You are on page 1of 45

Draft for Public Comment Form 36

Version 6.1

DPC: 04/30124515 DC

Head Office
389 Chiswick High Road Date: 9 November 2004
London W4 4AL
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

Origin: European
Telephone: +44(0)20 8996 9000
Fax: +44(0)20 8996 7001

Latest date for receipt of comments: 28 February 2005 Project no.: 2004/02610
Responsible committee: FSH/22 Fire Resistance Tests

Interested committees:

Title: Draft EN 1366-10 Fire resistance tests for service installations


Part 10: Smoke control dampers

Supersession information: If this document is published as a standard, the UK implementation of it will supersede
NONE and partially supersede NONE . If you are aware of a current national standard which may be affected,
please notify the secretary (contact details below).

WARNING: THIS IS A DRAFT AND MUST NOT BE REGARDED OR USED AS A BRITISH STANDARD.
THIS DRAFT IS NOT CURRENT BEYOND 28 February 2005.
This draft is issued to allow comments from interested parties; all comments will be given consideration prior to
publication. No acknowledgement will normally be sent. See overleaf for information on commenting.
No copying is allowed, in any form, without prior written permission from BSI except as permitted under the
Copyright, Designs and Patent Act 1988 or for circulation within a nominating organization for briefing purposes.
Electronic circulation is limited to dissemination by e-mail within such an organization by committee members.
Further copies of this draft may be purchased from BSI Customer Services, Tel: +44(0) 20 8996 9001 or email
orders@bsi-global.com. British, International and foreign standards are also available from BSI Customer Services.
British Standards on CD or Online are available from British Standards Publishing Sales Limited.
Tel: 01344 404409 or email bsonline@techindex.co.uk.
Information on the co-operating organizations represented on the committees referenced above may be obtained
from the responsible committee secretary.
Cross-references
The British Standards which implement International or European publications referred to in this draft may be found
via the British Standards Online Service on the BSI web site http://www.bsi-global.com.

Responsible Committee Secretary: Ms Sheila O'Reilly Direct tel: 020 8996 7252
(BSI)
E-mail: sheila.o'reilly@bsi-global.com

a
Introduction
This draft standard is based on European discussions in which the UK took an active part. Your comments on this
draft are welcome and will assist in the preparation of the consequent British Standard. If no comments are received
to the contrary, then the UK will approve this draft and implement it as a British Standard. Comment is particularly
welcome on national, legislative or similar deviations that may be necessary.
Even if this draft standard is not approved by the UK, if it receives the necessary support in Europe, the UK will be
obliged to publish the official English Language text unchanged as a British Standard and to withdraw any conflicting
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

standard.

UK Vote
Please indicate whether you consider the UK should submit a negative (with reasons) or positive vote on this draft.

Submission
The guidance given below is intended to ensure that all comments receive efficient and appropriate attention by the
responsible BSI committee. Annotated drafts are not acceptable and will be rejected.

All comments must be submitted, preferably electronically, to the Responsible Committee Secretary at the address
given on the front cover. Comments should be compatible with Version 6.0 or Version 97 of Microsoft® Word for
Windows™, if possible; otherwise comments in ASCII text format are acceptable. Any comments not submitted
electronically should still adhere to these format requirements.

All comments submitted should be presented as given in the example below. Further information on submitting
comments and how to obtain a blank electronic version of a comment form are available from the BSI web site at:
http://www.bsi-global.com/British_Standards/DPC/index.xalter.

Date Document

National Clause/ Paragraph/ Type of comment COMMENTS Proposed change OBSERVATIONS OF


Committee subclause Figure/ Table THE SECRETARIAT
(General/
technical/editorial)
3.1 1st definition Editorial Definition is ambiguous and Amend to read ‘... so
needs clarifying. that the mains
connector to which no
connection ...’

6.4 §2 Technical The use of the UV Delete reference to UV


photometer as an photometer.
alternative cannot be
supported as serious
problems have been
encountered in its use in the
UK.
Microsoft and MS-DOS are registered trademarks, and Windows is a trademark of Microsoft Corporation.

b
EUROPEAN STANDARD DRAFT
NORME EUROPÉENNE prEN 1366-10
EUROPÄISCHE NORM
October 2004
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

ICS

English version

Fire resistance tests for service installations - Part 10: Smoke


control dampers

Essais de résistance au feu des installations de service -


Partie 10 : Volets de désenfumage

This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 127.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the Management Centre has the same
status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,
Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia,
Slovenia, Spain, Sweden, Switzerland and United Kingdom.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.

EUROPEAN COMMITTEE FOR STANDARDIZATION


COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: rue de Stassart, 36 B-1050 Brussels

© 2004 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 1366-10:2004: E
worldwide for CEN national Members.
prEN 1366-10:2004 (E)

Contents Page
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

Foreword ............................................................................................................................................................. 3
1 Scope...................................................................................................................................................... 5
2 Normative references ........................................................................................................................... 5
3 Terms and definitions........................................................................................................................... 5
4 Test Equipment ..................................................................................................................................... 9
5 Test specimen ..................................................................................................................................... 13
6 Test Methods ....................................................................................................................................... 13
7 Test procedure .................................................................................................................................... 19
8 Test report ........................................................................................................................................... 21
9 Direct field of application of test results .......................................................................................... 22
Annex A Cycling test ....................................................................................................................................... 39

2
prEN 1366-10:2004 (E)

Foreword
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

This document (prEN 1366-10:2004) has been prepared by Technical Committee CEN/TC 127, "Fire
safety in buildings", the secretariat of which is held by BSI.

This document is currently submitted to the CEN Enquiry.

