW

5.1+3.4
CCR= ∙ 5(0)
5.1 x 3.4

=0

ROOM CAVITY RATIO, RCR:


L+W
RCR= ∙5 hrc
L xW

5.1+3.4
RCR= ∙ 5(3.2)
5.1 x 3.4

= 7.8431

FLOOR CAVITY RATIO, FCR:


L+W
FCR= ∙5 hfc
L xW

5.1+3.4
FCR= ∙ 5(0.8)
5.1 x 3.4

= 1.9608

2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρcc:


% BASE REFLECTANCE, ρC = 80 %
% WALL REFLECTANCE, ρW = 50 %
CEILING CAVITY RATIO, CCR = 0
ρCC = 80 %

3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρfc:


% BASE REFLECTANCE, ρF = 20 %
% WALL REFLECTANCE, ρW = 50 %
FLOOR CAVITY RATIO, FCR = 1.9608
ρFC = 18 %

4. OBTAIN COEFFICIENT OF UTILIZATION, Cu:


ρCC = 80 %
ρW = 50 %
RCR = 7.8461
CU = 0.3863

INTERPOLATION:
7−7.8431 0.42−Cu
=
7−8 0.42−0.38
= 0.3863

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD:


Item # 5
THE LIGHT DISTRIBUTION CURVE IS SEMI-DIRECT
% EXPECTED DIRT DEPRECIATION FACTOR = 8%
RCR = 7.8431
RSDD = 93%

6. LAMP LUMEN DEPRECIATION FACTOR, LLD:


LLD = 86.67 %

INTERPOLATION:
6−8 87−LLD
=
6−12 87−86
= 86.67 %

7. LAMP BURN-OUT FACTOR (LBO):


LBO = 100%

8. LUMINAIRE DIRT DEPRECIATION FACTOR (LDD) AT EVERY 12


MONTHS CLEANING CYCLE, CLEANING CYCLE IS VERY CLEAN,
MAINTENANCE CATEGORY IV.
LDD = 94 %

9. TOTAL LIGHT LOSS FACTOR (LLF):


LLF = (RSDD) (LLD) (LBO) (LDD)
= (93%) (86.67%) (100%) (94%)
= 75.77%

10. TOTAL NUMBER OF LUMINAIRES, N:


N = (ILLUMINANCE) (AREA OF THE ROOM)
(LUMENS/LUMINARE) (Cu) (LLF)
= (150) (5.1 x 3.4)
(3200) (0.39) (75.77%)
= 7.04 LUMINAIRES

L∙N
11. C =
√W
5.10(7)
=
√3.4
C = 3.25 ≈ 3

N
R=
C
7.04
=
3.25
R = 2.17 ≈ 2

XL = (L/R) = (5.10/2.17) = 2.35m


XW= (W/R) = (3.4/2.17) = 1.57m

12. ACTUAL ILLUMINANCE:


ILLUMINANCE = (N) (LUMENS/LUMINAIRE) (Cu) (LLF)
(AREA OF THE ROOM)
= (7) (3200) (0.39) (75.77%)
(5.1 x 3.4)
= 381.73 LUX

GENERAL INFORMATION:
PROJECT IDENTIFICATION: UNIT 1B, 2C, 3B, 4B
AVERAGE MAINTAINED ILLUMINANCE: 150 LUX
LUMINAIRE DATA:
MANUFACTURER:
CATALOG NUMBER: ITEM NO. 5
LAMP DATA:
TYPE AND COLOR: RAPID START, DAYLIGHT
NUMBER OF LAMPS/LUMINAIRE: 1
TOTAL LUMENS/LUMINAIRE: 6400

LENGTH OF THE ROOM = 5.1000 m


WIDTH OF THE ROOM = 3.4000 m
HEIGHT OF THE ROOM =4m

hCC = 0m

hRC = 3.2m

hFC = 0.8m

III. DATA:
1. AVERAGE MAINTAINED LUMINANCE: 150 LUX

2. LUMINAIRE DATA: ITEM NO. 5


DESCRIPTION: 1-20 W, 230 V, 60 HZ, DAYLIGHT, PIN LIGHT

3. AREA ATMOSPHERE:VERY CLEAN

4. ROOM SURFACE REFLECTANCES:


CEILING, ρC = 80 %
WALL, ρW = 50 %
FLOOR, ρF= 20 %

5. OPERATION CHARACTERISTICS: 8 HOURS

6. CLEANING CYCLE: ANNUALLY


IV. CALCULATION:

1. DETERMINING CAVITY RATIOS:

CEILING CAVITY RATIO, CCR:

