CLAMP METER
USERS MANUAL
CONTENTS
Safety Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - 1
Safety Information - - - - - - - - - - - - - - - - - - - - - - - - - - - 1
Safety Symbols - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2
General Description - - - - - - - - - - - - - - - - - - - - - - - - - - 2
Feature - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2
Meter Layout ------------------------------ 4
Using The Selector - - - - - - - - - - - - - - - - - - - - - - - - - - 5
Using The Buttons -------------------------- 6
Lcd Display ------------------------------- 9
Making Measurements ----------------------- 11
Measuring Ac Voltage - - - - - - - - - - - - - - - - - - - - - 11
Measuring Ac Current - - - - - - - - - - - - - - - - - - - - - 13
Measuring Single-Phase Circuit - - - - - - - - - - - - - 15
Measuring Three -Phase Four-Wire Circuit - - - - - - 19
Measuring Three -Phase Three-Wire Circuit - - - - - 24
Saving Measurement - - - - - - - - - - - - - - - - - - - - - - 24
Recalling Memory ----------------------- 24
RS232C Date Interface -------------------- 25
Input Voltage And Current ----------------- 26
Backlight Display ----------------------- 26
Sketch Of Safety Holding - - - - - - - - - - - - - - - - - - 26
Curve Diagram Of Power ------------------ 27
Low Voltage Indication - - - - - - - - - - - - - - - - - - - - 28
Replacing Batteries - - - - - - - - - - - - - - - - - - - - - - - - - 28
Specifications ----------------------------- 29
Accessories ------------------------------ 32
Safety Precautions
· Read these operation instructions thoroughly and completely before
operating your meter. Pay particular attention to WARNING. The
· You must be careful when working with voltages above 30V AC. Keep
fingers behind the probe barriers while measuring.
· Never use the meter to measure voltages that might exceed the
maximum allowable input value of any function measurement mode.
· Always inspect your meter and test leads before every use. If any
abnormal conditions exist: broken test leads, cracked cases, LCD not
· Using the meter with the equipped test leads is only conform to safety
requirements. If you need instead broken test leads, you must replaced
· Never touch a voltage source when the test leads are plugged into a
current jack.
WARNING
Safety Information
Three-phase digital power clamp meter has been designed according
Earth ground
Battery
General Description
Three-phase digital power clamp meter is a handheld aptitude meter with
and the power-supply circuit on the spot. The structure of the instrument
easy and fast. To the power measurement user, the digital power clamp
instrument.
Feature
1. For power measurement of 3-phase 3-wire circuit, 3-phase 4-wire
circuit, single-phase circuit.
count and high resolution, the instrument has high accuracy and easy
operation.
measurement parameter.
6. Measure five power parameters of each phase and total power value in
software.
supply for the clamp at one time in Active Energy measurement mode,
convenient to carrying .
- 3 -
Meter Layout
1
MAX MAX
1000A 600V
600kW CAT.III
8
DIGITAL POWER CLAMP
MS2203 OFF
HOLD
2
EX- P
MR
3
MAX
600V
W
3~ OPTICAL INTERFACE RS232
7 3
Ture RMS 2
AUTO RANGE
1
OFF
kVA kWh
kW / PF kVAr TIME
V / Hz A RS232 CLEAR
1 2 3 W W3 P
DC
AC kVA
CAL kWh 4
6 RS232
MAX
PF
MIN
FREQ
Time
Hz
kVAr
h min
MEM
MR 0 20 10 40 20 60 30 80 40100
MAX MIN
SAVE
V1 COM
V2 V3
5
( Figure 1 )
1. Clamp Jaws Ф50mm
2. HOLD Button
Holds the display reading and “ " symbol is shown in the LCD
measurement mode.
3. Function Selector Rotary Switch
V1: The input terminal for the first phase, using the yellow test lead
to connect.
V2: The input terminal for the second phase, using the green test
lead to connect.