EN 1366 ‘Fire resistance tests for service installations’ consists of the following

Part 1: Ducts

Part 2: Fire dampers

Part 3: Penetration seals (in course of preparation)

Part 4: Linear joint seals (in course of preparation)

Part 5: Service ducts and shafts (in course of preparation)

Part 6: Raised floors (in course of preparation)

Part 7: Closures for conveyors and trackbound transportation systems (in course of preparation)

Part 8: Smoke extraction ducts (in course of preparation)

Part 9: Smoke compartment smoke extraction ducts (in course of preparation)

Part 10: Smoke control dampers

Part 11: Fire protective systems for essential services (in course of preparation)

3
prEN 1366-10:2004 (E)

Introduction
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

The purpose of this standard is to define test methods to evaluate the abilities of smoke control
dampers to

1) be applicable to single compartment and/or multi compartment fire resisting applications;

2) be applicable to automatic systems or systems with manual intervention;

3) change state from closed to open at elevated temperatures;

4) once opened maintain a defined cross sectional area at elevated temperature;

5) maintain a satisfactory leakage performance when subjected to positive pressure at


elevated temperatures.

The units will be mounted for the tests in a manner representative of practice.

Temperature and integrity measurements will be carried out in various parts of the test construction
during the test. Impermeability measurements required will be measured by direct flow measurement
at the prescribed pressure differentials. Ambient leakage of the units will also be recorded.

Performance of these tests will allow products to conform to and be classified to prEN 12101-8. The
required temperatures, pressure differentials etc. are stated in prEN 12101-8.

Completing the tests within this standard does not ensure full compliance with prEN 12101-8, as other,
additional, requirements are defined in that standard.

Caution

The attention of all persons concerned with managing and carrying out this furnace testing is drawn to
the fact that fire testing may be hazardous and that there is a possibility that toxic and/or harmful
smoke and gases may be evolved during the test. Mechanical and operational hazards may also arise
during the construction of the test elements or structures, their testing and disposal of test residues.

An assessment of all potential hazards and risks to health shall be made and safety precautions shall
be identified and provided. Written safety instructions shall be issued. Appropriate training shall be
given to relevant personnel. Laboratory personnel shall ensure that they follow written safety
instructions at all times.

4
prEN 1366-10:2004 (E)

1 Scope
This Part of this European Standard specifies test methods for smoke control dampers. These tests
are required to confirm that the dampers meet the furnace testing requirements of prEN 12101-8. It
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

should be noted that the damper to be tested might require testing to EN 1366-2 and that this should
be considered before carrying out these tests.

To this end this standard must be read in conjunction with prEN 12101-8, EN 1366-2 and EN 1363,
the latter giving the details for fire resistance testing.

For installation details the requirements for smoke extraction ducts must be considered and these are
defined in EN 1366-8 and EN 1366-9

2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.

EN 1363-1, Fire resistance tests — Part 1: General Requirements

EN 1366-2, Fire resistance tests for service installations — Part 2: Fire dampers

EN 1366-8, Fire resistance tests for service installations — Part 8: Fire resistant Smoke extraction
ducts

EN 1366-9, Fire resistance tests for service installations — Part 9: Single compartment smoke
extraction ducts

EN 1751, The aerodynamic testing of dampers and valves

prEN ISO 13943, Fire safety vocabulary

EN ISO 5167-1, Measurement of fluid flow by means of orifice plates, nozzles and venturi tubes
inserted in circular cross section conduits running full

ISO 5221, Air distribution and air diffusion — Rules to methods of measuring airflow rate in an air
handling duct

prEN 12101-4, Smoke and heat control systems — Part 4: Fire and smoke installations — kits

prEN 12101-7, Smoke and heat control systems — Part 7: Smoke ducts

prEN 12101-8, Smoke and heat control systems — Part 8: Smoke dampers

prEN13501-4, Fire Classification of Construction products and building elements —


Part 4: Classification using data from fire resistance tests on components of smoke control systems

3 Terms and definitions

Where not covered by EN ISO 13943  Fire Safety Vocabulary, the following definitions apply:

5
prEN 1366-10:2004 (E)

3.1
air inlet
device connected to outside air to allow the inlet of air from outside the construction work

3.2
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

attended control room


a room with people, who have the duty to control the smoke exhaust system, permanently (24 hours,
seven days per week) monitor the incoming signals from the smoke control system and put the smoke
control system into operation in case of smoke alarm. This ensures that the smoke control system is
running and items such as dampers are in position within the system response time

3.3
back-up power supply
a power supply to operate the system when the normal power supply has failed

3.4
commissioning
the act of ensuring that all components and the system are installed and operating in accordance with
this standard

3.5
elevated temperature
temperatures in excess of normal ambient air, below those necessary for fire resistance testing, to
which smoke and heat exhaust ducts for single compartments are tested

3.6
fire compartment
an enclosed space, comprising one or more separate spaces, bounded by elements of construction
having a specified fire resistance and intended to prevent the spread of fire (in either direction) for a
given period of time

NOTE Fire compartment often has regulatory connotations. The term should not be confused with "room of
origin" or "fire cell".

3.7
interface control unit
a device with control the operation of the actuator located at the damper or within the same fire zone
as the damper

3.8
modulating actuators
a damper control mechanism which can control the damper to be in a position or number of positions
between fully open and fully closed

3.9
muti compartment fire resisting smoke control damets
smoke control dampers for use in multi compartment areas, which may be associated with smoke
control duct tested to prEN 1366-8 and/or may be installed in a fire compartment structure

3.10
multi compartment fire resisting smoke control system ducts
fire resisting ducts for use in multi compartment application and that have been tested and met the
requirements of prEN 1366-8

3.11
natural smoke and heat control system
a smoke and heat ventilation system which uses natural ventilation. Natural ventilation is caused by
bouyancy forces due to differences in density of the gases because of temperature differences

6
prEN 1366-10:2004 (E)

