Block: CYCLE
Author:
Created: 09/22/2000 11:41:10 am
Last Modified: 01/15/2003 11:48:32 am

Network 1
STEP 13 STANDBY WAIT FOR 24 HOURS AND COMPRESSOR RUNNING
STEP_13 SW_3A NEXT SYNCRO_START STEP_1 STEP_0
/ / /

TIME_AA GO MOV_W
EN ENO

STEP_0 +0 IN OUT VW100

INI

Network 2 STEP 0 OPEN L/C INLET AND OUTLET VALVES

STEP_0 TIME_B SW_3A SYNCRO_START STEP_2 STEP_1


/ / /

GO MOV_W
EN ENO

STEP_1 +1 IN OUT VW100

1 / 103
E204048

Network 3 STEP 1 CLOSE R/C INLET AND OUTLET VALVES

STEP_1 TIME_A SW_3A SYNCRO_START STEP_3 STEP_2


/ / /

GO MOV_W
EN ENO

STEP_2 +2 IN OUT VW100

Network 4 STEP 2 OPEN R/C REGEN INLET AND OUTLET VALVES


STEP_2 TIME_B SW_3A SYNCRO_START STEP_4 STEP_3
/ / /

GO MOV_W
EN ENO

STEP_3 +3 IN OUT VW100

2 / 103
E204048

Network 5 STEP 3 R/C IN HEATING MODE

STEP_3 HEAT_CNT SW_3A SYNCRO_START STEP_5 STEP_4


/ / /

MIN_HEAT TT_3_HIGH MOV_W


EN ENO

TIME_AA GO +4 IN OUT VW100

STEP_4

Network 6 STEP 4 R/C IN COOLING MODE

STEP_4 COOL_CNT SW_3A SYNCRO_START STEP_6 STEP_5


/ / /

MIN_COOL TT_3_LOW MOV_W


EN ENO

TIME_BB GO +5 IN OUT VW100

STEP_5

3 / 103
E204048

Network 7 STEP 5 CLOSE R/C REGEN INLET AND OUTLET

STEP_5 TIME_A SW_3A SYNCRO_START STEP_7 STEP_6


/ / /

GO MOV_W
EN ENO

STEP_6 +6 IN OUT VW100

Network 8 STEP 6 STANDBY WAIT FOR 24 HOURS AND COMPRESSOR RUNNING


STEP_6 SW_3A NEXT SYNCRO_START STEP_8 STEP_7
/ / /

TIME_BB GO MOV_W
EN ENO

STEP_7 +7 IN OUT VW100

4 / 103
E204048

Network 9 STEP 7 OPEN R/C INLET AND OUTLET VALVES

STEP_7 TIME_A SW_3A SYNCRO_START STEP_9 STEP_8


/ / /

GO MOV_W
EN ENO

STEP_8 +8 IN OUT VW100

Network 10 STEP 8 CLOSE L/C INLET AND OUTLET VALVES


STEP_8 TIME_B SW_3A SYNCRO_START STEP_10 STEP_9
/ / /

GO MOV_W
EN ENO

STEP_9 +9 IN OUT VW100

5 / 103
E204048

Network 11 STEP 9 OPEN L/C REGEN INLET AND OUTLET

STEP_9 TIME_A SW_3A SYNCRO_START STEP_11 STEP_10


/ / /

GO MOV_W
EN ENO

STEP_10 +10 IN OUT VW100

Network 12 STEP 10 L/C IN HEATING MODE


STEP_10 HEAT_CNT SW_3A SYNCRO_START STEP_12 STEP_11
/ / /

MIN_HEAT TT_3_HIGH MOV_W


EN ENO

TIME_BB GO +11 IN OUT VW100

STEP_11

6 / 103
E204048

Network 13 STEP 11 L/C IN COOLING MODE

STEP_11 COOL_CNT SW_3A SYNCRO_START STEP_13 STEP_12


/ / /

MIN_COOL TT_3_LOW MOV_W


EN ENO

TIME_AA GO +12 IN OUT VW100

STEP_12

Network 14 STEP 12 CLOSE L/C REGEN INLET AND OUTLET VALVES

STEP_12 TIME_B SW_3A SYNCRO_START STEP_0 STEP_13


/ / /

GO MOV_W
EN ENO

STEP_13 +13 IN OUT VW100

7 / 103
E204048

Network 15 CHANGE OVER IF COMPRESSOR RUNNING


AND WATCH DOG DONE AND DEWPOINT DONE IF AUTODEW ON

STEP_6 WHT_DOG SW_2B COMP NEXT


/

STEP_13 STBY_DP_GO HHS_1_DELAY

AUTO_WD

Network 16
ALWAYS_ON T61
IN TON

+100 PT

Network 17 INTERLOCK READY TO GO

SW_3A STEP_4 STEP_11 READY PB_1A PB_3 T61 GO


/ / /

COOL_ADV TT_2_LOW TT_3_LOW

8 / 103
E204048

Network 18 IGNITIATE END OF COOLING IN MANUAL MODE ONLY

STEP_4 PB_1A PB_2A COOL_ADV


IN TON

STEP_11 +150 PT

9 / 103
E204048

Network 19 INTERLOCK READY TO GO ON EACH STEP IN MANUAL MODE ONLY

SW_3A STEP_0 TIME_B PURGE_ON READY


/

STEP_1 TIME_A

STEP_2 TIME_B

STEP_3 TIME_AA

STEP_4 TIME_BB

STEP_5 TIME_A

STEP_6 TIME_BB

STEP_7 TIME_A

STEP_8 TIME_B

STEP_9 TIME_A

10 / 103
E204048

STEP_10 TIME_BB

STEP_11 TIME_AA

STEP_12 TIME_B

STEP_13 TIME_AA

Network 20 IGNITIATE SYNCHRO AT ANY STEP EXCEPT IN HEATING AND COOLING MODE
PB_1A PB_3 STEP_3 STEP_4 STEP_10 STEP_11 SYNCRO_START
/ / / / IN TON