V3: The input terminal for the third phase, using the red test lead to
connect.
COM: Common terminal, the earth input terminal for all measure-
6. LCD Display
7. Trigger
Press the lever to open the transformer. When the lever is released,
the jaws will close again.
8. RS232C Data Interface
Your clamp meter can use a serial interface cable to communicate
with a computer. Refer to Figure 18 for complete instructions.
– 5 –
( Table 1. Introducing The Selector )
ITEM DESCRIPTION
measurement
measurement
measurement
2 kVA
kVAr
Apparent Power, Reactive Power Measurement
Button.
kWh
3 TIME
Active Energy, Time Measurement Button
9 Backlight Button
MAX
– 6 –
kW / PF
1. Active Power, Power Factor Measurement Button
kW / PF
Press button to measure Active Power and Power Factor in
measurement mode. Then the LCD shows Active Power reading in
display.
kVA
2. kVAr
Apparent power, Reactive Power measurement button
kVA
Press kVAr
button to measure Apparent Power and Reactive
secondary display.
kWh
TIME
3. Active Energy, Time Measurement Button
kWh
TIME
Press button to measure Active Energy in measurement
mode. Then the LCD shows Active Energy reading in the primary
display.
button for the third phase after you getting the measured
value of the third phase on the display. So the meter will calculate the
sum in this three phase system automatically, you will rotate the
selector to ∑W at one time, then the display shows the total power
value.
V / Hz
5. Voltage Measurement Button
V / Hz
Press button to measure voltage of the circuit and display
– 7 –
A
6. Current Measurement Button
A
Press button to measure current of the circuit and display
the measurement value in the LCD display.
RS232
7. Data Transmit Button
RS232
Press button to transmit measured data to a computer by
special interface cable, you can record current measured value and
9. Backlight Button
Button
MAX
display.
MAX
previous memory location and display the data on the LCD. Once
display.
– 8 –
MIN
next memory location and display the data on the LCD. Once
pressing this button, the clamp meter recalls a memory location next
current location.
SAVE
12. Data Save Button
SAVE
Press button to save current measured data to the meter in
Lcd Display
( Figure 2 )
8. Battery symbol
- 9 -
9. Voltage unit (V), current unit (A), Apparent Power unit (kVA)
13. Voltage unit (V), current unit (A), Apparent Power unit (kVA),
- 10 -
Making Measurements
Measuring AC Voltage
1
AC V MAX MAX
1000A
600kW
600V
CAT.III Circuit
FREQ Hz AC V
MEM
0 20 40 60 80 100 OFF
HOLD
V1
EX - P
MR
Ture RMS 2
AUTO RANGE
1
OFF
1 kW / PF
kVA kWh
kVAr TIME
V / Hz A RS232 CLEAR
AC V
1
AC V
FREQ Hz MEM
FREQ Hz
0 10 20 30 40
MAX MIN
MEM SAVE
0 10 20 30 40 V1 COM
V2 V3
Black Yellow
the test leads to input terminals: Insert the black test lead into the
COM input terminal and one corresponding color test lead into the
V / Hz
2. Connect test leads to the load, press button, voltage
- 11 -
MAX
3. In voltage measurement mode, press button, the LCD
frequency value .