3.12
penetration seal
the product used between the smoke control system duct/damper and the fire compartment structure
to maintain the fire resistance, when tested and having met the requirements of EN 1366-8, at the
position where a smoke Control System Duct passes through the element, or a damper is mounted in
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

the element

3.13
powered smoke and heat exhaust system
a smoke and heat ventilation system which utilises a number of hot gas fans that are suitable for
handling hot gases for a limited period of time which causes the positive displacement of gases

3.14
pressure differential systems
a system of fans, ducts, vents, and other features provided for the purposes of creating a lower
pressure in the fire zone than in the protected space. (see prEN 12101-6)

3.15
remote signalling
a device located away from the damper which will indicate the damper position, open or closed

3.16
safety position
smoke control dampers do not have a designated safety postion, unlike fire dampers which are closed
in their safety position. Specific projects may require certain dampers to move to an open or closed
position, depending upon the fire location within the building

3.17
single compartment smoke control dampers
smoke control dampers for use in single compartment areas, which may be associated with smoke
control duct tested to prEN 1366-9, and/or may be installed in an external wall, floor or roof

3.18
single compartment smoke control system ducts
ducts for use within single fire compartment application and that have been tested and met the
requirements of prEN 1366-9

3.19
smoke and heat exhaust ventilation system (SHEVS)
a smoke and heat exhaust ventilation system consists of components jointly selected to exhaust
smoke and heat. The components form a system which complies with the requirements of
prEN 12101-4 in order to establish a buoyant layer of warm gases above cooler cleaner air

3.20
smoke and heat exhaust ventilator (SHEV)
device specially designed to move smoke and hot gases out of a construction work under conditions
of fire

3.21
smoke barrier
a barrier to restrict the spread of smoke and hot gases from a fire, forming part of the boundary of a
smoke reservoir or used as a channelling screen, or used as a void edge boundary

3.22
smoke control damper for systems with automatic activation
a smoke control damper that is applicable to the systems defined in 3.26

7
prEN 1366-10:2004 (E)

3.23
smoke control damper for systems with manual intervention
a smoke control damper that is applicable to the systems defined in 3.27 and 3.28

3.24
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

smoke control system damper


a device automatically or manually activated, which maybe open or closed in its operational position,
to control the flow of smoke and hot gases into, from or within a duct

3.25
smoke control system duct
a duct used in a system to control the movement and /or containment of smoke and heat

3.26
smoke control system with automatic activation
a smoke control system (smoke and heat exhaust ventilation type or pressure differential type), that
operates automatically on receipt of a smoke or fire alarm without any manual action/intervention. A
system with an attended control room can also be accepted as an automatic system. Once initiated
the system will not allow the damper position to be changed

3.27
smoke control system with automatic activation and with manual override
a smoke control system (smoke and heat exhaust ventilation type or pressure differential type), that
can be put into operation as 3.26 on receipt of a smoke or fire alarm, but once initiated the system will
allow the damper position to be changed by external input/firemans' override

3.28
smoke control system with manual Initiation
a smoke control system (smoke and heat exhaust ventilation type or pressurization type), that must
be put into operation, on detection smoke or fire, by human intervention. (e.g. by pressing a button,
or pulling a handle) leading to a sequence of automatic actions in the operation of the smoke control
system. Once initiated the system may allow the damper position to be changed by external
input/firemans' override

3.29
smoke layer
layer of smoke that stabilises underneath the roof due to the affect of temperature gradient

3.30
smoke logging
a condition within a building when the hot gases from a fire descend within it to a level whereby the
safe escape of the occupants is hampered and the ingress of firefighters is prevented

3.31
smoke reservoir
region within a building limited or bordered by smoke barriers or structural elements and which will in
the event of a fire retain a thermally buoyant smoke layer

3.32
smoke zone (zones)
areas into which a construction work is divided for the extraction of smoke and hot gases. Each zone
is served by a SHEV, (or sub system of a SHEV) which is initiated by a signal from a single or group
of initiation devices associated with the zone

3.33
structural supports
the means of retaining the smoke control system duct to the building structure

8
prEN 1366-10:2004 (E)

3.34
system response time
the time from the initiation of the smoke control system to it being fully operational [This definition
needs to be agreed with 12101-6 group since SC1 decided they have responsibility for this definition]
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

3.35
thermal operating device
temperature sensitive device which responds to initiate a subsequent action

3.36
triggering device
a device such as a fire detector system, smoke detector or pushbutton which sends an activating
signal to the initiation device(s)

4 Test Equipment

4.1 General

In addition to the test equipment specified in prEN 1363-1, and if applicable, prEN 1363-2, the
following is required: Examples of test configurations are shown in figures 1 and 2.

4.2 Connecting duct for multi compartment fire resisting smoke control damper
maintenance of opening test and 1366-2 test

The connecting duct shall be of all welded construction fabricated from (1.5 ± 0.1) mm thick steel with
a width and height appropriate to the size of fire damper being tested. The duct shall have a length of
two times the diagonal dimension of the damper up to a maximum of 2m. The connecting duct shall
be provided with a gas tight observation window.

4.3 Volume flow measuring station for multi compartment fire resisting smoke
control damper maintenance of opening test and 1366-2 test

This shall consist of a venturi, orifice plate, or other suitable device and (where necessary) an air flow
straightener, installed in straight lengths of pipe, all sized to EN ISO 5167-1 and ISO 5221. It shall be
installed between the connecting duct and the exhaust fan to determine the volume flow rate of gases
passing through the fire damper under test. The measuring device shall be capable of measuring to
an accuracy of ± 5 %. Regardless of whether vertical or horizontal fire dampers are being tested, the
volume flow measuring station shall always be used in a horizontal direction.

4.4 Cycling Equipment

Full information on the equipment needed to perform the cycling tests is shown in annex B. In addition
the following must be considered.

Equipment will be required to control a supply to allow the damper actuator to be cycled. This
equipment will be able to provide the nominal operating power less 10%, plus 15%, and be variable
between these values to confirm that the damper will operate at the extremes. If the unit to be tested
requires a control signal of any type this needs to be provide in addition and will be able to give the
device a signal at each extreme and any in between these.