+150 PT

Network 21 INITIALIZE STEP 1 IF NO STEP IS ENERGIZED

STEP_0 STEP_1 STEP_2 STEP_3 STEP_4 STEP_5 STEP_6 STEP_7 STEP_8 STEP_9 STEP_10
/ / / / / / / / / / / 21.A

STEP_11 STEP_12 STEP_13 INI_STAGE_1


21.A / / /

11 / 103
E204048

Network 22 CALL MESSAGE FOR DRYER VALVES IN SYNCHRONIZATION

INI_STAGE_1 MESS_EV_15

Network 23 AUTOMATIC VALVE SYNCHRONIZED AND START AT STEP 0


INI_STAGE_1 PB_2A LS_LC_O LS_RC_O INI_TMR_1
/ IN TON

+100 PT

INI_TMR_1 INI_STAGE_2

INI_STAGE_2 LS_V3L_C LS_V3R_C LS_V4L_C LS_V4R_C INI_TMR_2


IN TON

+100 PT

INI_TMR_2 INI

SYNCRO_AL
IN TON

+300 PT

12 / 103
E204048

Network 24 DETECT ALARM IN SYNCHRONIZATION MODE

SYNCRO_AL SYNCRO_FAIL

SYNCRO_FAIL PB_2A
/

Network 25 CALL SUBROUTINES

ALWAYS_ON TMR_CNT
EN

BLW_HT
EN

VALVE
EN

AL_AUTO
EN

PANEL_VEW
EN

ANALOG
EN

DRYER_RECO~
EN

13 / 103
E204048

Network 26 USE FOR CLOCK CONVERSION

STEP_3 TIME_CONV
EN

STEP_4

STEP_6

STEP_10

STEP_11

STEP_13

14 / 103
E204048

Block: TMR_CNT
Author:
Created: 11/09/2001 01:12:48 pm
Last Modified: 01/06/2003 09:31:46 am

Network 1 TIMER USE FOR STEP ADVANCE


STEP_1 MOV_W FILL_N
EN ENO EN ENO

STEP_5 TIME_A IN OUT VW200 +0 IN OUT VW204


8 N

STEP_7

STEP_9

15 / 103
E204048

Network 2 TIMER USE FOR STEP ADVANCE

STEP_1 LS_RC_C PULSE_SEC TIME_A


CD CTD

STEP_5 LS_V3R_C LS_V4R_C

STEP_7 LS_RC_O

STEP_9 LS_V3L_O LS_V4L_O

STEP_1 STEP_5 STEP_7 STEP_9


/ / / / LD

+5 PV

Network 3 TIMER USE FOR STEP ADVANCE

STEP_3 TIME_AA
IN TON

STEP_11 +50 PT

STEP_13

16 / 103
E204048

Network 4 TIMER USE FOR STEP ADVANCE

STEP_0 MOV_W FILL_N


EN ENO EN ENO

STEP_2 TIME_B IN OUT VW200 +0 IN OUT VW204


8 N

STEP_8

STEP_12

17 / 103
E204048

Network 5 TIMER USE FOR STEP ADVANCE

STEP_0 LS_LC_O PULSE_SEC TIME_B


CD CTD

STEP_2 LS_V3R_O LS_V4R_O

STEP_8 LS_LC_C

STEP_12 LS_V3L_C LS_V4L_C

STEP_0 STEP_2 STEP_8 STEP_12


/ / / / LD

+5 PV

Network 6 TIMER USE FOR STEP ADVANCE

STEP_4 TIME_BB
IN TON

STEP_6 +50 PT

STEP_10

18 / 103
E204048

Network 7 MINIMUM HEATING COUNTER

STEP_3 PULSE_MIN MIN_HEAT MIN_HEAT


/ CU CTU

STEP_10

STEP_3 STEP_10
/ / R

+60 PV

Network 8 HEATING COUNTER

STEP_3 SEC_CLOCK HEAT_CNT HEAT_CNT


/ CD CTD

STEP_10

STEP_3 STEP_10
/ / LD

+300 PV

19 / 103
E204048

Network 9 MINIMUM COOLING COUNTER

STEP_4 PULSE_MIN MIN_COOL MIN_COOL


/ CU CTU

STEP_11

STEP_4 STEP_11
/ / R

+60 PV

Network 10 COOLING COUNTER

STEP_4 SEC_CLOCK COOL_CNT COOL_CNT


/ CD CTD

STEP_11

STEP_4 STEP_11
/ / LD

+300 PV

20 / 103
E204048

Network 11 WATCH DOG COUNTER FOR HALF CYCLE 24 HOURS COMPRESSOR TIME

STEP_0 STEP_7 COMP SEC_CLOCK WHT_DOG WHT_DOG


/ / / CD CTD

STEP_0
LD

STEP_7 +1440 PV

Network 12 AUTODEW WATCH DOG COUNTER FOR 24 HOURS


SW_2B WHT_DOG COMP SEC_CLOCK AUTO_WD AUTO_WD
/ CD CTD

WHT_DOG
/ LD

+1440 PV

21 / 103
E204048

Network 13 IN STAND BY IF DEW POINT BAD STEP AHEAD

STEP_6 PULSE_MIN STBY_DP_GO STBY_DP_GO


/ CU CTU

STEP_13

STEP_6 STEP_13
/ / R

+60 PV

Network 14 SECONDS PULSE COUNTER

ALWAYS_ON PULSE_SEC SEC_CLOCK


CD CTD

SEC_CLOCK
LD

+60 PV

22 / 103
E204048

Network 15 MINUTES COUNTER

ALWAYS_ON COMP PULSE_MIN MIN_CNT


CU CTU

MIN_CNT
R

+60 PV

Network 16 HOURS COUNTER


MIN_CNT HRS_CNT
CU CTU

PB_1A PB_2A PB_3


R

+32000 PV

23 / 103
E204048

Block: BLW_HT
Author:
Created: 11/09/2001 01:12:48 pm
Last Modified: 01/06/2003 09:31:48 am