L+W
CCR= ∙5 hcc
L xW
5.1+3.4
CCR= ∙ 5(0)
5.1 x 3.4

=0

ROOM CAVITY RATIO, RCR:


L+W
RCR= ∙5 hrc
L xW

5.1+3.4
RCR= ∙ 5(3.2)
5.1 x 3.4

= 7.8431

FLOOR CAVITY RATIO, FCR:


L+W
FCR= ∙5 hfc
L xW

5.1+3.4
FCR= ∙ 5(0.8)
5.1 x 3.4

= 1.9608

2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρcc:


% BASE REFLECTANCE, ρC = 80 %
% WALL REFLECTANCE, ρW = 50 %
CEILING CAVITY RATIO, CCR = 0
ρCC = 80 %

3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρfc:


% BASE REFLECTANCE, ρF = 20 %
% WALL REFLECTANCE, ρW = 50 %
FLOOR CAVITY RATIO, FCR = 1.9608
ρFC = 18 %

4. OBTAIN COEFFICIENT OF UTILIZATION, Cu:


ρCC = 80 %
ρW = 50 %
RCR = 7.8461
CU = 0.3863

INTERPOLATION:
7−7.8431 0.42−Cu
=
7−8 0.42−0.38
= 0.3863

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD:


Item # 5

THE LIGHT DISTRIBUTION CURVE IS SEMI-DIRECT


% EXPECTED DIRT DEPRECIATION FACTOR = 8%
RCR = 7.8431
RSDD = 93%

6. LAMP LUMEN DEPRECIATION FACTOR, LLD:


LLD = 86.67 %

INTERPOLATION:
6−8 87−LLD
=
6−12 87−86
= 86.67 %

7. LAMP BURN-OUT FACTOR (LBO):


LBO = 100%

8. LUMINAIRE DIRT DEPRECIATION FACTOR (LDD) AT EVERY 12


MONTHS CLEANING CYCLE, CLEANING CYCLE IS VERY CLEAN,
MAINTENANCE CATEGORY IV.
LDD = 94 %

9. TOTAL LIGHT LOSS FACTOR (LLF):


LLF = (RSDD) (LLD) (LBO) (LDD)
= (93%) (86.67%) (100%) (94%)
= 75.77%
10. TOTAL NUMBER OF LUMINAIRES, N:
N = (ILLUMINANCE) (AREA OF THE ROOM)
(LUMENS/LUMINARE) (Cu) (LLF)
= (150) (5.1 x 3.4)
(3200) (0.39) (75.77%)
= 7.04 LUMINAIRES

L∙N
11. C =
√ W
5.10(7)
=
√ 3.4
C = 3.25 ≈ 3

N
R=
C
7.04
=
3.25
R = 2.17 ≈ 2

XL = (L/R) = (5.10/2.17) = 2.35m


XW= (W/R) = (3.4/2.17) = 1.57m

12. ACTUAL ILLUMINANCE:


ILLUMINANCE = (N) (LUMENS/LUMINAIRE) (Cu) (LLF)
(AREA OF THE ROOM)
= (7) (3200) (0.39) (75.77%)
(5.1 x 3.4)
= 381.73 LUX
GENERAL INFORMATION:
PROJECT IDENTIFICATION: UNIT 1C, 2C, 3C, 4C
AVERAGE MAINTAINED ILLUMINANCE: 150 LUX
LUMINAIRE DATA:
MANUFACTURER:
CATALOG NUMBER: ITEM NO. 5
LAMP DATA:
TYPE AND COLOR: RAPID START, DAYLIGHT
NUMBER OF LAMPS/LUMINAIRE: 1
TOTAL LUMENS/LUMINAIRE: 6400

LENGTH OF THE ROOM = 5.1000 m


WIDTH OF THE ROOM = 3.4000 m
HEIGHT OF THE ROOM =4m

hCC = 0m

hRC = 3.2m

hFC = 0.8m

V. DATA:
1. AVERAGE MAINTAINED LUMINANCE: 150 LUX

2. LUMINAIRE DATA: ITEM NO. 5


DESCRIPTION: 1-20 W, 230 V, 60 HZ, DAYLIGHT, PIN LIGHT
3. AREA ATMOSPHERE:VERY CLEAN

4. ROOM SURFACE REFLECTANCES:


CEILING, ρC = 80 %
WALL, ρW = 50 %
FLOOR, ρF= 20 %

5. OPERATION CHARACTERISTICS: 8 HOURS

6. CLEANING CYCLE: ANNUALLY


VI. CALCULATION:

1. DETERMINING CAVITY RATIOS:

CEILING CAVITY RATIO, CCR:

L+W
CCR= ∙5 hcc
L xW

5.1+3.4
CCR= ∙ 5(0)
5.1 x 3.4

=0

ROOM CAVITY RATIO, RCR:


L+W
RCR= ∙5 hrc
L xW

5.1+3.4
RCR= ∙ 5(3.2)
5.1 x 3.4

= 7.8431

FLOOR CAVITY RATIO, FCR:


L+W
FCR= ∙5 hfc
L xW

5.1+3.4
FCR= ∙ 5(0.8)
5.1 x 3.4

= 1.9608

2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρcc:


% BASE REFLECTANCE, ρC = 80 %
% WALL REFLECTANCE, ρW = 50 %
CEILING CAVITY RATIO, CCR = 0
ρCC = 80 %
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρfc:
% BASE REFLECTANCE, ρF = 20 %
% WALL REFLECTANCE, ρW = 50 %
FLOOR CAVITY RATIO, FCR = 1.9608
ρFC = 18 %

4. OBTAIN COEFFICIENT OF UTILIZATION, Cu:


ρCC = 80 %
ρW = 50 %
RCR = 7.8461
CU = 0.3863

INTERPOLATION:
7−7.8431 0.42−Cu
=
7−8 0.42−0.38
= 0.3863

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD:


Item # 5

THE LIGHT DISTRIBUTION CURVE IS SEMI-DIRECT


% EXPECTED DIRT DEPRECIATION FACTOR = 8%
RCR = 7.8431
RSDD = 93%

6. LAMP LUMEN DEPRECIATION FACTOR, LLD:


LLD = 86.67 %

INTERPOLATION:
6−8 87−LLD
=
6−12 87−86
= 86.67 %

7. LAMP BURN-OUT FACTOR (LBO):


LBO = 100%

8. LUMINAIRE DIRT DEPRECIATION FACTOR (LDD) AT EVERY 12


MONTHS CLEANING CYCLE, CLEANING CYCLE IS VERY CLEAN,
MAINTENANCE CATEGORY IV.
LDD = 94 %

9. TOTAL LIGHT LOSS FACTOR (LLF):


LLF = (RSDD) (LLD) (LBO) (LDD)
= (93%) (86.67%) (100%) (94%)
= 75.77%
10. TOTAL NUMBER OF LUMINAIRES, N:
N = (ILLUMINANCE) (AREA OF THE ROOM)
(LUMENS/LUMINARE) (Cu) (LLF)
= (150) (5.1 x 3.4)
(3200) (0.39) (75.77%)
= 7.04 LUMINAIRES

L∙N
11. C =
√ W
5.10(7)
=
√ 3.4
C = 3.25 ≈ 3

N
R=
C
7.04
=
3.25
R = 2.17 ≈ 2

XL = (L/R) = (5.10/2.17) = 2.35m


XW= (W/R) = (3.4/2.17) = 1.57m

12. ACTUAL ILLUMINANCE:


ILLUMINANCE = (N) (LUMENS/LUMINAIRE) (Cu) (LLF)
(AREA OF THE ROOM)
= (7) (3200) (0.39) (75.77%)
(5.1 x 3.4)
= 381.73 LUX
GENERAL INFORMATION:
PROJECT IDENTIFICATION: UNIT 1D, 2D, 3D, 4D
AVERAGE MAINTAINED ILLUMINANCE: 150 LUX
LUMINAIRE DATA:
MANUFACTURER:
CATALOG NUMBER: ITEM NO. 5
LAMP DATA:
TYPE AND COLOR: RAPID START, DAYLIGHT
NUMBER OF LAMPS/LUMINAIRE: 1
TOTAL LUMENS/LUMINAIRE: 6400

