You are on page 1of 19

SKE4 11 equipos EDIFICIO A

Project Information

Project Number: SK231010026

Project Name: SKE4 23 equipos EDIFICIO A

Project Date: 05/04/2023

Customer Name: TROX

Customer Address:

Customer Purchase Order Number:

Location: Ciudad de México

Engineer: Mónica Rodríguez

Agent (Salesperson): Haften S.A. de C.V. / Mario Roman

Notes:
Product and Option Schedule:
Tag
Air Conditions Edificio A(Hum-1) Edificio A[2](Hum-1) Edificio A[3](Hum-1)
Temperature
External
R.H.
Temperature
Entering
R.H.
Temperature
Indoor
R.H.
Outdoor Air
Total Air Flow
Mechanical
Outside Air
Total Air Flow
Economizer Mixed Air
Temp.
Building
Natural Volume
Air Changes/hr
Humidifier Selection
Calculated Load
Humidifier Capacity 13.62kg/hr 13.62kg/hr 13.62kg/hr
Humidifier Model SKE4-N10M-480-3 SKE4-N10M-480-3 SKE4-N10M-480-3
Signal Modulating Modulating Modulating
Power 10kW 10kW 10kW
Voltage/Phase/Cycle 480/3/60hz 480/3/60hz 480/3/60hz
Amperage 12A 12A 12A
Dispersion Selection
Dimensions Width 500mm 500mm 500mm
Duct/AHU Height 840mm 840mm 840mm
Air Temp. before humidification
Entering
R.H.
Leaving
Dispersion Model (# of tubes) SAME2 (1) H SAME2 (1) H SAME2 (1) H
Absorption distance
Controls and LO Hose 35, NF LO Hose 35, NF LO Hose 35, NF
Accessories SHS80, SW APS SHS80, SW APS SHS80, SW APS

Note
Tag
Air Conditions Edificio A[4](Hum-1) Edificio A[5](Hum-1) Edificio A[6](Hum-1)
Temperature
External
R.H.
Temperature
Entering
R.H.
Temperature
Indoor
R.H.
Outdoor Air
Total Air Flow
Mechanical
Outside Air
Total Air Flow
Economizer Mixed Air
Temp.
Building
Natural Volume
Air Changes/hr
Humidifier Selection
Calculated Load
Humidifier Capacity 13.62kg/hr 13.62kg/hr 13.62kg/hr
Humidifier Model SKE4-N10M-480-3 SKE4-N10M-480-3 SKE4-N10M-480-3
Signal Modulating Modulating Modulating
Power 10kW 10kW 10kW
Voltage/Phase/Cycle 480/3/60hz 480/3/60hz 480/3/60hz
Amperage 12A 12A 12A
Dispersion Selection
Dimensions Width 500mm 500mm 500mm
Duct/AHU Height 840mm 840mm 840mm
Air Temp. before humidification
Entering
R.H.
Leaving
Dispersion Model (# of tubes) SAME2 (1) H SAME2 (1) H SAME2 (1) H
Absorption distance
Controls and LO Hose 35, NF LO Hose 35, NF LO Hose 35, NF
Accessories SHS80, SW APS SHS80, SW APS SHS80, SW APS

Note
Tag
Air Conditions Edificio A(Hum-1) Edificio A [2](Hum-1) Edificio A(Hum-1)
Temperature
External
R.H.
Temperature
Entering
R.H.
Temperature
Indoor
R.H.
Outdoor Air
Total Air Flow
Mechanical
Outside Air
Total Air Flow
Economizer Mixed Air
Temp.
Building
Natural Volume
Air Changes/hr
Humidifier Selection
Calculated Load
Humidifier Capacity 13.62kg/hr 13.62kg/hr 18.16kg/hr
Humidifier Model SKE4-N10M-480-3 SKE4-N10M-480-3 SKE4-N14M-480-3
Signal Modulating Modulating Modulating
Power 10kW 10kW 13.5kW
Voltage/Phase/Cycle 480/3/60hz 480/3/60hz 480/3/60hz
Amperage 12A 12A 16.5A
Dispersion Selection
Dimensions Width 600mm 600mm 700mm
Duct/AHU Height 840mm 840mm 840mm
Air Temp. before humidification
Entering
R.H.
Leaving
Dispersion Model (# of tubes) SAME2 (1) H SAME2 (1) H SAME2 (1) H
Absorption distance
Controls and LO Hose 35, NF LO Hose 35, NF LO Hose 35, NF
Accessories SHS80, SW APS SHS80, SW APS SHS80, SW APS

