You are on page 1of 1

`

Summary of Design & Verification Report


Comparison Sheet
Item Description Remarks
Equipment Schedule As Per RFI As per Design Concluded Proposed
(As built Drawing) Verification Capacity & size

FAHU-B-1 & Accessories

1 Supply Air & Outdoor Air flow rate 800 l/s (1685 cfm) 944 l/s (2000 cfm) 844 l/s (1788 cfm) 944 l/s (2000 cfm)

2 External Static Pressure (ESP) ? - 160 200

3 Supply Air discharge duct size (main) 550 x 350mm - ? ?

4 Outdoor Fresh Air duct size 550 x 350mm - ? ?

5 Outdoor Fresh Air Louver size (FAL-1) 750 x 400mm - ? ?


As per Tata (2000 CFM), value
6 Chilled water flow rate 1.58l/s (3.37cfm) - ? ? will change
7 Chilled water pipe & valves size 50 & 45 (As per Existing) - ? ?

FAHU-B-2 & Accessories

1 Supply Air & Outdoor Air flow rate 820 l/s (1737 cfm) 944 l/s (2000 cfm) 826 l/s (1750 cfm) 944 l/s (2000 cfm)

2 External Static Pressure (ESP) ? - ? ?

3 Supply Air discharge duct size (main) 600 x 350mm - ? ?

4 Outdoor Fresh Air duct size 600 x 350mm - ? ?

5 Outdoor Fresh Air Louver size (FAL-2) 750 x 375mm - ? ?

6 Chilled water flow rate 1.58l/s (3.37cfm) - ? ?

7 Chilled water pipe & valves size ? - ? ?

FAHU-B-3 & Accessories

1 Supply Air & Outdoor Air flow rate 800 l/s (1685 cfm) 944 l/s (2000 cfm) ? ?

2 External Static Pressure (ESP) ? - ? ?

3 Supply Air discharge duct size (main) ? - ? ?

4 Outdoor Fresh Air duct size ? - ? ?

5 Outdoor Fresh Air Louver size (FAL-2) ? - ? ?

6 Chilled water flow rate 1.38l/s (2.92cfm) - ? ?

7 Chilled water pipe & valves size ? - ? ?

FAHU-B-4 & Accessories

1 Supply Air & Outdoor Air flow rate 675 l/s (1430 cfm) 944 l/s (2000 cfm) ? ?

2 External Static Pressure (ESP) ? - ? ?

3 Supply Air discharge duct size (main) ? - ? ?

4 Outdoor Fresh Air duct size ? - ? ?

5 Outdoor Fresh Air Louver size (FAL-2) ? - ? ?

6 Chilled water flow rate 1.32/s (2.79cfm) - ? ?

7 Chilled water pipe & valves size ? - ? ?