LENGTH OF THE ROOM = 5.1000 m


WIDTH OF THE ROOM = 3.4000 m
HEIGHT OF THE ROOM =4m

hCC = 0m

hRC = 3.2m

hFC = 0.8m
VII. DATA:
1. AVERAGE MAINTAINED LUMINANCE: 150 LUX

2. LUMINAIRE DATA: ITEM NO. 5


DESCRIPTION: 1-20 W, 230 V, 60 HZ, DAYLIGHT, PIN LIGHT

3. AREA ATMOSPHERE:VERY CLEAN

4. ROOM SURFACE REFLECTANCES:


CEILING, ρC = 80 %
WALL, ρW = 50 %
FLOOR, ρF= 20 %

5. OPERATION CHARACTERISTICS: 8 HOURS

6. CLEANING CYCLE: ANNUALLY


VIII. CALCULATION:

1. DETERMINING CAVITY RATIOS:

CEILING CAVITY RATIO, CCR:

L+W
CCR= ∙5 hcc
L xW

5.1+3.4
CCR= ∙ 5(0)
5.1 x 3.4

=0

ROOM CAVITY RATIO, RCR:


L+W
RCR= ∙5 hrc
L xW

5.1+3.4
RCR= ∙ 5(3.2)
5.1 x 3.4

= 7.8431
FLOOR CAVITY RATIO, FCR:
L+W
FCR= ∙5 hfc
L xW

5.1+3.4
FCR= ∙ 5(0.8)
5.1 x 3.4

= 1.9608

2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρcc:


% BASE REFLECTANCE, ρC = 80 %
% WALL REFLECTANCE, ρW = 50 %
CEILING CAVITY RATIO, CCR = 0
ρCC = 80 %

3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρfc:


% BASE REFLECTANCE, ρF = 20 %
% WALL REFLECTANCE, ρW = 50 %
FLOOR CAVITY RATIO, FCR = 1.9608
ρFC = 18 %

4. OBTAIN COEFFICIENT OF UTILIZATION, Cu:


ρCC = 80 %
ρW = 50 %
RCR = 7.8461
CU = 0.3863

INTERPOLATION:
7−7.8431 0.42−Cu
=
7−8 0.42−0.38
= 0.3863

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD:


Item # 5
THE LIGHT DISTRIBUTION CURVE IS SEMI-DIRECT
% EXPECTED DIRT DEPRECIATION FACTOR = 8%
RCR = 7.8431
RSDD = 93%

6. LAMP LUMEN DEPRECIATION FACTOR, LLD:


LLD = 86.67 %

INTERPOLATION:
6−8 87−LLD
=
6−12 87−86
= 86.67 %

7. LAMP BURN-OUT FACTOR (LBO):


LBO = 100%

8. LUMINAIRE DIRT DEPRECIATION FACTOR (LDD) AT EVERY 12


MONTHS CLEANING CYCLE, CLEANING CYCLE IS VERY CLEAN,
MAINTENANCE CATEGORY IV.
LDD = 94 %

9. TOTAL LIGHT LOSS FACTOR (LLF):


LLF = (RSDD) (LLD) (LBO) (LDD)
= (93%) (86.67%) (100%) (94%)
= 75.77%
10. TOTAL NUMBER OF LUMINAIRES, N:
N = (ILLUMINANCE) (AREA OF THE ROOM)
(LUMENS/LUMINARE) (Cu) (LLF)
= (150) (5.1 x 3.4)
(3200) (0.39) (75.77%)
= 7.04 LUMINAIRES

L∙N
11. C =
√W
5.10(7)
=
√3.4
C = 3.25 ≈ 3
N
R=
C
7.04
=
3.25
R = 2.17 ≈ 2

XL = (L/R) = (5.10/2.17) = 2.35m


XW= (W/R) = (3.4/2.17) = 1.57m

12. ACTUAL ILLUMINANCE:


ILLUMINANCE = (N) (LUMENS/LUMINAIRE) (Cu) (LLF)
(AREA OF THE ROOM)
= (7) (3200) (0.39) (75.77%)
(5.1 x 3.4)
= 381.73 LUX

GENERAL INFORMATION:
PROJECT IDENTIFICATION: UNIT 2F, 3F, 4F
AVERAGE MAINTAINED ILLUMINANCE: 150 LUX
LUMINAIRE DATA:
MANUFACTURER:
CATALOG NUMBER: ITEM NO. 5
LAMP DATA:
TYPE AND COLOR: RAPID START, DAYLIGHT
NUMBER OF LAMPS/LUMINAIRE: 1
TOTAL LUMENS/LUMINAIRE: 6400