MIN
4. Press button, the LCD displays “MIN” symbol, then
5. For input voltage exceeds 600V, the display will show ”OL” symbol
MAX MAX
1000A
600kW
600V
CAT.III Circuit
AC V
OFF
HOLD
V1
EX - P
MR
Ture RMS 2
AUTO RANGE
1
OFF
1
kVA kWh
kW / PF kVAr TIME
AC V V / Hz A RS232 CLEAR
AC V
FREQ Hz FREQ Hz
MEM
0 10 20 30 40
0 20 40 60 80 100
V1 COM
V2 V3
Black Yellow
7. There are two modes to show the bar graph in the LCD. You can
2
Tested conductor
3
MAX MAX
1000A 600V
600kW CAT.III
Earth wire
HOLD
OFF
EX - P
MR
3 3
Ture RMS 2
AUTO RANGE
1
OFF
AC A kVA kWh
kW / PF kVAr TIME
V / Hz A RS232 CLEAR
RS232
AC A
RS232
MEM
MEM
0 10 20 30 40
0 10 20 30 40
MAX MIN
SAVE
V1 COM
V2 V3
2. Press the trigger to hook the clamp jaw around one conductor to
A
be measured. Press button, the primary display reading is
( Figure 6)
MIN
symbol. ( Figure 7)
- 13 -
6. There are two modes to show the bar graph. You can observe the
Figure 6 )
2
Tested conductor
3
MAX MAX
1000A 600V
600kW CAT.III
Earth wire
HOLD
OFF
EX- P
3 MR
AC A Ture RMS
3
2
AUTO RANGE
1
OFF
kVA kWh
MAX A
kW / PF kVAr TIME
V / Hz A RS232 CLEAR
MEM 3
AC A
0 20 40 60 80 100
MAX A
MEM
0 20 40 60 80 100
MAX MIN
SAVE
V1 COM
V2 V3
2
Tested conductor
3
MAX MAX
1000A 600V
600kW CAT.I II
Earth wire
HOLD
OFF
EX - P
3 MR
AC A Ture RMS
AUTO RANGE
3
2
1
OFF
kVA kWh
kW / PF kVAr TIME
V / Hz A RS232 CLEAR
3
MEM AC A
0 20 40 60 80 100 RS232
MEM
0 20 40 60 80 100
MAX MIN
SAVE
V1 COM
V2 V3
Tested conductor
MAX MAX
1000A 600V
600kW CAT.I II
Earth wire
HOLD
OFF
EX - P
MR
Ture RMS 2
AUTO RANGE
1
OFF
2
kVA kWh
kW / PF kVAr TIME
AC V / Hz A RS232 CLEAR
kW 2
AC
kW
PF
PF MEM
0 20 40 60 80 100
0 20 40 60 80 100 V1 COM
V2 V3
Black Green
“OL” symbol will be shown in the display too. And the bar
Tested conductor
MAX MAX
1000A 600V
600kW CAT.I II
Earth wire
HOLD
OFF
EX - P
MR
Ture RMS 2
AUTO RANGE
1
OFF
2
kVA kWh
kW / PF kVAr TIME
AC V / Hz A RS232 CLEAR
kW 2
AC
kW
PF
PF MEM
0 20 40 60 80 100
0 20 40 60 80 100 V1 COM
V2 V3
Black Green
- 16 -
( 2. ) Apparent Power (kVA)and Reactive Power ( kVAr )
kVA
a. Press kVAr
button, the Apparent Power value is
shown in the primary display, Reactive Power value and
Tested conductor
MAX
1000A
600kW
MAX
600V
CAT.I II
Earth wire
HOLD
OFF
EX - P
MR
Ture RMS 2
AUTO RANGE
1
OFF
3
kVA kWh
kW / PF kVAr TIME
3
AC kVA
kVAr
kVAr MEM
0 20 40 60 80 100
0 20 40 60 80 100 V1 COM
V2 V3
Black Red
in software.