Network 1 IGNITIATE BLOWER TO RUN IF NO NEGATIVE CONDITION


BLW_AL_LOW BLW_AL_HIGH BLW_FAIL BLW_STP_AL COOL_OT BLW
/ / / / /

Network 2 BLOWER STATOR MOTOR

STEP_3 LS_RC_C BLW COOL_CNT MS_1


/

STEP_4

STEP_10 LS_LC_C

STEP_11

24 / 103
E204048

Network 3 DELAY TO CHECK IF BLOWER RUNNING

MS_1 BLW_DELAY
IN TON

+100 PT

Network 4 INISIATE BLOWER OVERLOAD ALARM

BLW_DELAY O_L_1 BLW_FAIL

BLW_FAIL PB_2A
/

Network 5 INISIATE HIGH OR LOW DIFFERENTIAL PRESSURE BLOWER ALARM


BLW_DELAY LOW_DP BLW_AL_LOW

BLW_AL_LOW PB_2A
/

25 / 103
E204048

Network 6 INISIATE HIGH OR LOW DIFFERENTIAL PRESSURE BLOWER ALARM

BLW_DELAY HIGH_DP BLW_AL_HIGH

BLW_AL_HIGH PB_2A
/

Network 7 IGNITIATE HEATING MODE IF NO NEGATIVE CONDITION

COOL_OT OVER_TEMP HEAT_FAIL SHT_AL_HTR_1 SHT_AL_HTR_2 HTR_OUT_AL COOL_OT READY_HEAT


/ / / / /

Network 8 HEATER CONTACTOR

STEP_3 BLW_DELAY READY_HEAT HEAT_CNT BANK_1_LOCK C_1


/ /

STEP_10 C_2

Network 9 TEMPERATURE CONTROL FOR BANK 1

TT_1_HIGH BANK_1_LOCK

BANK_1_LOCK TT_1_LOW
/

26 / 103
E204048

Network 10 TIME OF 15 MINUTES TO CHECK IF HEATER FAIL TO HEAT

C_1 HEAT_CHK
IN TON

+9000 PT

Network 11 INTERLOCK HEATER FAIL TO HEAT ALARM

STEP_3 HEAT_CHK TT_2_LOW HEAT_FAIL

STEP_10

HEAT_FAIL PB_2A
/

Network 12 INTERLOCK HEATER OVERSHEATH BANK 1

SHT_AL_HTR_1 TSH_1_CR_3 SHT_AL_HTR_1


/

PB_2A

SM0.1

27 / 103
E204048

Network 13 INTERLOCK HEATER OVERSHEATH BANK 2

SHT_AL_HTR_2 TSH_2_CR_4 SHT_AL_HTR_2


/

PB_2A

SM0.1

Network 14 DELAY THE OVERTEMP WHEN BACK FROM POWER FAILURE


C_1 DELAY_PWR_O~
IN TON

+250 PT

Network 15 INTERLOCK HEATER OUTLET OVERTEMP

TSH_3_CR_5 DELAY_PWR_O~ HTR_OUT_AL

HTR_OUT_AL PB_2A
/

28 / 103
E204048

Network 16 COOLER FAN CONTROL RUNNING

STEP_3 TT_4_LOW COOL_ON


/

STEP_4 COOL_ON OFF_COOLER


/

STEP_10

STEP_11

Network 17 DELAY OF 90 SECONDES FOR COOLER OFF

STEP_3 TT_4_LOW OFF_COOLER


IN TON

STEP_4 +900 PT

STEP_10

STEP_11

29 / 103
E204048

Network 18 COOLER STATOR MOTOR

COOL_ON BLW_STP_AL COOL_FAIL MS_2


/ /

Network 19 DELAY FOR OVERLOAD


MS_2 COOL_DEL
IN TON

+100 PT

Network 20 INTERLOCK COOLER OVERLOAD

COOL_DEL O_L_2 COOL_FAIL

COOL_FAIL PB_2A
/

Network 21 TT 4 DELAY FOR TEMPERATURE READING

TT_4_HIGH TT4_DELAY
IN TON

+600 PT

30 / 103
E204048

Network 22 INTERLOCK COOLER OVER TEMP

TT4_DELAY COOL_OT

COOL_OT PB_2A
/

Network 23 DELAY TO STOP BLOWER IN ALARM

OVER_TEMP PULSE_MIN BLW_STP_AL BLW_STP_AL


/ CU CTU

HEAT_FAIL

SHT_AL_HTR_1
/

SHT_AL_HTR_2
/

HTR_OUT_AL

COOL_OT OVER_TEMP HEAT_FAIL SHT_AL_HTR_1 SHT_AL_HTR_2 HTR_OUT_AL


/ / / / R

PB_2A +15 PV

31 / 103
E204048

Block: VALVE
Author:
Created: 11/09/2001 01:12:48 pm
Last Modified: 01/06/2003 09:31:49 am