LENGTH OF THE ROOM = 5.1000 m


WIDTH OF THE ROOM = 3.4000 m
HEIGHT OF THE ROOM =4m

hCC = 0m

hRC = 3.2m

hFC = 0.8m

I. DATA:
1. AVERAGE MAINTAINED LUMINANCE: 150 LUX

2. LUMINAIRE DATA: ITEM NO. 5


DESCRIPTION: 1-20 W, 230 V, 60 HZ, DAYLIGHT, PIN LIGHT

3. AREA ATMOSPHERE:VERY CLEAN

4. ROOM SURFACE REFLECTANCES:


CEILING, ρC = 80 %
WALL, ρW = 50 %
FLOOR, ρF= 20 %

5. OPERATION CHARACTERISTICS: 8 HOURS

6. CLEANING CYCLE: ANNUALLY


II. CALCULATION:

1. DETERMINING CAVITY RATIOS:

CEILING CAVITY RATIO, CCR:


L+W
CCR= ∙5 hcc
L xW

5.1+3.4
CCR= ∙ 5(0)
5.1 x 3.4

=0

ROOM CAVITY RATIO, RCR:


L+W
RCR= ∙5 hr c
L xW

5.1+3.4
RCR= ∙ 5(3.2)
5.1 x 3.4

= 7.8431

FLOOR CAVITY RATIO, FCR:


L+W
FCR= ∙5 hfc
L xW

5.1+3.4
FCR= ∙ 5(0.8)
5.1 x 3.4

= 1.9608

2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρcc:


% BASE REFLECTANCE, ρC = 80 %
% WALL REFLECTANCE, ρW = 50 %
CEILING CAVITY RATIO, CCR = 0
ρCC = 80 %

3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρfc:


% BASE REFLECTANCE, ρF = 20 %
% WALL REFLECTANCE, ρW = 50 %
FLOOR CAVITY RATIO, FCR = 1.9608
ρFC = 18 %

4. OBTAIN COEFFICIENT OF UTILIZATION, Cu:


ρCC = 80 %
ρW = 50 %
RCR = 7.8461
CU = 0.3863

INTERPOLATION:
7−7.8431 0.42−Cu
=
7−8 0.42−0.38
= 0.3863

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD:


Item # 5

THE LIGHT DISTRIBUTION CURVE IS SEMI-DIRECT


% EXPECTED DIRT DEPRECIATION FACTOR = 8%
RCR = 7.8431
RSDD = 93%

6. LAMP LUMEN DEPRECIATION FACTOR, LLD:


LLD = 86.67 %

INTERPOLATION:
6−8 87−LLD
=
6−12 87−86
= 86.67 %

7. LAMP BURN-OUT FACTOR (LBO):


LBO = 100%

8. LUMINAIRE DIRT DEPRECIATION FACTOR (LDD) AT EVERY 12


MONTHS CLEANING CYCLE, CLEANING CYCLE IS VERY CLEAN,
MAINTENANCE CATEGORY IV.
LDD = 94 %

9. TOTAL LIGHT LOSS FACTOR (LLF):


LLF = (RSDD) (LLD) (LBO) (LDD)
= (93%) (86.67%) (100%) (94%)
= 75.77%
10. TOTAL NUMBER OF LUMINAIRES, N:
N = (ILLUMINANCE) (AREA OF THE ROOM)
(LUMENS/LUMINARE) (Cu) (LLF)
= (150) (5.1 x 3.4)
(3200) (0.39) (75.77%)
= 7.04 LUMINAIRES

L∙N
11. C =
√ W
5.10(7)
=
√ 3.4
C = 3.25 ≈ 3

N
R=
C
7.04
=
3.25
R = 2.17 ≈ 2

XL = (L/R) = (5.10/2.17) = 2.35m


XW= (W/R) = (3.4/2.17) = 1.57m

12. ACTUAL ILLUMINANCE:


ILLUMINANCE = (N) (LUMENS/LUMINAIRE) (Cu) (LLF)
(AREA OF THE ROOM)
= (7) (3200) (0.39) (75.77%)
(5.1 x 3.4)
= 381.73 LUX
GENERAL INFORMATION:
PROJECT IDENTIFICATION: UNIT 2E, 3E, 4E (BEDROOM)
AVERAGE MAINTAINED ILLUMINANCE: 150 LUX
LUMINAIRE DATA:
MANUFACTURER:
CATALOG NUMBER: ITEM NO. 5
LAMP DATA:
TYPE AND COLOR: RAPID START, DAYLIGHT
NUMBER OF LAMPS/LUMINAIRE: 1
TOTAL LUMENS/LUMINAIRE: 3200