Note
Tag
Air Conditions Edificio A[2](Hum-1) Edificio A[3](Hum-1)
Temperature
External
R.H.
Temperature
Entering
R.H.
Temperature
Indoor
R.H.
Outdoor Air
Total Air Flow
Mechanical
Outside Air
Total Air Flow
Economizer Mixed Air
Temp.
Building
Natural Volume
Air Changes/hr
Humidifier Selection
Calculated Load
Humidifier Capacity 18.16kg/hr 18.16kg/hr
Humidifier Model SKE4-N14M-480-3 SKE4-N14M-480-3
Signal Modulating Modulating
Power 13.5kW 13.5kW
Voltage/Phase/Cycle 480/3/60hz 480/3/60hz
Amperage 16.5A 16.5A
Dispersion Selection
Dimensions Width 700mm 700mm
Duct/AHU Height 840mm 840mm
Air Temp. before humidification
Entering
R.H.
Leaving
Dispersion Model (# of tubes) SAME2 (1) H SAME2 (1) H
Absorption distance
Controls and LO Hose 35, NF LO Hose 35, NF
Accessories SHS80, SW APS SHS80, SW APS

Note
Product Description
CABINET: The compartmentalized enclosure separates the plumbing, controls, and high-voltage sections to simplify
access to the different trades required to install, maintain, and commission the humidifier.
- Cold roll steel and stainless base with baked enamel finish. Key locked access doors.
- Plumbing and high-voltage access panels hang on the edge of the humidifier for easy storage.

HUMIDIFIER CONTROL: Microprocessor-based controller with 128x64 pixel LCD, menu-driven configuration, and 8
configuration buttons including auto/off and drain buttons.
- User rights management to display only menu functions available to the type of user logged in
- Quick Config Menu displays only the most commonly used functions for faster and easier installation
- Independent schedules for unit operation and drain cycle
- In-field firmware upgradeable via SD card, USB or BACnet
- Simple viewing and exporting of trending log and alarm log
- Optional BMS integration via BACnet MS/TP or Modbus
- Optional Ethernet module for BACnet IP/Modbus IP and web services for remote configuration and diagnostics

PIPING: Tubing is molded silicone eliminating junctions that could leak and allows for the use of any water type (tap, DI
or RO).

VALVES: Inlet: Quiet solenoid. Drain: Motorized pump. A manual drain valve permits draining of the evaporation
chamber even during a power failure.

EVAPORATION CHAMBER: Permanent stainless steel evaporation chamber can be removed by accessing only the
evaporation chamber – all other components, such as the heating elements and the steam hose remain permanently fixed.
Access the evaporation chamber without any tools by removing the water inlet quick connect, disengaging the latches, and
sliding the chamber down using the unique rail-guided system. The evaporation chamber hangs freely on the edge of the
humidifier eliminating the need to lift the chamber and place it on the floor or work table. The heating elements remain
fixed within the enclosure without needing to disconnect power cables or move the heating elements, which reduces
manipulation and the weight of the evaporation chamber and saves time.

ELEMENTS: Made of Incoloy 800/825 with a high coefficient of thermal expansion. The elements are self-cleaning due
to their expansion and contraction.

AFEC (Anti-foaming Energy Conservation): The patented AFEC system ensures proper water level control under
varying water conditions (Hard, soft, RO or DI) by initiating a drain only when foam is detected eliminating the need for
surface skimming.