Methods of loading the smoke control damper will be required

NOTE A device that allows the damper to be cycled automatically, together with a method of recording
completed cycles, would be useful, so that a test could be set to run without attendance, noting that each cycle
could potentially take 120 seconds

9
prEN 1366-10:2004 (E)

4.5 Condensing unit

Where materials used in the construction of the test duct or the smoke control damper may generate
quantities of steam during the fire test, a condensing unit having provisions for drainage shall be
installed between the fire damper and the flow measuring device. When using the condensing device,
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

the temperature recorded by the thermocouple positioned downstream of the flow measuring device
described in 4.3 shall not exceed 40 °C.

A suitable condensing device may be considered to be a water tank fed with water at ambient
temperature with [approximately 9 metres] of measuring duct immersed in the tank prior to reaching
the measuring device providing that there is a means for removal of the condensate. Custom devices
designed by individual laboratories that meet the 40°C condition and allow condensate removal are
allowable.

4.6 Gas temperature measuring devices

These shall be positioned adjacent to the flow measuring device. A suitable device is a 1.5 mm
diameter sheathed thermocouple orientated vertically with its measuring junction located at the centre
line of the measuring duct and at a distance equal to twice the diameter of the measuring duct
downstream from the flow measuring device. A similar thermocouple shall be located at the exit from
the connecting duct plenum (see Ffigure 1).

4.7 Exhaust fan system

This shall be capable of controlling the flow rates and maintaining the specified pressure differential
between the connecting duct and the furnace when the fire damper is closed.

The pressure differential shall be regulated by means of a dilution damper installed just before the fan
inlet. The pressure shall be controlled to within ± 5 % of the specified value. A balancing damper shall
be fitted at the outlet of the fan to adjust the pressure range of the systems to suit the fire damper
under test. A variable speed fan may be used instead of the dilution damper.

4.8 Perforated plate

The perforated plate controls the flow through the duct so that the required differential pressure, see
Table 1, can be achieved. Depending on the end-use conditions, a pressure level from Table 1 shall
be selected: These levels correspond to typical values used in smoke extraction design.

The plate shall be positioned 250 ± 50 mm from where the duct passes through the furnace wall
(see Figures 1 and 2).

These plates shall be made from heat resisting steel, 19 % min. Cr content and 11 % min. Ni content.
The number of holes and dimensions are given in tables 2 and 3. The thickness of the plates shall be
2,5 mm.

NOTE 1 Table 2 gives details of perforated plates for standard rectangular ducts of size 1000 mm × 250 mm.
For smaller sizes, the number of holes will be reduced proportional to the smaller cross-section.

NOTE 2 Table 3 gives details of perforated plates for standard circular ducts of diameter 560 mm. For smaller
sizes, the number of holes will be reduced proportional to the cross-section (a change to larger sizes is not
accepted; see 6.1.2 and Table 5).

Further details of the plate are shown in Figures n1,n2 and n3.

10
prEN 1366-10:2004 (E)

Table 1 — Differential pressures between inside and outside the duct for smoke extraction
ductwork
*)
Pressure Level Operating differential pressure at Differential pressure for the
ambient temperature fire test and pre-test calibration
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

Pa Pa

1 -500 -150
2 -1000 -300
3 -1500 -500
*)
See clause 5.

Table 2 — Details of perforated plates for testing rectangular ducts (see Figure 3)
*)
Pressure level
Specification for perforations
1 2 3

Total number of holes 550 407 324


Number of holes - horizontally 50 37 36
Number of holes - vertically 11 11 9
Diameter of hole (mm) 10 10 10
Horizontal distance from rim e (mm) 15 15 20
Vertical distance from rim c (mm) 15 15 20
Mounting hole separation a (mm) 19,8 26,9 27,4
Mounting hole separation b (mm) 21,8 22 26,3
*)
See clause 5.

Table 3 — Details of perforated plate for testing circular ducts (see Figure 4)
*)
Pressure level
Specification for perforations
1 2 3

Total number of holes 541 403 319


Diameter of hole (mm) 10 10 10
Horizontal distance from rim e (mm) 30 35 35
Mounting hole separation a (mm) 20,8 22,2 27,5
Mounting hole separation b (mm) 20,8 22,2 27,5
*)
See clause 5.

4.9 Inlet nozzles (fire test)

Each nozzle shall have an internal dimension of 160 mm (see Figure 10, suitable for the standard size
of duct specified in 6.1) in accordance with ISO 5167/ISO 5221 and shall be suitably mounted to the
end of the duct with its piezometric ring connected to appropriate differential pressure measuring
equipment. The measuring device shall be capable of measuring to an accuracy of ± 5 %.

11
prEN 1366-10:2004 (E)

4.10 Ambient leakage measuring device

These shall be in accordance with ISO 5167/ISO 5221 and suitably mounted to the end of the duct,
connected to appropriate differential pressure measuring equipment. The measuring device shall be
capable of measuring to an accuracy of ± 5 %. Ambient leakage may be used as described in
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

EN 1751, were this is more practical.

4.11 Pressure sensors for differential pressure control

A tube sensor as specified in EN 1363-1 shall be located at the end of the duct, inside the duct, at the
level of its centre line. A second sensor (e.g. an open end of a measuring tube) shall be located on
the same level outside the duct differential pressure fine control device.

A flow control damper shall be provided for a fine control for maintaining the required differential
pressure. Alternatively, another suitable device such as a variable speed fan may be used. Any flow
control damper shall be attached to the extract fan connecting duct (see 4.8).

4.12 Welded connecting tube

A welded connecting tube is a tube designed to provide a suitable gas tight connection between the
inlet nozzles and the oxygen measuring probes.