LENGTH OF THE ROOM = 5.1000 m


WIDTH OF THE ROOM = 3.0904 m
HEIGHT OF THE ROOM =4m

hCC = 0m

hRC = 3.2m

hFC = 0.8m

I. DATA:
1. AVERAGE MAINTAINED LUMINANCE: 150 LUX

2. LUMINAIRE DATA: ITEM NO. 5


DESCRIPTION: 1-20 W, 230 V, 60 HZ, DAYLIGHT, PIN LIGHT

3. AREA ATMOSPHERE: VERY CLEAN


4. ROOM SURFACE REFLECTANCES:
CEILING, ρC = 80 %
WALL, ρW = 50 %
FLOOR, ρF= 20 %

5. OPERATION CHARACTERISTICS: 10 HOURS

6. CLEANING CYCLE: ANNUALLY

II. CALCULATION:

1. DETERMINING CAVITY RATIOS:

CEILING CAVITY RATIO, CCR:

L+W
CCR= ∙5 hcc
L xW

5.25+2.9
CCR= ∙5 (0)
5.25 x 2.9

=0

ROOM CAVITY RATIO, RCR:


L+W
RCR= ∙5 hrc
L xW

5.25+2.9
RCR= ∙5 (3)
5.25 x 2.9
=8

FLOOR CAVITY RATIO, FCR:


L+W
FCR= ∙5 hfc
L xW

5.25+2.9
FCR= ∙5 (1)
5.25 x 2.9

= 2.7

2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρcc:


% BASE REFLECTANCE, ρC = 80 %
% WALL REFLECTANCE, ρW = 50 %
CEILING CAVITY RATIO, CCR = 0
ρCC = 80 %

3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρfc:


% BASE REFLECTANCE, ρF = 20 %
% WALL REFLECTANCE, ρW = 50 %
FLOOR CAVITY RATIO, FCR = 2.7
ρFC = 23%

INTERPOLATION:
2.6−2.7 18−ρ FC
=
2.6−2.8 18−18
= 23%

4. OBTAIN COEFFICIENT OF UTILIZATION, Cu:


ρCC = 80 %
ρW = 50 %
RCR = 8
CU = 0.38

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD:


Item # 27

THE LIGHT DISTRIBUTION CURVE IS SEMI-DIRECT


% EXPECTED DIRT DEPRECIATION FACTOR = 8%
RCR = 8
RSDD = 93%

6. LAMP LUMEN DEPRECIATION FACTOR, LLD:


LLD = 86.33 %
INTERPOLATION:
6−10 87−LLD
=
6−12 87−86
= 86.33 %

7. LAMP BURN-OUT FACTOR (LBO):


LBO = 100%

8. LUMINAIRE DIRT DEPRECIATION FACTOR (LDD) AT EVERY 12


MONTHS CLEANING CYCLE, CLEANING CYCLE IS VERY CLEAN,
MAINTENANCE CATEGORY II.
LDD = 97 %

9. TOTAL LIGHT LOSS FACTOR (LLF):


LLF = (RSDD) (LLD) (LBO) (LDD)
= (93%) (86.33%) (100%) (97%)
= 78%

10. TOTAL NUMBER OF LUMINAIRES, N:


N = (ILLUMINANCE) (AREA OF THE ROOM)
(LUMENS/LUMINARE) (Cu) (LLF)
= (250) (5.25 x 2.9)
(6400) (0.38) (78%)
= 2 LUMINAIRES

L∙N
11. C =
√ W
5.25(2)
=
√ 2.9
C = 1.9 ≈ 2

N
R=
C
2
=
1.9
R=1

XL = (L/R) = (5.25/1) = 5.25m


XW= (W/R) = (2.9/1) = 2.9m

12. ACTUAL ILLUMINANCE:


ILLUMINANCE = (N) (LUMENS/LUMINAIRE) (Cu) (LLF)
(AREA OF THE ROOM)
= (2) (6400) (0.38) (78%)
(5.25 x 2.9)
= 249.19 LUX

GENERAL INFORMATION:
PROJECT IDENTIFICATION: LEASABLE SPACE
AVERAGE MAINTAINED ILLUMINANCE: 250 LUX
LUMINAIRE DATA:
MANUFACTURER:
CATALOG NUMBER: ITEM NO. 5
LAMP DATA:
TYPE AND COLOR: RAPID START, COOL WHITE
NUMBER OF LAMPS/LUMINAIRE: 1
TOTAL LUMENS/LUMINAIRE: 6400