- 17 -
(3.) Active Energy (kWh) and Time(hmin)
Tested conductor
MAX
1000A
600kW
MAX
600V
CAT.I II
Earth wire
HOLD
OFF
EX - P
MR
Ture RMS 2
AUTO RANGE
1
OFF
3
kVA kWh
kW / PF kVAr TIME
AC V / Hz A RS232 CLEAR
kWh 3
AC
kWh
hmin
MEM
0 20 40 60 80 100
h min
MEM MAX MIN
SAVE
0 20 40 60 80 100 V1 COM
V2 V3
Black Yellow
lead to every phase live wire of the three-phase circuit and V1 jack,
V2 jack, V3 jack of the meter respectively, connect black test lead
hook the clamp jaw around the first phase conductor of the tested
kW / PF
circuit, press button to measure Active Power (kW) and
Power Factor (PF). the measured value are shown in the LCD then
Tested conductor
1
MAX MAX
1000A 600V
600kW CAT.I II
3
1 OFF
HOLD
EX - P
AC W
MR
Earth wire
kW 3
Ture RMS 2
AUTO RANGE
1
OFF
PF kW / PF
kVA kWh
kVAr TIME
V / Hz A RS232 CLEAR
MEM
0 20 40 60 80 100
1
AC
kW
PF
MEM
0 20 40 60 80 100
1 MAX MIN
SAVE
V1 COM
V2 V3
AC kVA
Black Red Green Yellow
kVAr
MEM
0 20 40 60 80 100
- 20 -
3. Turn the selector to Φ2(to the second phase measurement), hook
the clamp jaw around the second phase conductor of the tested
kW / PF kVA
clamp jaw around the third phase conductor of the tested circuit,
kW / PF kVA
1
Tested conductor
2
MAX MAX
1000A 600V
600kW CAT.I II
HOLD
Earth wire
2 EX - P
OFF
MR
AC W
kW Ture RMS
AUTO RANGE
2
1
OFF
kVA kWh
PF kW / PF kVAr TIME
V / Hz A RS232 CLEAR
MEM
2
0 20 40 60 80 100
AC
kW
PF
MEM
0 20 40 60 80 100
MAX MIN
SAVE
2 V1
V2 V3
COM
kVAr
MEM
0 20 40 60 80 100
- 21 -
1
2
Tested conductor
3
MAX MAX
1000A 600V
600kW CAT.I II
Earth wire
HOLD
3 EX - P
OFF
MR
AC W
kW Ture RMS
AUTO RANGE
2
1
OFF
kVA kWh
PF kW / PF kVAr TIME
V / Hz A RS232 CLEAR
MEM
3
0 20 40 60 80 100
AC
kW
PF
MEM
0 20 40 60 80 100
MAX MIN
SAVE
3 V1
V2 V3
COM
kVAr
MEM
0 20 40 60 80 100
- 22 -
1
2
Tested conductor
3
MAX MAX
1000A 600V
600kW CAT.I II
Earth wire
HOLD
OFF
EX - P
MR
Ture RMS 2
AUTO RANGE
1
OFF
1 2 3 W
kVA kWh
kW / PF kVAr TIME
AC V / Hz A RS232 CLEAR
kW 1 2 3 W
AC
kW
PF
PF MEM
0 20 40 60 80 100
0 20 40 60 80 100 V1 COM
V2 V3
2
Tested conductor
3
MAX MAX
1000A 600V
600kW CAT.III
Earth wire
HOLD
OFF
EX- P
MR
Ture RMS 2
AUTO RANGE
1
OFF
1 2 3 W
kVA kWh
kW / PF kVAr TIME
1 2 3 W
AC kVA
PF kVAr
kVAr MEM
0 20 40 60 80 100
0 20 40 60 80 100 V1 COM
V2 V3
- 23 -
Measuring Three-Phase Three-Wire Circuit
In three-phase three-wire circuit, the operation of the selector and
function button is same as the operation in three-phase four-wire
1
MAX MAX
1000A 600V
600kW CAT.III
2
Tested conductor
3
1 OFF
HOLD
EX - P
AC W
MR
kW 3
Ture RMS 2
AUTO RANGE
1
OFF
PF kVA kWh
kW / PF kVAr TIME
V / Hz A RS232 CLEAR
MEM
0 20 40 60 80 100
1
AC
kW
PF
MEM
0 20 40 60 80 100
MAX MIN
SAVE
V1 COM
V2 V3
Saving Measurement
SAVE
In measurement mode, you can press button to save the
of measurement date.
