Professional Documents
Culture Documents
DPWH
OFFICE OF THE BUILDING OFFICIALS
SCHEDULE OF LOADS
CALINOG,ILOILO
ELECTRICAL
DESIGN ANALYSIS
CKT-1 LIGHTING OUTLET CKT-4 LIGHTING OUTLET CKT-7 LIGHTING OUTLET CKT-10 LIGHTING OUTLET
12 - 20W LED DOWNLIGHT 12 - 80W HIGH BAY LIGHT 8 - 12W LED DOWNLIGHT 11 - 12W LED DOWNLIGHT
I = ( 12x20VA) / (230) = 1.043A I = ( 12x80VA) / (230) = 4.174A I = ( 8x12VA) / (230) = 0.417A I = ( 11x12VA) / (230) = 0.574A
Ic = 1.043X 1.25 = 1.3048 A Ic = 4.174X 1.25 = 5.218 A Ic = 0.417X 1.25 = 0.521 A Ic = 0.574X 1.25 = 0.718 A
USE: 20 AMPERE CIRCUIT BREAKER USE: 20 AMPERE CIRCUIT BREAKER USE: 20 AMPERE CIRCUIT BREAKER USE: 20 AMPERE CIRCUIT BREAKER
CONDUCTOR 2-3.5 mm2 THHN Cu. WIRE CONDUCTOR 2-3.5 mm2 THHN Cu. WIRE CONDUCTOR 2-3.5 mm2 THHN Cu. WIRE CONDUCTOR 2-3.5 mm2 THHN Cu. WIRE
1-2.0mm2 THHN Cu. WIRE FOR GROUNDING 1-2.0mm2 THHN Cu. WIRE FOR GROUNDING 1-2.0mm2 THHN Cu. WIRE FOR GROUNDING 1-2.0mm2 THHN Cu. WIRE FOR GROUNDING
CKT-2 LIGHTING OUTLET CKT-5 LIGHTING OUTLET CKT-8 LIGHTING OUTLET CKT-11 LIGHTING OUTLET
12 - 80W HIGH BAY LIGHT 10 - 12W LED DOWNLIGHT 8 - 12W LED DOWNLIGHT 15 - 50W SPOTLIGHT
I = ( 12x80VA) / (230) = 4.174A 2 - 3VA SIGNAGE I = ( 8x12VA) / (230) = 0.417A I = ( 15x50VA) / (230) = 3.261A
Ic = 4.174X 1.25 = 5.218 A I =[ ( 10x12VA)+(2X5VA)] / (230) = 0.626A Ic = 0.417X 1.25 = 0.521 A Ic = 3.261X 1.25 = 4.076 A
USE: 20 AMPERE CIRCUIT BREAKER Ic = 0.626 X 1.25 = 0.783 A USE: 20 AMPERE CIRCUIT BREAKER USE: 20 AMPERE CIRCUIT BREAKER
CONDUCTOR 2-3.5 mm2 THHN Cu. WIRE USE: 20 AMPERE CIRCUIT BREAKER CONDUCTOR 2-3.5 mm2 THHN Cu. WIRE CONDUCTOR 2-3.5 mm2/THHN
1-2.0mm2 THHN Cu. WIRE FOR GROUNDING CONDUCTOR 2-3.5 mm2 THHN Cu. WIRE 1-2.0mm2 THHN Cu. WIRE FOR GROUNDING
1-2.0mm2 THHN Cu. WIRE FOR GROUNDING SERVICE ENTRANCE
CKT-3 LIGHTING OUTLET CKT-9 LIGHTING OUTLET = 21.3 @ 85% DEMAND FACTOR
16 - 80W HIGH BAY LIGHT CKT-6 LIGHTING OUTLET 6 - 20W LED DOWNLIGHT = 21.3 X 0.85
I = ( 16x80VA) / (230) = 5.565A 10 - 12W LED DOWNLIGHT I = ( 6x12VA) / (230) = 0.522A = 18.11
Ic = 5.565 X 1.25 = 6.956 A I = ( 10x12VA) / (230) = 0.522A Ic = 0.522X 1.25 = 0.653 A SERVICE ENTRANCE CONDUCTOR USE
USE: 20 AMPERE CIRCUIT BREAKER Ic = 0.522X 1.25 = 0.653 A USE: 20 AMPERE CIRCUIT BREAKER CONDUCTOR 2-8.0 mm2 THHN Cu. WIRE
CONDUCTOR 2-3.5 mm2 THHN Cu. WIRE USE: 20 AMPERE CIRCUIT BREAKER CONDUCTOR 2-3.5 mm2 THHN Cu. WIRE 1-5.5mm2 THHN Cu. WIRE
1-2.0mm2 THHN Cu. WIRE FOR GROUNDING CONDUCTOR 2-3.5 mm2 THHN Cu. WIRE 1-2.0mm2 THHN Cu. WIRE FOR GROUNDING 60 AMPERE TRIP, 60 AMP FRAME 240V
1-2.0mm2 THHN Cu. WIRE FOR GROUNDING 2 PST CIRCUIT BREAKER
FOR MAIN CIRCUIT BREAKER