LENGTH OF THE ROOM = 10.9 m


WIDTH OF THE ROOM = 4.9 m
HEIGHT OF THE ROOM =5m

hCC = 0m

hRC = 4m
hFC = 1m

I. DATA:
1. AVERAGE MAINTAINED LUMINANCE: 250 LUX

2. LUMINAIRE DATA: ITEM NO. 5


DESCRIPTION: 1-40 W, 230 V, 60 HZ, PIN LIGHT

3. AREA ATMOSPHERE: VERY CLEAN

4. ROOM SURFACE REFLECTANCES:


CEILING, ρC = 80 %
WALL, ρW = 50 %
FLOOR, ρF= 20 %

5. OPERATION CHARACTERISTICS: 10 HOURS

6. CLEANING CYCLE: ANNUALLY

II. CALCULATION:

1. DETERMINING CAVITY RATIOS:

CEILING CAVITY RATIO, CCR:

L+W
CCR= ∙5 hcc
L xW

10.9+4.9
CCR= ∙ 5(0)
10.9 x 4.9

=0

ROOM CAVITY RATIO, RCR:


L+W
RCR= ∙5 hrc
L xW
10.9+4.9
RCR= ∙ 5(4)
10.9 x 4.9
= 5.91

FLOOR CAVITY RATIO, FCR:


L+W
FCR= ∙5 hfc
L xW

10.9+4.9
FCR= ∙ 5(1)
10.9 x 4.9

= 1.4

2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρcc:


% BASE REFLECTANCE, ρC = 80 %
% WALL REFLECTANCE, ρW = 50 %
CEILING CAVITY RATIO, CCR = 0
ρCC = 80 %

3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρfc:


% BASE REFLECTANCE, ρF = 20 %
% WALL REFLECTANCE, ρW = 50 %
FLOOR CAVITY RATIO, FCR = 1.4
ρFC = 18%

4. OBTAIN COEFFICIENT OF UTILIZATION, Cu:


ρCC = 80 %
ρW = 50 %
RCR = 5.91
CU = 75%
INTERPOLATION:
5−5.91 0.80−CU
=
5−6 0.80−0.74
= 75%

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD:


Item # 5
THE LIGHT DISTRIBUTION CURVE IS SEMI-DIRECT
% EXPECTED DIRT DEPRECIATION FACTOR = 8%
RCR = 5.91
RSDD = 94%

6. LAMP LUMEN DEPRECIATION FACTOR, LLD:


LLD = 86.33 %

INTERPOLATION:
6−10 87−LLD
=
6−12 87−86
= 86.33 %

7. LAMP BURN-OUT FACTOR (LBO):


LBO = 100%

8. LUMINAIRE DIRT DEPRECIATION FACTOR (LDD) AT EVERY 12


MONTHS CLEANING CYCLE, CLEANING CYCLE IS VERY CLEAN,
MAINTENANCE CATEGORY II.
LDD = 97 %

9. TOTAL LIGHT LOSS FACTOR (LLF):


LLF = (RSDD) (LLD) (LBO) (LDD)
= (94%) (86.33%) (100%) (97%)
= 79%

10. TOTAL NUMBER OF LUMINAIRES, N:


N = (ILLUMINANCE) (AREA OF THE ROOM)
(LUMENS/LUMINARE) (Cu) (LLF)
= (500) (10.9 x 4.9)
(6400) (.75) (79%)
= 4 LUMINAIRES
L∙N
11. C =
√ W
10.9( 4)
=
√ 4.9
C = 2.98 ≈ 3

N
R=
C
4
=
3
R = 1.3 ≈ 1

XL = (L/R) = (10.9/1) = 10.9m


XW= (W/R) = (4.9/1) = 4.9m

12. ACTUAL ILLUMINANCE:


ILLUMINANCE = (N) (LUMENS/LUMINAIRE) (Cu) (LLF)
(AREA OF THE ROOM)
= (4) (6400) (0.75) (79%)
(10.9 x 4.9)
= 283.99 LUX

You might also like