4.13 Extract fan connecting duct

An extract fan connecting duct is a duct designed to connect between the test specimen and the
extraction fan. An inlet opening may be provided if a flow control damper is used for fine control of the
differential pressure (see 4.6).

4.14 Extraction fan

The extraction fan provided by the laboratory should be capable of exceeding the test requirements
stated in this standard.

4.15 Thermocouples

1,5 mm sheathed thermocouples shall be provided for measuring the gas temperature adjacent to the
nozzles. An alternative thermocouple may be used, provided it can be shown to have equivalent
response time.

4.16 Oxygen measuring equipment

Equipment for measuring the oxygen content of gases shall be provided. This system shall consist of
paramagnetic cell oxygen analysers together with appropriate equipment for cooling, filtering and
drying the gases. Appropriate connecting tubes and probes shall be provided. The 90 % response
time of the complete system shall be 20 s maximum. The accuracy shall be better than ± 0,1 %.

4.17 Restraint equipment

Restraining equipment shall be applied as for duct B in EN 1366-1. [IS THIS NEEDED?]

4.18 Observation windows

Provision should be made to provide suitable observation windows to allow the test observations to
be made safely.

12
prEN 1366-10:2004 (E)

5 Test specimen

5.1 Cross-section

The size of damper subjected to the elevated temperature tests, should be the largest that is to be
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

manufactured. Cold leakage will be required to be determined on the smallest size to be


maunufactured.

5.2 Design

The test shall be made on a test specimen representative of damper range. Duct installation shall be
as tested.

An attempt shall be made to reproduce the edge conditions and the method of fixing of the damper to
the duct.

6 Test Methods

6.1 General

Smoke Control Dampers shall be tested according to their proposed final application to enable
classification to be made. They may be broadly split into two the two main groups of multi and single
compartment applications. Within these applications there are further tests to which each type may be
subjected and these shall be considered before embarking on a test sequence. The required initiation
regime and number of cycles to be tested should be included within the sequence of testing

6.1.1 Initiation regimes for elevated temperature and fire tests

6.1.1.1 Smoke Control Damper for Systems with Automatic Activation

T = 0 seconds - furnace ignition

a) damper mounted in furnace closed;

b) damper mounted outside open, unless if in its application it will never be open at the
commencement of a smoke situation.

T = 30 seconds

a) Signal damper mounted in furnace to move to open position;

b) Signal damper mounted outside furnace to close or the damper remains in the closed position, if
in its application it will never be open at the commencement of a smoke situation.

T = 90 seconds - Dampers to reach end positions

6.1.1.2 Smoke Control Damper for Systems with Manual Intervention:

T = 0 minutes - furnace ignition

a) damper mounted in furnace closed;

b) damper mounted outside open, unless if in its application it will never be open at the
commencement of a smoke situation.

13
prEN 1366-10:2004 (E)

T = 25 minutes

a) Signal damper mounted in furnace to move to open position;

b) Signal damper mounted outside furnace to close or the damper remains in the closed position, if
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

in its application it will never be open at the commencement of a smoke situation.

T = 26 minutes - Dampers to reach end positions

6.1.2 Cycling test requirements (to form part of the sequences of testing defined below)

Full details of the test and the loading to be used is given in annex B.

6.1.2.1 Smoke control damper to be used in a dedicated Smoke control systems, operated
only in the case of emergency

100 cycles at nominal operating supply less 10 %, followed by

100 cycles at nominal operating supply plus 15 %, followed by

100 cycles at nominal operating supply

The results shall record that the cycles were fully completed and that each travel took not longer than
60 seconds.

6.1.2.2 Smoke control damper to be used also as part of a general HVAC system as well as
a Smoke control systems, or as part of a Smoke control systems that is cycled every day to
check operation

10000 cycles at nominal operating supply

100 cycles at nominal operating supply less 10 %, followed by

100 cycles at nominal operating supply plus 15 %, followed by

The results shall record that the cycles were fully completed and that each travel took not longer than
60 seconds.

6.1.2.3 Smoke control damper to be used also as part of a general HVAC system as well as
a Smoke control systems, that uses a modulating actuator

10,000 cycles at nominal operating supply (0 to 90°)

10,000 cycles at nominal operating supply (45° to 60°)

The results shall record that the full cycles were fully completed and that each travel took not longer
than 60 seconds.

6.1.3 Differential pressure conditions

Depending on the end-use conditions, a pressure selected from Table 4 shall be selected: These
levels correspond to typical values used in smoke extraction design.

14
prEN 1366-10:2004 (E)

Table 4 — Differential pressures between inside and outside the duct for smoke extraction
ductwork
Pressure Level Operating differential pressure at Differential pressure
ambient temperature for the fire test
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

Pa Pa

1 -500 -150
2 -1000 -300
3 -1500 -500

6.2 Single compartment Smoke Control Dampers

6.2.1 Duct test for surface mounted smoke control dampers on a horizontal duct

6.2.1.1 Sequence

Two damper samples shall be selected. These shall be tested for ambient leakage. The two units
shall then be subjected to a cycling test, the number of cycles dependent upon their final proposed
application. The units shall be fitted to the test duct and be tested for ambient leakage prior to
elevated temperature testing. The results shall then be used for classification and the application of
any direct or extended fields of application.

6.2.1.2 Ambient leakage

The two samples will be tested for ambient leakage using the method shown in EN 1751 and the
results recorded.

6.2.1.3 Cycling test

The two samples will be cycle tested (see annex B), the number of cycles being selected from 6.1.2.

6.2.1.4 Elevated temperature test

The test samples (as previously tested 6.2.1.2 and 6.2.1.3 above) shall be mounted in the
arrangement shown in Figure 1.

The units shall be tested for ambient leakage.

The heating conditions and the furnace atmosphere shall conform to those specified in EN 1363-1
until the selected elevated temperature is reached. After the temperature has been reached it shall be
maintained between +10%°C, -0 °C for the rest of the test.

