NF800 型系列保护装置产品 NF807 发电机(发变组)差动保护测控装置说明书
NF807发电机(发变组)差动保护测控装置说明书
NF807 generator differential protection and control device
基本配置 Basic device
Chapter 1
Iah、Ibh、Ich、Ial、Ibl、Icl为两侧的保护CT电流,测量用电流经隔离变换器变换后,在低通滤波
器之后输入至模数变换器,经CPU采样数字处理后作为遥测量。
Iah、Ibh、Ich、Ial、Ibl、Icl are the protection CT current for two sides. The measure current will be changed after passing the
isolating converter, then pass the low-pass filter, and then input to the module converter. At last the measurement turns out via
the CPU sample digital processor.
Ua、Ub、Uc输入在本装置中的母线或发电机机端电压(选配)。
UA、UB、UC input to the busbar of the device or the voltage of generator end (matching).
当差电流大于整定定值时,说明发电机(或发变组)内部肯定出现了严重故障,差动保护应不进行
任何制动而立即动作于跳闸。差电流速断保护动作定值应按躲过各种不平衡电流和涌流整定。
NF800 型系列保护装置产品 NF807 发电机(发变组)差动保护测控装置说明书
When the differential current is bigger than the setting value, the serious fault should have been occurred inside the generator and
the differential protection should trip at once but not brake. Differential current quick-break protection setting should be set by
avoiding different kinds of unbalanced current and inrush current.
采用比率制动的差动保护,动作特性如图所示。
The differential protection adopts percentage brake. Refer to the following diagram for the operation features.
其中:Thereinto
Iop Iop----------各侧同相的差电流(计算得到);
装置采用三相差电流中二次谐波与基波的比值作为励磁涌流的判据。当任一相差动电流中的二次谐
波比值大于定值,即满足闭锁条件,则闭锁三相比率差动保护。
The device uses the ratio between second-harmonic and basic harmonic in the three-phase differential current as the decision of
excitation inrush current. When the second-harmonic of any- phase differential current is bigger than the setting value w
meets the requirements of blocking, the three-phase percentage differential protection will lock.
1.7 发变组各侧电流相位与平衡补偿
Each-side current phase and balanced compensation of generator
当所保护范围为发变组时,由于两侧CT变比不同,需要进行补偿,将中性点侧电流规整到变压器
NF800 型系列保护装置产品 NF807 发电机(发变组)差动保护测控装置说明书
高压侧,计算出调整系数,将其输入装置,通过软件将由此造成的不平衡电流完全补偿。发变组两侧的
电流互感器二次电流相位由软件校正,具体见功能配置说明。
W h e n t h e p r o t e c t i o n r a n g e i s g e n e r a t o r, i t n e e d s t o r e g u l a t e t h e n e u t r a l c u r r e n t t o t h e H V s i d e o f t r a n s f o r m e r, c a l c
regulation factors and input to the device to completely compensate the unbalanced current by the software due to the difference
of two sides’ CT ratio. The CT secondary current phase of two-side generator is corrected by the software, refer to the function
instruction for detail.
非电量保护包括重瓦斯、调压重瓦斯、超温、水工故障、压力释放、失磁信号。
Non-electric protection includes severe gas, voltage-regulation severe gas, overtemper
excitation-loss signal.
遥测量主要有:三相不平衡电流,这些量都进行实时计算。
Remote-measure includes three-phase unbalanced current. These datas are calculated according to local real-time.
遥信量主要有:16路遥信开入、装置变位遥信及事故遥信,并作事件顺序记录。
Remote-signal includes 16-ways remote input, device deflection remote-signal, emergency remote-signal. It also re
event sequence.
装置可记录保护动作事件、告警事件以及遥信变位事件。
The device can record the protetion action event, alarm event and remote-signal deflection event.
保护动作事件记录保护动作时间,作用于跳闸的保护类型、以及故障时的差动电流。
The protection action event records the protection action time, the protection types actting on tripping and differential current
when occurs fault.
告警事件记录PT断线、CT断线、过负荷等系统告警信号。
Alram event records the alarm signal of CT wire-break, overload system and so on .
遥信变位记录遥信量的变位情况。
The remote-signal deflection records the deflection condition of remote-signal.
本装置故障录波功能,记录的模拟量为Iah、Ibh、Ich、Ian、Ibn、Icn(Ian、Ibn、Icn为中性点电
流),记录的状态量为开关位置。
With the function of fault re c ord , t he re cord a na l ogs of t he de vi c e whose r
Iah、Ibh、Ich、Ian、Ibn、Icn. Thereinto, Ian、Ibn、Icn are the neutral current.
常见的水电站有三种:第一种是正常的发电机的差动保护,第二种是变压器为YD11接线的发变组
差动保护,第三种为YY0接线的发变组保护。如下图,它们对应不同的配置:
The common hydropower station has the following three types. The first type is the differential protec
g e n e r a t o r. T h e s e c o n d t y p e i s t h e d i ff e r e n t i a l p r o t ec t i o n o f g e n e r a t o r w i t h Y D 11 t r a n s f o r m e r. T h e t h i r d t y p e i s t h e g e n
protection with YY0 connection. Refer to the following drawing, they correspond to different devices.
NF800 型系列保护装置产品 NF807 发电机(发变组)差动保护测控装置说明书
第一种 “需要进行相位调整”控制字设为0,中性点调整率公式为
The first type’s control word “phase regulation” is set as 0, the neutral regulation formula is:
Kctn
Kn=
Kctt
第三种 “需要进行相位调整”控制字设为0,中性点调整率公式为
The third type’s control word “phase regulation” is set as 0, the neutral regulation formula is:
Ule×Kctn
Kn=
Uhe×Kcth
在CT的接线上要注意,流向发电机(或发变组)方向为各侧电流正方向!
Pay attention to the connection of CT, the direction that flow to the generator is the positive direction of each-side current.
NF807 机箱端子示意图及端子定义图
NF807 unit terminal schematic diagram and terminal definition
NF800 型系列保护装置产品 NF807 发电机(发变组)差动保护测控装置说明书