Network 1 TIMER FOR DRYER PURGING SYSTEM AT STEP 0 ONLY


SW_3A STEP_0 PURGE_ON PURGE_LOCK
IN TOF

+50 PT

Network 2 SOLENOID OPEN L/C INLET AND OUTLET VALVE


STEP_0 EV1L_2L_O

INI_STAGE_1

Network 3 SOLENOID CLOSE R/C INLET AND OUTLET VALVE

STEP_1 EV1R_2R_C

32 / 103
E204048

Network 4 SOLENOID OPEN R/C REGEN INLET AND OUTLET VALVES

STEP_2 EV3R_4R_O

SW_3A STEP_0 PURGE_ON

Network 5 SOLENOID CLOSE ALL REGEN INLET AND OUTLET VALVES

STEP_5 EV3_4_C

STEP_12

INI_STAGE_2

PURGE_ON PURGE_LOCK
/

Network 6 SOLENOID OPEN R/C INLET AND OUTLET VALVES


STEP_7 EV1R_2R_O

INI_STAGE_1

33 / 103
E204048

Network 7 SOLENOID CLOSE L/C INLET AND OUTLET VALVES

STEP_8 EV1L_2L_C

Network 8 SOLENOID OPEN L/C REGEN INLET AND OUTLET VALVES


STEP_9 EV3L_4L_O

SW_3A STEP_0 PURGE_ON

34 / 103
E204048

Network 9 SWITCHING FAILURE ALARM CONTROL

STEP_8 STEP_9 STEP_10 STEP_11 STEP_12 STEP_13 LS_LC_O PB_2A PURGE_ON SW_FAIL
/ / / / / / / / / IN TON

STEP_1 LS_RC_C SW_3A +200 PT


/ /

STEP_2

STEP_3

STEP_4

STEP_5

STEP_6

STEP_2 LS_V3R_O
/

STEP_3 LS_V4R_O
/

STEP_4

35 / 103
E204048

STEP_2 STEP_3 STEP_4 LS_V3R_C


/ / / /

LS_V4R_C
/

STEP_1 STEP_2 STEP_3 STEP_4 STEP_5 STEP_6 LS_RC_O


/ / / / / / /

STEP_8 LS_LC_C
/

STEP_9

STEP_10

STEP_11

STEP_12

STEP_13

STEP_9 LS_V3L_O
/

36 / 103
E204048

STEP_10 LS_V4L_O
/

STEP_11

STEP_9 STEP_10 STEP_11 LS_V3L_C


/ / / /

LS_V4L_C
/

Network 10 INTERLOCK SWITCHING FAILURE ALARM


SW_FAIL FAIL_SW

FAIL_SW PB_2A
/

37 / 103
E204048

Block: AL_AUTO
Author:
Created: 11/09/2001 01:12:48 pm
Last Modified: 01/06/2003 09:31:50 am

Network 1 HYGROMETER
SW_2A HHS

Network 2 SELECT HYGROMETER OFF AND DRYER IN FIXE CYCLE

SW_2A FIXE_CYCLE
/

Network 3 SELECT DRYER IN FIXE CYCLE AND HYGROMETER ON

SW_2A SW_2B METER_ON


/

Network 4 HHS 1 CONTROL AUTODEW IN AUTODEW MODE SELECTED


SW_2A SW_2B HHS_1 COMP HHS_1_DELAY HHS_1_DELAY
/ / IN TONR

+12000 PT

38 / 103
E204048

Network 5 DELAY HHS-1 CONTROL SWITCH

SW_2A HHS_1_DELAY
/ R
1
SW_2B
/

HHS_1

COMP
/

Network 6 DELAY DEWPOINT MESSAGE

HHS_1_DELAY DEWPOINT
/

Network 7 INDICATE HYGROMETER OFF

SW_2A HYGRO_OFF
/

39 / 103
E204048

Network 8 DELAY OF 20 MIN FOR HIGH HUMIDITY ALARM

SW_2A HHS_2 HH_DELAY HH_DELAY


/ IN TONR

+12000 PT

Network 9 RESET HIGH HUMIDITY TIMER ALARM

HHS_2 HH_DELAY
/ R
1
SW_2A
/

HH_DELAY PB_2A

Network 10 INTERLOCK HIGH HUMIDITY ALARM

HH_DELAY HIGH_HUM

HIGH_HUM PB_2A
/

40 / 103
E204048

Network 11 INTERLOCK HIGH LIQUID LEVEL IN SEPARATOR

LS_1 HIGH_LEVEL

HIGH_LEVEL PB_2A
/

Network 12 COMMON ALARM RELAY

FAIL_SW BLW_AL_HIGH BLW_AL_LOW BLW_FAIL HEAT_FAIL SHT_AL_HTR_1 SHT_AL_HTR_2 HTR_OUT_AL COOL_FAIL COOL_OT OVER_TEMP
/ / / / / / / / / 12.A

HIGH_HUM HIGH_LEVEL CR_1


12.A / /

41 / 103
E204048

Network 13 SELECT ALARM SCREEN IN ALARM CONDITION

FAIL_SW AL_MOVE
P

BLW_AL_HIGH
P

BLW_AL_LOW
P

BLW_FAIL
P

HEAT_FAIL
P

SHT_AL_HTR_1
/ P

SHT_AL_HTR_2
/ P

HTR_OUT_AL
P

COOL_FAIL
P

COOL_OT
P

42 / 103
E204048

OVER_TEMP
P

HIGH_HUM
P

HIGH_LEVEL
P

Network 14 INDICATE DRYER IN ALARM

CR_1 IL_3
/

SW_3A PB_1A
/

43 / 103
E204048

Block: PANEL_VEW
Author:
Created: 11/09/2001 01:12:48 pm
Last Modified: 01/06/2003 09:31:53 am