The furnace pressure shall be controlled to (15 ± 3) Pa throughout the test at the mid-height position
of the ducts in the furnace.

The equipment shown in Figure 1 will be supported by the following:

Figure 2 - arrangement of furnace thermocouples

Figure 9 - arrangement for surface T/C’s for the damper mounted external to the furnace

Figure 10 - details of perforated plate pressure control device

Figure 11 - details for mounting the perforated plate pressure control device

15
prEN 1366-10:2004 (E)

Figure 12, 13, 14, 15 - arrangement and mounting details off gas testing probes and nozzles

The initiation regime should be selected from 6.1.1

6.3 Multi compartment fire resisting Smoke Control Dampers


Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

6.3.1 Fire resistance test (for units mounted within a compartment structure)

Units need to be tested in the plane of proposed installation (i.e. vertically and horizontally).

6.3.1.1 Sequence

One damper sample shall be selected. This shall be tested for ambient leakage. The unit shall then
be subjected to a cycling test, the number of cycles dependent upon their final proposed application.
The units shall be fitted to the test duct and be tested for ambient leakage prior to elevated
temperature testing. The results shall then be used for classification and the application of any direct
or extended fields of application.

6.3.1.2 Ambient leakage

The sample will be tested for ambient leakage using the method shown in EN 1751 and the results
recorded.

6.3.1.3 Cycling test

The sample will be cycle tested (see Annex B), the number of cycles being selected from 6.1.2.

6.3.1.4 Fire resistance test

The test sample will be mounted in the test equipment shown in EN 1366-2. It shall be tested for
ambient leakage using the method described in EN 1366-2 and then fire tested. No fusible element is
required or allowed.

The initiation regime should be selected from 6.1.1. Units will be open at the start of the test, unless if
in its application it will never be open at the commencement of a smoke situation.

The heating conditions and the furnace atmosphere shall conform to those specified in EN 1363-1
following the standard curve and tolerances.

The furnace pressure shall be controlled to (15 ± 3) Pa throughout the test at the mid-height position
of the ducts in the furnace.

6.3.2 Maintenance of opening test (for units mounted within a compartment structure)

Units need to be tested in the plane of proposed installation (i.e. vertically and horizontally).

6.3.2.1 Sequence

One damper sample shall be selected. This shall be tested for ambient leakage. The unit shall then
be subjected to a cycling test, the number of cycles dependent upon their final proposed application.
The units shall be fitted to the test duct and be tested for ambient leakage prior to elevated
temperature testing. The results shall then be used for classification and the application of any direct
or extended fields of application.

16
prEN 1366-10:2004 (E)

6.3.2.2 Ambient leakage

The sample will be tested for ambient leakage using the method shown in EN 1751 and the results
recorded.
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

6.3.2.3 Cycling test

The sample will be cycle tested (see annex B), the number of cycles being selected from 6.1.2.

6.3.2.4 Fire resistance test

The test sample will be mounted in the test equipment shown in Figure 3. It shall be tested for
ambient leakage using the method described in EN 1366-2 and then fire tested.

The initiation regime should be selected from 6.1.1. Units will be closed at the start of the test and
then opened at the correct time

The heating conditions and the furnace atmosphere shall conform to those specified in EN 1363-1
following the standard curve and tolerances.

The furnace pressure shall be controlled to (15 ± 3) Pa throughout the test at the mid-height position
of the ducts in the furnace.

The equipment shown in Figure 3 will be supported by the following:

Figure 4 - arrangement for leakage measurement

Figure 5 - arrangement for surface T/C’s

6.3.3 Duct test for surface mounted smoke control dampers on a horizontal duct

6.3.3.1 Sequence

Two damper samples shall be selected. These shall be tested for ambient leakage. The two units
shall then be subjected to a cycling test, the number of cycles dependent upon their final proposed
application. The units shall be fitted to the test duct and be tested for ambient leakage prior to
elevated temperature testing. The results shall then be used for classification and the application of
any direct or extended fields of application.

6.3.3.2 Ambient leakage

The two samples will be tested for ambient leakage using the method shown in EN 1751 and the
results recorded.

6.3.3.3 Cycling test

The two samples will be cycle tested (see annex B), the number of cycles being selected from 6.1.2.

6.3.3.4 Fire resistance test

The test samples (as previously tested 6.3.3.2 and 6.3.3.3 above) shall be mounted in the
arrangement shown in Figure 6.

The units shall be tested for ambient leakage.

17
prEN 1366-10:2004 (E)

The heating conditions and the furnace atmosphere shall conform to those specified in EN 1363-1
following the standard curve and tolerances.

The furnace pressure shall be controlled to (15 ± 3) Pa throughout the test at the mid-height position
of the ducts in the furnace.
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

The equipment shown in Figure 6 will be supported by the following:

Figure 2 - arrangement of furnace thermocouples

Figure 9 - - arrangement for surface T/C’s for the damper mounted external to the furnace

Figure 10 - details of perforated plate pressure control device

Figure 11 - details for mounting the perforated plate pressure control device

Figure 12, 13, 14, 15 - arrangement and mounting details off gas testing probes and nozzles

The initiation regime should be selected from 5.1.1.

6.3.4 Vertical duct test for surface mounted smoke control dampers

6.3.4.1 Sequence

Two damper samples shall be selected. These shall be tested for ambient leakage. The two units
shall then be subjected to a cycling test, the number of cycles dependent upon their final proposed
application. The units shall be fitted to the test duct and be tested for ambient leakage prior to
elevated temperature testing. The results shall then be used for classification and the application of
any direct or extended fields of application.

6.3.4.2 Ambient leakage

The two samples will be tested for ambient leakage using the method shown in EN 1751 and the
results recorded.

6.3.4.3 Cycling test

The two samples will be cycle tested (see annex B), the number of cycles being selected from 6.1.2.