WATER LEVEL DETECTION SYSTEM: The patent-pending water level detection system with redundancy uses three
sensors consisting of a high-resolution capacitive sensor and two resistive sensors. The capacitive sensor and dual
resistive sensors cross-verify their respective functions, which results in automatic self-zeroing throughout the lifetime of
the humidifier. The two types of water level sensors provide redundancy; if one fails, the other sensor takes over and
ensures safe and uninterrupted operation while providing a local/remote warning. A fill valve at the top of the sensors’ tube
flushes and cleans the sensors at every drain cycle to ensure they are free of deposits.

THERMAL PROTECTION: Two-level temperature protection. The first temperature sensor is located inside the
evaporation chamber and the second temperature sensor is located on the outside of the evaporation chamber cover.
Either sensor stops the humidifier if a high-temperature condition is detected.

ELEMENT MODULATION CONTROL: Modulation is done using SSRs (Solid state relays) with zero crossing detection
and firing. The SSRs do not generate spikes, noise or harmonic distortion on the electrical system.

CAPACITY REDUCTION: Using the controller, the capacity of a modulating system can be programmed from 0 to
100% by using the MaxOutput setting.

WATER COOLER: Internal drain water to ensure drain water tempering to 140˚F (60˚C) or less.

ETL-C-US listed.
SKE4-N Series Humidifier
SKE4-N Monitoring and Control Panel

Back/Menu Button Enter Button


Up Arrow Button Plus Button

Down Arrow Button Minus Button

Power Button Drain Button

Status Display

Feature Description
☼ Indicates that the humidifier is turned on. The LED will begin blinking as the
(Blue) system is initializing.

Status Display
☼ Indicates that the alarm is issuing a warning and that the system must be verified.
(Red)
O Indicates that the humidifier is turned off.
(Off)
The power button is used to turn the humidifier on or off. Must be pressed and
held for 3 seconds to perform the related action, in order to prevent accidental
Power Button
activation. Even when the humidifier is powered off, the controller remains
operational.
The drain button is used to manually activate the drain cycle. Must be pressed
and held for 3 seconds to perform the related action, in order to prevent accidental
activation. Even when the humidifier is powered off, a manual drain cycle may be
Drain Button
initiated.
Once the manual drain cycle is completed, the system will automatically be
powered off. To turn the humidifier back on, press and hold the power button.
The up arrow button is used to scroll to the next menu item or parameter.
Up and Down Arrow
Buttons
The down arrow button is used to scroll to the previous menu item or parameter.

The plus button is used to increase the value of the displayed parameter.
Plus and Minus
Buttons
The minus button is used to decrease the value of the displayed parameter.
The back/menu button is used to go to previous menu or to access the Main
Back/Menu Button
Menu page from the Idle Screen.
The enter button is used to advance to the next sub-menu, to access selected
Enter Button
option or to confirm set parameter value.

www.neptronic.com 12/23
Dimensions:

Dimensions and Weight

Dimensions of the Cabinet (in) Steam Outlet(s) Location (in)

Tag Weight (lb) No. of Steam


A B C I J Steam Outlet
Full of Outlet Dia.
Empty
Water
Edificio A SKE4-N10M 813 565 384 49 69 191 305 1 35

Edificio A[2] SKE4-N10M 813 565 384 49 69 191 305 1 35

Edificio A[3] SKE4-N10M 813 565 384 49 69 191 305 1 35

Edificio A[4] SKE4-N10M 813 565 384 49 69 191 305 1 35

Edificio A[5] SKE4-N10M 813 565 384 49 69 191 305 1 35

Edificio A[6] SKE4-N10M 813 565 384 49 69 191 305 1 35

Edificio A SKE4-N10M 813 565 384 49 69 191 305 1 35

Edificio A
SKE4-N10M 813 565 384 49 69 191 305 1 35
[2]

Edificio A SKE4-N14M 813 565 384 49 69 191 305 1 35


Dimensions of the Cabinet (in) Steam Outlet(s) Location (in)

Tag Model Weight (lb) No. of Steam


A B C I J Steam Outlet
Full of Outlet Dia.
Empty
Water
Edificio A[2] SKE4-N14M 813 565 384 49 69 191 305 1 35