Network 1 SELECT LEFT CHAMBER DRYING


STEP_0 MESS_EV_01

Network 2 LEFT CHAMBER DRYING CLOSE RIGHT CHAMBER INLET AND OUTLET VALVES

STEP_1 MESS_EV_02

Network 3 LEFT CHAMBER DRYING OPEN RIGHT CHAMBER REGEN VALVES

STEP_2 MESS_EV_03

Network 4 LEFT CHAMBER DRYING RIGHT CHAMBER IN HEATING MODE


STEP_3 MESS_EV_04

Network 5 LEFT CHAMBER DRYING RIGHT CHAMBER IN COOLING MODE


STEP_4 MESS_EV_05

44 / 103
E204048

Network 6 LEFT CHAMBER DRYING CLOSE RIGHT CHAMBER REGEN VALVES

STEP_5 MESS_EV_06

Network 7 LEFT CHAMBER DRYING RIGHT CHAMBER IN STAND BY


STEP_6 MESS_EV_07

Network 8 SELECT RIGHT CHAMBER DRYING


STEP_7 MESS_EV_08

Network 9 RIGHT CHAMBER DRYING CLOSE LEFT CHAMBER INLET AND OUTLET VALVES

STEP_8 MESS_EV_09

Network 10 RIGHT CHAMBER DRYING OPEN LEFT CHAMBER REGEN VALVES

STEP_9 MESS_EV_10

Network 11 RIGHT CHAMBER DRYING LEFT CHAMBER IN HEATING MODE


STEP_10 MESS_EV_11

45 / 103
E204048

Network 12 RIGHT CHAMBER DRYING LEFT CHAMBER IN COOLING MODE

STEP_11 MESS_EV_12

Network 13 RIGHT CHAMBER DRYING CLOSE LEFT CHAMBER REGEN VALVES


STEP_12 MESS_EV_13

Network 14 RIGHT CHAMBER DRYING LEFT CHAMBER IN STAND BY


STEP_13 MESS_EV_14

46 / 103
E204048

Network 15 LEFT CHAMBER INLET AND OUTLET VALVES FAIL TO OPEN

STEP_0 FAIL_SW LS_LC_O MESS_AL_01


/

STEP_1

STEP_2

STEP_3

STEP_4

STEP_5

STEP_6

STEP_7

47 / 103
E204048

Network 16 RIGHT CHAMBER INLET AND OUTLET VALVES FAIL TO CLOSE

STEP_1 FAIL_SW LS_RC_C MESS_AL_04


/

STEP_2

STEP_3

STEP_4

STEP_5

STEP_6

Network 17 RIGHT CHAMBER REGEN INLET FAIL TO OPEN

STEP_2 FAIL_SW LS_V3R_O MESS_AL_07


/

STEP_3

STEP_4

48 / 103
E204048

Network 18 RIGHT CHAMBER REGEN OUTLET FAIL TO OPEN

STEP_2 FAIL_SW LS_V4R_O MESS_AL_11


/

STEP_3

STEP_4

Network 19 RIGHT CHAMBER REGEN INLET FAIL TO CLOSE


STEP_2 STEP_3 STEP_4 FAIL_SW LS_V3R_C MESS_AL_08
/ / / /

Network 20 RIGHT CHAMBER REGEN OUTLET FAIL TO CLOSE


STEP_2 STEP_3 STEP_4 FAIL_SW LS_V4R_C MESS_AL_12
/ / / /

49 / 103
E204048

Network 21 RIGHT CHAMBER INLET AND OUTLET FAIL TO OPEN

STEP_7 FAIL_SW LS_RC_O MESS_AL_03


/

STEP_8

STEP_9

STEP_10

STEP_11

STEP_12

STEP_13

STEP_0

50 / 103
E204048

Network 22 LEFT CHAMBER INLET AND OUTLET FAIL TO CLOSE

STEP_8 FAIL_SW LS_LC_C MESS_AL_02


/

STEP_9

STEP_10

STEP_11

STEP_12

STEP_13

Network 23 LEFT CHAMBER REGEN INLET FAIL TO OPEN

STEP_9 FAIL_SW LS_V3L_O MESS_AL_05


/

STEP_10

STEP_11

51 / 103
E204048

Network 24 LEFT CHAMBER REGEN OUTLET FAIL TO OPEN

STEP_9 FAIL_SW LS_V4L_O MESS_AL_09


/

STEP_10

STEP_11

Network 25 LEFT CHAMBER REGEN INLET FAIL TO CLOSE


STEP_9 STEP_10 STEP_11 FAIL_SW LS_V3L_C MESS_AL_06
/ / / /

Network 26 LEFT CHAMBER REGEN OUTLET FAIL TO CLOSE


STEP_9 STEP_10 STEP_11 FAIL_SW LS_V4L_C MESS_AL_10
/ / / /

Network 27 INDICATE ACCUMALATOR HIGH LEVEL

HIGH_LEVEL MESS_AL_13

52 / 103
E204048

Network 28 INDICATE DRYER OUTLET HIGH HUMIDITY ALARM

HIGH_HUM MESS_AL_14

Network 29 INDICATE BLOWER MOTOR OVERLOAD


BLW_FAIL MESS_AL_15

Network 30 INDICATE BLOWER HIGH DIFFERENTIAL PRESSURE


BLW_AL_HIGH MESS_AL_16

Network 31 INDICATE LOW DIFFERENTIAL PRESSURE

BLW_AL_LOW MESS_AL_17

Network 32 INDICATE COOLER MOTOR OVERLOAD

COOL_FAIL MESS_AL_18

Network 33 INDICATE COOLER OUTLET HIGH TEMPERATURE


COOL_OT MESS_AL_19

53 / 103
E204048

Network 34 INDICATE HEATER OUTLET OVERTEMP

HTR_OUT_AL MESS_AL_20

Network 35 INDICATE HEATER BANK 1 OVERSHEATH


SHT_AL_HTR_1 MESS_AL_21
/

Network 36 INDICATE HEATER BANK 2 OVERSHEATH


SHT_AL_HTR_2 MESS_AL_23
/

Network 37 INDICATE HEATER FAIL TO HEAT

HEAT_FAIL MESS_AL_22

Network 38 INDICATE A FAULT DURING THE VALVES SYNCHRONISATION

SYNCRO_FAIL M13.7

54 / 103
E204048

Network 39 INDICATE NO ALARM IF (MESS_AL_23) IS DE-ENERGIZED

MESS_AL_01 NO_ALARM

MESS_AL_02

MESS_AL_03

MESS_AL_04

MESS_AL_05

MESS_AL_06

MESS_AL_07

MESS_AL_08

MESS_AL_09

MESS_AL_10

55 / 103
E204048

MESS_AL_11

MESS_AL_12

MESS_AL_13

MESS_AL_14

MESS_AL_15

MESS_AL_16

MESS_AL_17

MESS_AL_18

MESS_AL_19

MESS_AL_20

56 / 103
E204048

MESS_AL_21

MESS_AL_22

Network 40 SCREEN SELECTOR SYSTEM


PB_3 PB_1A SCREEN_SEL
/ P CU CTU

SCREEN_SEL
R

+9 PV

Network 41 RESET SCREEN AT #1 IF C15 IS AT 0


SCREEN_SEL MOV_W
>=I EN ENO
+7
+1 IN OUT SCREEN_SEL

57 / 103
E204048

Network 42 5 MIN DELAY IF NO SCREEN ARE SELECTED TO GO AT SCREEN NUMBER 1

PB_1A PB_3 SCREEN_SEL SCREEN_DEL SCREEN_DEL


/ / <>I / IN TONR
+5
+32000 PT

Network 43 RESET SCREEN DELAY TIMER

PB_3 SCREEN_DEL
R
1

Network 44 MOVE NUMBER 1 TO COUNTER C15

SCREEN_DEL MOV_W
EN ENO

+5 IN OUT SCREEN_SEL

Network 45 IN ALARM SELECT THE ALARM SCREEN

CR_1 MOV_W
/ P EN ENO

+4 IN OUT SCREEN_SEL

58 / 103
E204048

Network 46 INDICATE BLOWER RUNNING

MS_1 BLOWER_ON

Network 47 STEPPER USE FOR DEGRES C OR F SELECTED


STEP_D PB_4 TIME_C STEP_B STEP_A
/ /

STEP_A

INI

Network 48 STEPPER USE FOR DEGRES C OR F SELECTED


STEP_A PB_4 TIME_D STEP_C STEP_B
/

STEP_B

59 / 103
E204048

Network 49 STEPPER USE FOR DEGRES C OR F SELECTED

STEP_B PB_4 TIME_C STEP_D STEP_C


/ /

STEP_C

Network 50 STEPPER USE FOR DEGRES C OR F SELECTED

STEP_C PB_4 TIME_D STEP_A STEP_D


/

STEP_D

Network 51 TIMER USE TO ALLOW STEP


STEP_D PULSE_SEC TIME_C TIME_C
/ CU CTU

STEP_B

STEP_D STEP_B
/ / R

+2 PV

60 / 103
E204048

Network 52 TIMER USE TO ALLOW STEP

STEP_A PULSE_SEC TIME_D TIME_D


/ CU CTU

STEP_C

STEP_A STEP_C
/ / R

+2 PV

Network 53 SELECT DEGRES C OR F

STEP_A DEGRE_C_F

STEP_C

61 / 103
E204048

Block: ANALOG
Author:
Created: 11/09/2001 01:12:48 pm
Last Modified: 01/15/2003 11:48:32 am