Recalling Memory
If something is saved in the meter memory, use following procedure
memory location.
Figure 18, then rotate the interface cable deasil to lock it in the meter.
you want to take out the interface cable from the meter, first you must
rotate the cable widdershins to unlock it, then you can pull out it .
You will install the special data record software into the computer
print the measured data of the meter in real time mode in the
WINDOWS. The software can record, plot, print data and curve.
MAX
600V
COMPUTER
INTERFACE
RS232-C
OPTICAL
will display “OL” symbol, and bar graph is full. When input voltage
Backlight Display
When press button, backlight of LCD display is on. After
Figure 19.
OPEN
WARNING
PLEASE READ MANUAL FOR SAFETY.TO AVOID
ELECTRICAL SHOCK NEVER CONNECT THE TEST
LEADS TO THE INPUT JACKS WHICH ARE NOT
FORRELATED MEASURING AND REMOVE ALL
INPUTS BEFORE OPENING CASE.
BATTERIES : 4 X 1.5 V SIZE AA
IEC1010-1 IEC1010-2-032
600V CAT.III POLLUTION DEGREE 2
( Figure 19 )
- 26 -
Curve Diagram Of Power ( PF=KW / KVA )
2000W 2000W
+E PEAK VALUE OF POWER
+I
+P E =141V
MAX
PEAK VALUE
1000W
-E ACTIVE POWER
-I
-P POWER
PEAK VALUE
IMAX
500W
ACTIVE POWER
KW=I R
2
X
45° 90° 180° 270° 360°
225°
-E θ PEAK VALUE
-I 45°
-P
θ
45°
( Figure 21 )
+V
+I P
+P V MAX
+V
+i I MAX
kW= I R
2
180° X
-E θ -i
θ
-I 360°
-P -V
( Figure 22 )
- 27 -
Low Voltage Indication
The " " symbol is shown on the top right of the LCD display,
when the batteries is weak, you need replace new batteries or use
the EX- P function of the meter now. Turn the selector to EX- P ,
the meter use the measured voltage signal as power supply to work.
But the meter only measure single-phase circuit and can not work in
Replacing Batteries
WARNING
To avoid electrical shock , the instrument must be
power off and disconnect the lest leads or any input
signals before replacing the batteries. Never use the
instrument unless the back cover of the instrument is
fastened completely. Replace only with same type or
rating batteries.
Coin
OPEN
OPEN
WARNING
PLEASE READ MANUAL FOR SAFETY.TO AVOID
ELECTRICAL SHOCK NEVER CONNECT THE TEST WARNING
LEADS TO THE INPUT JACKS WHICH ARE NOT PLEASE READ MANUAL FOR
FORRELATED MEASURING AND REMOVE ALL ELECTRICAL SHOT
INPUTS BEFORE OPENING CASE.
BATTERIES : 4 X 1.5 V SIZE AA
IEC1010-1 IEC1010-2-032
600V CAT.III POLLUTION DEGREE 2
1. Disconnect test leads from any signals, turn the rotary function
switch to OFF, and remove the test leads from the input
terminals.
2. Open the battery cover and remove the battery cover. Because
Figure 23 for opening it: Insert a coin into the groove of the
battery cover, press the coin down, then open the cover.
SPECIFICATIONS
AC VOLTAGE RMS
RANGE ACCURACY RESOLUTION INPUT IMPEDANCE
- 29 -
AC CURRENT RMS
RANGE ACCURACY RESOLUTION
ACTIVE POWER (W )
RANGE ACCURACY RESOLUTION
- 31 -
FREQUENCY ( Hz )
RANGE ACCURACY RESOLUTION
current is 45Hz~65Hz
ACCESSORIES
Users manual 1
Battery 1.5V AA 4
Test Leads (MS3000) 1
Connect test clamp (MS3102) 1
RS232C interface cable ( MS3403 ) 1