Edificio A[3] SKE4-N14M 813 565 384 49 69 191 305 1 35


Positioning and Installation
General Recommendations

The humidifier must be installed in an easily accessible location to


allow proper access for inspection and servicing of the humidifier.
The unit must never be installed in a location where unusual
malfunction of the unit can cause damage to the building structure
or to costly equipment. Typically, the total steam line length
between the humidifier and the steam distributor depends on the
steam line material type:
 For flexible steam hoses: the total steam line length must not
exceed 16 feet (5 meters). For longer distances, use insulated
hard piping.
 For insulated hard piping: the total steam line length is
determined by the humidifier capacity: one equivalent foot for
 each lb/h capacity of the humidifier (0.67m equivalent for each
kg/h), with a maximum of 50 feet (15m). For longer steam line
runs, consult factory.

Positioning

The humidifier must be mounted at a minimum of 24” (0.6m)


above floor level. Leave a clearance of at least 10” (0.25m) under
the humidifier for the installation of water supply, drain piping and
electrical connections. A clearance of at least 48” (1.2m) from the
front of the unit and 12” (0.3m) from the right and left hand side is
necessary for ease of access and service. Leave a clearance of at
least 20” (0.5m) on top of the humidifier. The humidifier must be
installed in a well-ventilated area and the ambient temperature
must not exceed 86˚F (30˚C).

Wall Mounting

The mounting of the humidifier on the wall is to be done by using


the supplied brackets and screws.
After securing the brackets to the support or wall using 4 screws
per bracket, the top inserts located on the back of the humidifier
cabinet must be placed into the open slots of the top bracket.
By opening the front door of the humidifier, secure the humidifier
to the bottom bracket by drilling screws in the center of the
bracket.

Dimensions (in)
Tag
A B C D E
Edificio A SKE4-N10M 813 565 540 514 22
Edificio
SKE4-N10M 813 565 540 514 22
A[2]
Edificio
SKE4-N10M 813 565 540 514 22
A[3]
Edificio
SKE4-N10M 813 565 540 514 22
A[4]
Edificio
SKE4-N10M 813 565 540 514 22
A[5]
Edificio
SKE4-N10M 813 565 540 514 22
A[6]
Edificio A SKE4-N10M 813 565 540 514 22
Edificio A
SKE4-N10M 813 565 540 514 22
[2]
Edificio A SKE4-N14M 813 565 540 514 22
Edificio
SKE4-N14M 813 565 540 514 22
A[2]
Edificio
SKE4-N14M 813 565 540 514 22
A[3]
Steam Dispersion System Selection and Positioning

S.A.M.E2 (Steam Absorption Manifold)


The S.A.M.E2 is to be installed
where absorption distances are
short, less than 5 feet (1500mm)
and/or low duct temperatures are
air in effect. The S.A.M.E2 are used
in applications with restricted duct
dimensions.

The S.A.M.E2 is a stainless steel


900 manifold with brass nozzle inserts.
The nozzles collect the dry steam
from the center of the tube
preventing condensate from
escaping.

Tag Model
Edificio A MF SAM AE2-M Manifold Length: 400 mm H
Edificio A[2] MF SAM AE2-M Manifold Length: 400 mm H
Edificio A[3] MF SAM AE2-M Manifold Length: 400 mm H
Edificio A[4] MF SAM AE2-M Manifold Length: 400 mm H
Edificio A[5] MF SAM AE2-M Manifold Length: 400 mm H
Edificio A[6] MF SAM AE2-M Manifold Length: 400 mm H
Edificio A MF SAM AE2-M Manifold Length: 500 mm H
Edificio A [2] MF SAM AE2-M Manifold Length: 500 mm H
Edificio A MF SAM AE2-M Manifold Length: 600 mm H
Edificio A[2] MF SAM AE2-M Manifold Length: 600 mm H
Edificio A[3] MF SAM AE2-M Manifold Length: 600 mm H
Plumbing Connections
Shutoff Valve, Water Strainer and Water Hammer Arrestor:
In order to facilitate servicing, install a shutoff valve in the water supply line close to the humidifier.
It is also recommended to install a standard water strainer in the water supply line and to install a water hammer
arrestor, in order to absorb hydraulic shock and minimize water hammer when the fill valve closes.