Network 1
M16.0 M16.1 MOV_W
/ EN ENO

+24 IN OUT SMW32

SM31.0
S
1
SM31.1
S
1
SM31.7
S
1
M16.1
S
1
M16.0
S
1

62 / 103
E204048

Network 2
M16.0 M16.1 SM31.7 MOV_W
/ EN ENO

+30 IN OUT SMW32

SM31.0
S
1
SM31.1
S
1
SM31.7
S
1
M16.0
R
1
M16.1
R
1

Network 3
ALWAYS_ON VD24 MOV_R
==R EN ENO
0.0
-40.0 IN OUT VD24

63 / 103
E204048

Network 4
ALWAYS_ON VD30 MOV_R
==R EN ENO
0.0
-35.0 IN OUT VD30

Network 5
ALWAYS_ON SUB_R
EN ENO

VD24 IN1 OUT VD34


2.0 IN2

Network 6 INDICATE DEW POINT GOOD, TOP DEGREES F°AND BOTTOM DEGREES C°
VD20 HHS_1
<=R
VD34
HHS_1 VD20
<=R
VD24

64 / 103
E204048

Network 7
ALWAYS_ON SUB_R
EN ENO

VD30 IN1 OUT VD34


2.0 IN2

Network 8 INDICATE DEW POINT BAD, TOP DEGREES F°AND BOTTOM DEGREES C°

VD20 HHS_2
>=R
VD30
HHS_2 VD20
>=R
VD34

65 / 103
E204048

Network 9 BLOWER DIFFERENTIAL PRESSURE CONTROL

ALWAYS_ON SHR_W
EN ENO

AIW8 IN OUT VW16


3 N

MUL
EN ENO

VW16 IN1 OUT VD4


+15 IN2

DI_R
EN ENO

VD4 IN OUT VD4

DIV_R
EN ENO

VD4 IN1 OUT VD8


3276.0 IN2

SUB_R
EN ENO

VD8 IN1 OUT VD12


3.690476 IN2

66 / 103
E204048

Network 10 DELAY FOR LOW DIFFERENTIAL PRESSURE ALARM

VD12 TIME_LDP
<=R IN TON
0.2
+100 PT

Network 11 INDICATE LOW DIFFERENTIAL PRESSURE ALARM

TIME_LDP LOW_DP

Network 12 DELAY FOR HIGH DIFFERENTIAL PRESSURE ALARM

VD12 TIME_HDP
>=R IN TON
6.0
+100 PT

Network 13 INDICATE HIGH DIFFERENTIAL PRESSURE ALARM

TIME_HDP HIGH_DP

67 / 103
E204048

Network 14 HYGROMETER DEGREES C

PB_4 SW_2A T60 SHR_W SHR_W


/ / EN ENO EN ENO

AIW10 IN OUT AC0 AIW10 IN OUT VW500


3 N 3 N

MUL
EN ENO

+216 IN1 OUT AC0


AC0 IN2

DI_R
EN ENO

AC0 IN OUT AC0

DIV_R
EN ENO

AC0 IN1 OUT AC0


3198.0 IN2

SUB_R
EN ENO

AC0 IN1 OUT VD20


201.8 IN2

68 / 103
E204048

Network 15 INDICATE DEW POINT FAIL IF PROBE OPEN OR DEFECT

PB_4 VD20 DEW_FAIL


/ <=R
-148.0
PB_4 VD20
<=R
-100.0

Network 16 WHEN HYGROMETER OFF INDICATE 0.0 DEGREE

SW_2A MOV_R
/ EN ENO

T60 0.0 IN OUT VD20

SW_2A T60
/ IN TOF

+100 PT

69 / 103
E204048

Network 17 HYGROMETER DEGREES F

PB_4 SW_2A T60 SHR_W SHR_W


/ EN ENO EN ENO

AIW10 IN OUT AC0 AIW10 IN OUT VW500


3 N 3 N

MUL
EN ENO

+120 IN1 OUT AC0


AC0 IN2

DI_R
EN ENO

AC0 IN OUT AC0

DIV_R
EN ENO

AC0 IN1 OUT AC0


3198.0 IN2

SUB_R
EN ENO

AC0 IN1 OUT VD20


129.9 IN2

70 / 103
E204048

Network 18 HEATER OUTLET BANK 1 DEGREE °F

DEG_C_F DIV_I
EN ENO

AIW0 IN1 OUT MW22


+10 IN2

Network 19 BANK 1 STOP HEATING

DEG_C_F MW22 TT_1_HIGH


>=I
+350
DEG_C_F MW22
/ >=I
+176

Network 20 BANK 1 RE-START HEATING


DEG_C_F MW22 TT_1_LOW
<=I
+300
DEG_C_F MW22
/ <=I
+148

71 / 103
E204048

Network 21 HEATER OUTLET BANK 1 DEGREE °C

DEG_C_F DIV_I SUB_I


/ EN ENO EN ENO

AIW0 IN1 OUT MW22 MW22 IN1 OUT MW22


+10 IN2 +32 IN2

MUL_I
EN ENO

+5 IN1 OUT MW22


MW22 IN2

DIV_I
EN ENO

MW22 IN1 OUT MW22


+9 IN2

Network 22 HEATER OUTLET BANK 2 DEGREE °F

DEG_C_F DIV_I
EN ENO

AIW2 IN1 OUT MW24


+10 IN2