6.3.4.4 Elevated temperature test

The test samples (as previously tested 6.3.4.2 and 6.3.4.3 above) shall be mounted in the
arrangement shown in Figure 7.

The units shall be tested for ambient leakage.

The heating conditions and the furnace atmosphere shall conform to those specified in EN 1363-1
following the standard curve and tolerances.

The furnace pressure shall be controlled to (15 ± 3) Pa throughout the test at the mid-height position
of the ducts in the furnace.

The equipment shown in figure 7 will be supported by the following:

Figure 2 - arrangement of furnace thermocouples

Figure 9 - - arrangement for surface T/C’s for the damper mounted external to the furnace

18
prEN 1366-10:2004 (E)

Figure 10 - details of perforated plate pressure control device

Figure 11 - details for mounting the perforated plate pressure control device

Figure 12, 13, 14, 15 - arrangement and mounting details off gas testing probes and nozzles
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

The initiation regime should be selected from 6.1.1

7 Test procedure

7.1 Pre-test calibration

7.1.1 Oxygen-measuring instrument

Calibrate the measuring instrument just prior to the fire test.

7.1.2 Perforated plate

Switch on the extract fan. Check that both the required differential pressure and air velocity of 3 m/s
are obtained under ambient conditions. Ensure the air velocity is within ± 15 % and the differential
pressure is within ± 3 %. However, if these values cannot be achieved, switch off the fan, remove the
perforated plate and as appropriate, drill additional holes or seal some holes using screws. Replace
the perforated plate and repeat the procedure until the required values have been achieved.

NOTE The initial check on the perforated plate should be undertaken on a duct section provided for the
purpose and not the test specimen where the removal of the plate may create problems.

7.1.3 Leakage measurement at ambient temperature

Seal the two openings in the duct that are located inside the furnace.

Switch on the extract fan, making any fine adjustments so that the differential pressure reading is
within ± 3 % of the prescribed value given in table 1 throughout the time over which the leakage
measurements are taken.

NOTE The pressure level may be selected by the sponsor, alternatively it is possible to progressively work
up from pressure level 1 to pressure level 3, subject to compliance with 6.13.

Switch on measuring equipment related to the ambient leakage measuring device.

After stable conditions are achieved, for a period of not less than five minutes measure and record the
pressure differential through to the ambient leakage measuring device at the selected pressure level.
Where information is required on leakage at other pressure levels, repeat the procedure. Calculate
the airflow in accordance with ISO 5167/ISO 5221.

Switch off measuring equipment and the extraction fan.

Remove sealing from openings.

7.2 Fire test

7.2.1 Extraction fan

Switch on the extraction fan and make any adjustments to the damper or fan to maintain the
differential pressure at the selected pressure level given in Table 5.

19
prEN 1366-10:2004 (E)

7.2.2 Ignition of furnace

Ignite the furnace and switch on all measuring equipment.

7.2.3 Furnace conditions


Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

Throughout the test, maintain the furnace conditions to comply with the requirements of clause 5 of
this standard. Make any adjustments necessary to maintain the differential pressure readings inside
the duct to within ± 3 % of the appropriate value given in the third column of table 1 after 5 min of the
start of the test.

7.2.4 Temperatures and pressures

Record all temperatures and pressures at the intervals specified in EN 1363-1.

7.2.5 Oxygen measurements

After the first minutes of the test, start recording the oxygen measurement, readings being taken at
the furnace location and then at the nozzle location.

7.2.6 General observations

Take observations on the general behaviour of the duct throughout the test, in particular observe for
collapse of any part of the duct inside and outside of the furnace that would effect the liability of
function for the purpose for which it is intended.

7.2.7 Reduction of cross-section

Record continuously via video camera, and using imaging software check cross sectional area
changes to ensure area does not decrease by more than 10 %

7.2.8 Leakage calculations

Using the values recorded, calculate the leakage from the O2 measurements as follows:

C f × mG2 × (c G2 − c G1 )
mL =
21 − c G1

where

mL is the leakage mass flow (kg/s)

mG2 is the mass flow at point G2 near inlet nozzles (kg/s)

cG1 is the oxygen content of first sensor (vol-%)

cG2 is the oxygen content of second sensor (vol-%)

Cf the correction factor, is determined as follows:

0,79 × Lmin + 1,85 × C


Cf =
0,79 × Lmin + 1,85 × C + ( 21 − c G2 ) × 0,529 × H

20
prEN 1366-10:2004 (E)

where

C is the carbon content in fuel (kg/kg fuel)

H is the hydrogen content in fuel (kg/kg fuel)


Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

S is the sulphur content in fuel (kg/kg fuel)


3
Lmin is the minimum stoichiometrical air needed (m /kg fuel) at standard temperature and
pressure

Lmin is determined as follows:

Lmin = 8,88 × C + 26,44 × H + 3,33 × S

where

VL shall be used to determine compliance with the leakage criteria stated in 11.3 and is calculated
as:

mL
VL =
ρ
3
VL is the leakage volume flow (m /s)
3
ρ is the density of dry air at 20 °C/1013 hPa (= 1,2 kg/m )

7.3 Termination of test

The test may be terminated

a) at the request of the sponsor;

b) at end of classification period (or if a serious failure occurs);

c) when criteria is exceeded leakage (but this may need to be calculated after the test); if duct
inside furnace collapses and reduction of cross-section (confirmed after test).