Drain Connection:
Use standard copper hydraulic pipes placed underneath the humidifier to provide the connection between the
unit and the two drain connections, located on the underside of the unit. Ensure that the drain pipe dimension is
sufficient, especially if more than one unit is evacuating into the same drain line.
 Evaporation chamber water drain temperature: 140F (60C)

Water Supply Inlet:


Connect top of 1/2” (DN15)
NPT fitting to male
threaded part of pipe
Main Drain: Pan Drain:
Connect 3/4” (DN20) Connect 1/2” (DN15)
compression fitting to elbow fitting to
hydraulic pipe hydraulic pipe

Plumbing connections

Water Supply:
The water inlet specifications are:
 Inlet water pressure: 10 to 70 psig (0.7 to 4.8
bars)
 Maximum temperature: 86˚F (30˚C) maximum
 ½” (DN15) standard copper water line
connection

(Bottom view)

Dimensions (in)
Tag Model
A B C D E F
Edificio A SKE4-N10M 304 178 38 51 73 83

Edificio A[2] SKE4-N10M 304 178 38 51 73 83

Edificio A[3] SKE4-N10M 304 178 38 51 73 83

Edificio A[4] SKE4-N10M 304 178 38 51 73 83

Edificio A[5] SKE4-N10M 304 178 38 51 73 83


Dimensions (in)
Tag Model
A B C D E F
Edificio A[6] SKE4-N10M 304 178 38 51 73 83

Edificio A SKE4-N10M 304 178 38 51 73 83

Edificio A [2] SKE4-N10M 304 178 38 51 73 83

Edificio A SKE4-N14M 304 178 38 51 73 83

Edificio A[2] SKE4-N14M 304 178 38 51 73 83

Edificio A[3] SKE4-N14M 304 178 38 51 73 83


Wiring Diagram (Edificio A,Edificio A[2],Edificio A[3],Edificio
A[4],Edificio A[5],Edificio A[6],Edificio A,Edificio A [2],Edificio
A,Edificio A[2],Edificio A[3])
Purple SP5804
Water Level Sensor

Brown SP5799

JP1 Foaming sensor Temp


Black SP5841 Ground
Fuses
(when required)

Drain Cooler
Water Level

Drain Pump
Tank Water
Valve

Valve
Valve
Temperature Heating
sensor Elements

Drain
Tank

Purple SP5804
Orange SP5801
Blue SP5802
Green
White
Black

Blue
Red

White SP5807 Only for Current Sensor option


Yellow SP5797
Purple SP5804 Current sensors

Red SP5806

White SP5807
Brown SP5799
1 2 3 4 5 1 2 3
1 2 3 1 2 3 4 1 2 1 2 3 1 2 3 4
JP6 JP7 JP8 JP9 JP10 JP11 JP12
Klixon
WATER WATER TANK WATER DRAIN RELAY STEAM
LEVEL TEMP+FOAM DETECT VALVES PUMP SPARE1 VALVE

1 Red SP5806
JP13
Blue SP5823 Purple SP5804
2
THERMAL
SWITCH 3 Orange SP5801 +

SSR
Thermistor

-
JP14 1 Purple SP5804
DOUBLE 2
LCD1 ISOLATION

ETHERNET
BOARD Purple SP5804
JP15 1
FFC Cable, Red SP5806

Main Contactor
MAIN
Connects to JP3 CONTR 2
Display Board

JP16 1
STAGE 2
CONTR1

JP17 1

ETHERNET STAGE 2
CONTR2
PCB
JP18 1 Ground

STAGE
CONTR3 2

1
JP19 Grey SP5824
2
SD1
3
SDU+APS XXX / 24VAC
Micro SD 4 Red SP5819
card port

16 AWG
JP4 Transformer
Purple SP5822
CN2 JP20 1
ETHERNET Blue SP5823
POWER 2 Fuse
BOARD Ground
USB drive (when required)
port