72 / 103
E204048

Network 23 CHECK HEATER FAILURE BANK 2

DEG_C_F MW24 TT_2_LOW


<=I
+250
DEG_C_F MW24
/ <=I
+120

Network 24 HEATER OUTLET BANK 2 DEGREE °C

DEG_C_F DIV_I SUB_I


/ EN ENO EN ENO

AIW2 IN1 OUT MW24 MW24 IN1 OUT MW24


+10 IN2 +32 IN2

MUL_I
EN ENO

+5 IN1 OUT MW24


MW24 IN2

DIV_I
EN ENO

MW24 IN1 OUT MW24


+9 IN2

73 / 103
E204048

Network 25 START HEATING CONTROL SCR

DEG_C_F MW24 MOV_W


>=I EN ENO
+425
DEG_C_F MW24 +0 IN OUT AQW0
/ >=I
+218

Network 26 STOP HEATING CONTROL SCR

DEG_C_F MW24 MOV_W


<I EN ENO
+425
DEG_C_F MW24 +32000 IN OUT AQW0
/ <I
+218

Network 27 COOLER INLET DEGREE °F


DEG_C_F DIV_I
EN ENO

AIW4 IN1 OUT MW26


+10 IN2

74 / 103
E204048

Network 28 COOLER INLET

DEG_C_F MW26 TT_3_HIGH


>=I
+200
DEG_C_F MW26
/ >=I
+93

Network 29 COOLER INLET

DEG_C_F MW26 TT_3_LOW


<=I
+120
DEG_C_F MW26
/ <=I
+49

75 / 103
E204048

Network 30 COOLER INLET DEGREE °C

DEG_C_F DIV_I SUB_I


/ EN ENO EN ENO

AIW4 IN1 OUT MW26 MW26 IN1 OUT MW26


+10 IN2 +32 IN2

MUL_I
EN ENO

+5 IN1 OUT MW26


MW26 IN2

DIV_I
EN ENO

MW26 IN1 OUT MW26


+9 IN2

Network 31 COOLER OUTLET DEGREE °F

DEG_C_F DIV_I
EN ENO

AIW6 IN1 OUT MW28


+10 IN2

76 / 103
E204048

Network 32 COOLER OUTLET

DEG_C_F MW28 TT_4_HIGH


>=I
+135
DEG_C_F MW28
/ >=I
+57

Network 33 COOLER OUTLET

DEG_C_F MW28 TT_4_LOW


<=I
+80
DEG_C_F MW28
/ <=I
+26

77 / 103
E204048

Network 34 COOLER OUTLET DEGREE °C

DEG_C_F DIV_I SUB_I


/ EN ENO EN ENO

AIW6 IN1 OUT MW28 MW28 IN1 OUT MW28


+10 IN2 +32 IN2

MUL_I
EN ENO

+5 IN1 OUT MW28


MW28 IN2

DIV_I
EN ENO

MW28 IN1 OUT MW28


+9 IN2

78 / 103
E204048

Block: TIME_CONV
Author:
Created: 04/02/2002 11:02:27 am
Last Modified: 01/06/2003 09:31:57 am

Network 1 INTERNAL CLOCK SECONDS


ALWAYS_ON SEC_CLOCK SUB_I
>I EN ENO
+0
SEC_CLOCK IN1 OUT VW200
+1 IN2

Network 2 HEAT COUNTER CLOCK


STEP_3 SUB_I
EN ENO

STEP_10 HEAT_CNT IN1 OUT AC1


+1 IN2

Network 3 COOLING COUNTER CLOCK

STEP_4 SUB_I
EN ENO

STEP_11 COOL_CNT IN1 OUT AC1


+1 IN2

79 / 103
E204048

Network 4 AUTODEW WATCH DOG COUNTER CLOCK

STEP_6 SW_2B HHS_1_DELAY ADD_I SUB_I


/ EN ENO EN ENO

STEP_13 AUTO_WD IN1 OUT AC1 AC1 IN1 OUT AC1


WHT_DOG IN2 +1 IN2

Network 5 WATCH DOG COUNTER CLOCK

STEP_6 SW_2B SUB_I


/ EN ENO

STEP_13 WHT_DOG IN1 OUT AC1


+1 IN2

Network 6 INTERNAL CLOCK SYSTEM


ALWAYS_ON I_DI DI_R DIV_R
EN ENO EN ENO EN ENO 6.A

AC1 IN OUT AC1 AC1 IN OUT AC1 AC1 IN1 OUT AC2 AC2
60.0 IN2

TRUNC DI_R
6.A EN ENO EN ENO

IN OUT VD208 VD208 IN OUT AC3

80 / 103
E204048

Network 7 INTERNAL CLOCK SYSTEM

ALWAYS_ON SUB_R MUL_R ROUND


EN ENO EN ENO EN ENO

AC2 IN1 OUT AC3 60.0 IN1 OUT AC3 AC3 IN OUT VD204
AC3 IN2 AC3 IN2

Network 8 INTERNAL STAND BY CLOCK

STEP_6 COMP MOV_W


/ EN ENO

STEP_13 +0 IN OUT VW200

81 / 103
E204048

Block: DRYER_RECORD
Author:
Created: 08/28/2002 10:18:25 am
Last Modified: 01/06/2003 09:32:01 am

Network 1
PB_1A RESET_CNT
IN TON

+150 PT

Network 2 SELECT AUTODEW MODE


SW_2A SW_2B C20
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

82 / 103
E204048

Network 3 COUNT WHEN HYGROMETER IS OFF

SW_2A SW_2B C21


/ / CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

Network 4 COUNT DRYER IN FIXE CYCLE AND HYGROMETER ON


SW_2A SW_2B C22
/ CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

83 / 103
E204048

Network 5 IN AUTODEW MODE COUNT THE SIGNAL FROM BAD DEWPOINT

SW_2A SW_2B HHS_1 C23


CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

Network 6 HIGH HUMIDITY ALARM


HIGH_HUM C24
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

84 / 103
E204048

Network 7 SELECT MANUAL MODE

SW_3A C25
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

Network 8 STEP ADVANCE IN MANUAL MODE


SW_3A PB_1A C26
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

85 / 103
E204048

Network 9 COMPRESSOR CONTACT COUNT COMPRESSOR START

COMP C27
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

Network 10 COUNT POWER FAILURE OR DRYER SHUT DOWN


SM0.1 C28
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

86 / 103
E204048

Network 11 PLC RUN SWITCH COUNTER

SM0.7 C29
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

Network 12 DRYER ALARM INDICATOR IL 3


IL_3 C30
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

87 / 103
E204048

Network 13 RESET COUNTER

PB_2A C56
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

88 / 103
E204048

Network 14 LEFT CHAMBER INLET V1L & V2L FAIL TO OPEN

SW_FAIL STEP_0 LS_LC_O C31


/ CU CTU

STEP_1

STEP_2

STEP_3

STEP_4

STEP_5

STEP_6

STEP_7

SW_3A RESET_CNT
/ R

+9999 PV

89 / 103
E204048

Network 15 LEFT CHAMBER INLET V1L & V2L FAIL TO CLOSE

SW_FAIL STEP_8 LS_LC_C C32


/ CU CTU

STEP_9

STEP_10

STEP_11

STEP_12

STEP_13

SW_3A RESET_CNT
/ R

+9999 PV

90 / 103
E204048

Network 16 RIGHT CHAMBER INLET V1R & V2R FAIL TO OPEN

SW_FAIL STEP_7 LS_RC_O C33


/ CU CTU

STEP_8

STEP_9

STEP_10

STEP_11

STEP_12

STEP_13

STEP_0

SW_3A RESET_CNT
/ R

+9999 PV

91 / 103
E204048

Network 17 RIGHT CHAMBER INLET V1R & V2R FAIL TO CLOSE

SW_FAIL STEP_1 LS_RC_C C34


/ CU CTU

STEP_2

STEP_3

STEP_4

STEP_5

STEP_6

SW_3A RESET_CNT
/ R

+9999 PV

92 / 103
E204048

Network 18 LEFT CHAMBER REGEN V3L FAIL TO OPEN

SW_FAIL STEP_9 LS_V3L_O C35


/ CU CTU

STEP_10

STEP_11

SW_3A RESET_CNT
/ R

+9999 PV

Network 19 LEFT CHAMBER REGEN V3L FAIL TO CLOSE


SW_FAIL STEP_9 STEP_10 STEP_11 LS_V3L_C C36
/ / / / CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

93 / 103
E204048

Network 20 RIGHT CHAMBER REGEN V3R FAIL TO OPEN

SW_FAIL STEP_2 LS_V3R_O C37


/ CU CTU

STEP_3

STEP_4

SW_3A RESET_CNT
/ R

+9999 PV

Network 21 LEFT CHAMBER REGEN V3R FAIL TO CLOSE


SW_FAIL STEP_2 STEP_3 STEP_4 LS_V3R_C C38
/ / / / CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

94 / 103
E204048

Network 22 LEFT CHAMBER REGEN V4L FAIL TO OPEN

SW_FAIL STEP_9 LS_V4L_O C39


/ CU CTU

STEP_10

STEP_11

SW_3A RESET_CNT
/ R

+9999 PV

Network 23 LEFT CHAMBER REGEN V4L FAIL TO CLOSE


SW_FAIL STEP_9 STEP_10 STEP_11 LS_V4L_C C40
/ / / / CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

95 / 103
E204048

Network 24 RIGHT CHAMBER REGEN V4R FAIL TO OPEN

SW_FAIL STEP_2 LS_V4R_O C41


/ CU CTU

STEP_3

STEP_4

SW_3A RESET_CNT
/ R

+9999 PV

Network 25 LEFT CHAMBER REGEN V4R FAIL TO CLOSE


SW_FAIL STEP_2 STEP_3 STEP_4 LS_V4R_C C42
/ / / / CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

96 / 103
E204048

Network 26 SEPARATOR HIGH LEVEL ALARM

LS_1 C43
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

Network 27 BLOWER RUNNING


MS_1 C44
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

97 / 103
E204048

Network 28 BLOWER OVERLOAD ALARM

BLW_FAIL C45
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

Network 29 BLOWER LOW DIFFERENTIAL PRESSURE ALARM


BLW_AL_LOW C46
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

98 / 103
E204048

Network 30 BLOWER HIGH DIFFERENTIAL PRESSURE ALARM

BLW_AL_HIGH C47
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

Network 31 HEATER OUTLET OVERTEMP ALARM


HTR_OUT_AL C48
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

99 / 103
E204048

Network 32 HEATER FAIL TO HEAT ALARM

HEAT_FAIL C49
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

Network 33 HEATER BANK 1 OVERSHEATH ALARM


SHT_AL_HTR_1 C50
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

100 / 103
E204048

Network 34 HEATER BANK 2 OVERSHEATH ALARM

SHT_AL_HTR_2 C51
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

Network 35 COOLER RUNNING


MS_2 C52
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

101 / 103
E204048

Network 36 COOLER OVERLOAD ALARM

COOL_FAIL C53
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

Network 37 COOLER OUTLET OVERTEMP ALARM


COOL_OT C54
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

102 / 103
E204048

Network 38 FULL CYCLE COUNTER

STEP_0 C55
CU CTU

SW_3A RESET_CNT
/ R

+9999 PV

103 / 103