1
JP21
TXD
2 Disconnect Switch
(by others)
JP1 RXD
3
SSR +
RS 485 A+ TEMP.
TB1

(TRLH) 4
EOL

B-

JP2
RS 485 A+ NETWORK NETWORK 1
TB2

BOARD JP22
(BACnet) PCB L1 L2 L3
EOL

B- 2
TXD
TEMP.
RXD SENSOR 3
24 Vac
Airflow Switch
TB3

JP5
High limit Humidistat
1
Interlock JP23
On/Off demand contact 2

Common CURRENT 3 DATE: Nov. 23, 2017


SKE4-3PH-1ST
TB4

24 Vac
SENSOR
4 TITLE:
Control Demand
DRAWN BY: D.R.
Room Humidity
SHEET: 1 OF 1 DESCRIPTION:
Duct Humidity 1
JP24
Steam Output
DIG. INP
2 Wiring diagram SKE4 - 3 Phase, 1 Stage
SPARE
3 REV 3.0 (Mod)
COM
Alarm
TB5

contacts NO
NC Purple SP5822 NOTES: Models SKE4-N04 to N30 (3ph) / SKE4-E05 to E40 (3ph)
1
Service COM JP25
Blue SP5823
TB6

2
contacts NO
NC Neptronic
16 AWG
TB7
400 boul. Lebeau, St-Laurent, H4N 1R6
WATER
LEAK
DETECT
Québec, Canada
1 2 Tel: (514) 333-1433 Fax: (514) 333-3163
Control Terminals

Electrical Control
Connections
RS 485 A+ 1

TB1
(HRL24) B- 2
Network Contacts RS 485
(BACnet MS/TP A+ 1

TB2
or Modbus RTU) B- 2
24 Vac 1
Airflow switch 2

TB3
Safety Contacts High limit humidistat 3
Interlock 4
On/Off demand contact 5
1

TB4
Common
Power Output 24 Vac 2
Control Demand 3
Analog Inputs Room Humidity 4
Duct Humidity 5
Analog Output Steam Output 6
Common 1

TB5
Alarm Contacts Normally Open 2
Normally Closed 3
Common 1

TB6
Service Contacts Normally Open 2
Normally Closed 3

Safety Contacts
The Airflow switch contact must be wired between terminals TB3 1&2. If this contact opens, operation of the
SKE4 unit will stop. The unit will display the airflow switch as open, but will not generate an alarm. If an airflow
switch is not used, install a jumper between terminals TB3 1&2.

The High limit humidistat contact must be wired between terminals TB3 1&3. If this contact opens, operation of
the SKE4 unit will stop and an alarm message will be displayed. If a high limit humidistat is not used, install a
jumper between terminals TB3 1&3.

The Interlock must be wired between terminals TB3 1&4. If this contact opens, operation of the SKE4 unit will
stop. The unit will display the Interlock as open, but will not generate an alarm. If Interlock is not used, install a
jumper between terminals TB3 1&4.

Dry Contacts
Two series of volt free contacts are provided: Alarm Contacts and Service Contacts.
Each series has one Normally Closed contact and one Normally Open contact.
These contacts are used to switch a low voltage, ideally 24V, with a switching current of no more than 3 Amps.
It is recommended to use the Normally Closed contact, as this contact will open in the event of a humidifier
fault.
Control Wiring Diagram (Edificio A, Edificio A[2], Edificio A[3],
Edificio A[4], Edificio A[5], Edificio A[6], Edificio A, Edificio A [2],
Edificio A, Edificio A[2], Edificio A[3], Edificio X, Edificio X[1], Edificio
X[2], Edificio X[3], Edificio X[4], Edificio X[5], Edificio X[6], Edificio
X[7], Edificio X[8], Edificio X[9], Edificio X[10], Edificio X[11])
Controls & Accessories

Item Model Description

Duct mounted humidity sensor with On/Off high limit humidistat,


0-10VDC output, with an accuracy of +/-3%.
SHS80
Adjustable range: 20-90% RH.
Built-in humidity and temperature sensor.

APS Air pressure switch, SPDT, 0.05"WC (1.3mmWC) set point.

You might also like