8 Test report
In addition to the items required by EN 1363-1, the following shall also be included in the test report:

a) The method of fixing, support and mounting, as appropriate for the type of specimen, and a
description of the method and materials used to seal the gap between the duct and opening
provided in the wall to accommodate the duct, the details of the supporting construction.
Connections of the damper to the duct etc.

b) Other observations made during the test including a complete record of the following test
parameters as a function of time:

 furnace temperature;

 furnace pressure;

 volume flow measuring station gas temperatures;

21
prEN 1366-10:2004 (E)

 volume flow measuring station pressure differential;

 calculated volume flow rate;

 differential pressure between inside and outside the duct (negative values indicate
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

underpressure).

c) Details of the leakage measured in accordance with section 7.

d) Where the test is terminated before the occurrence of failure under the relevant criteria, this shall
be reported.

e) Where steel ducts are used, the thickness, leakage class to EN 1507 and details of any external
stiffening or internal stiffeners if incorporated.

f) Full calculations in accordance with section 7.

g) All measurements and observations recorded in respect to reduction in cross-section.

9 Direct field of application of test results

9.1 General

The requirements for direct field of application for all dampers tested to EN 1366-1 apply, together
with the following.

NOTE CHECK ALSO 1366-2.

9.2 Damper sizes

Dampers smaller than the sizes tested may be used.

9.3 Application of dampers to different positions in ducts

Dampers tested in the positions shown in the figures may be applied to any surface of the ductwork
and where necessary between sections of ductwork, where this does not occur at a compartment
barrier. Dampers installed in ductwork at compartment barriers must be tested to the methods defined
for this purpose.

9.4 Pressure difference

The test results of the smoke control dampers are applicable to smoke control dampers with an
underpressure or overpressure up to the relevant values as specified in Table 7.

Table 5 — Pressure difference


Tested pressure level Underpressure Overpressure
(see Table 1) up to up to

1 500 Pa 500 Pa
2 1000 Pa 500 Pa
3 1500 Pa 500 Pa

22
prEN 1366-10:2004 (E)

9.5 Elevated temperatures

Multi compartment smoke control dampers tested to the EN1363-1standard fire test curve are suitable
for single compartment applications for the same time period and other application data.
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

Single compartment smoke control dampers tested to elevated temperatures are applicable to all
temperatures below the temperature tested for the same time period and other application data.

9.6 Cycling tests

9.6.1 Smoke control dampers meeting the cycling requirements for modulating applications

Are also applicable to

a) systems for use with combined smoke control and general HVAC applications;

b) systems with smoke control dampers that are cycle checked every day;

c) systems where the dampers are operated only in the case of emergency.

9.6.2 Smoke control dampers meeting the cycling requirements for use with combined
smoke control and general HVAC applications and for smoke control systems that are cycle
checked every day

Are also applicable to

a) systems where the dampers are operated only in the case of emergency.

9.6.3 Smoke control dampers meeting the cycling requirements for dampers that are
operated only in the case of emergency

Are not applicable to other installations.

9.7 Initiation method

Smoke control dampers that are tested for systems with manual intervention are suitable for
application in automatic systems, but not vice versa.

9.8 Application to duct constructions other than that tested

9.8.1 Single compartment Smoke Control dampers

Dampers may be applied to ducts that have been tested to EN 1366-9, constructed from materials of
the same density as those tested or of the same material with a greater density or thickness.
Application may not be made where there is a change in the surface protection materials. Any paint
surface finish should be as the duct tested or assessed.

9.8.2 Multi compartment Smoke Control dampers

Dampers may be applied to ducts that have been tested to EN 1366-9 and 1366-8 as appropriate,
constructed from materials of the same density as those tested or of the same material with a greater
density or thickness. Application may not be made where there is a change in the surface protection
materials. Paint surface finish, should be as the duct tested or assessed.

23
prEN 1366-10:2004 (E)

3
2
1
4 8
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

100
5 6

500 ±50
7

9 G1 9
10

H
250 ±50
11

12
13
14
5 11 7
500

15

G1
9 9
W
10
500

250 ±50

4 000
500 2 500
3 000

Key

1 Furnace roof 10 Duct


2 Observation window 11 Duct surface EN 1366-9
3 Mirror 12 Supporting construction (wall)
4 Video camera 13 Fire stopping as in practice
5 Furnace chamber 14 Thermocouple (see Figure 8)
6 Damper during the test open 15 Detail Figure 13
7 Perforated plate W Width
8 Damper during the test closed H Height
9 Joints G1 Gas sample sensor at the perforated plate

Figure 1 — Test arrangement for smoke control damper 600 °C mounted to the surface of the
duct EN 1366-9

24
prEN 1366-10:2004 (E)

I
1
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

2
500 500
A 3
X X X

X A X X
1/2
100

1
100 ±50
=

X X
=

6
A -A

Key

1 Furnace roof
2 Supporting construction (wall)
3 Duct surface
4 Duct
x Thermocouples

Figure 2 — Arrangement of furnace thermocouples

25
prEN 1366-10:2004 (E)

100 ±50
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

5 7

H
6
250 ±50
4

a) Start with the damper in the closed position (see Table 1 and 3.11)

9
1
500

W
5
500

250 ±50
10 4 000

3 000

b) For test according to 3.12 and 3.13 start in the open position

Key

1 Furnace chamber 7 Mirror


2 Furnace roof 8 Supporting construction (wall)
3 Video camera 9 Fire stopping as in practice
4 Damper, open during the test 10 Furnace roof
5 Duct W Width
6 Observation window H Height

Figure 3 — Test arrangement for opening and loss of free area test Smoke control damper
mounted as in EN 1366-2 (see 6.3.3, 6.3.4 and 6.3.5)

26
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

prEN 1366-10:2004 (E)

5
1
3
2

8 9
6 7

17

p
25 16 19
14 15
10 12
11 18
13 21
20

Key

1 Supporting construction (wall) 10 19 Pressure control dilution damper


2 Connecting duct (to a maximum of 2 m) 11 20
3 Pressure probe 12 Pressure sensor (on centre line) 21
4 Pressure sensor in laboratory 13 Support
5 Pressure differential control box 14 Flange
6 Observation window 15 Support
7 Thermocouple, 1,5 diameter 16 Support
8 Orifice plate or venturi 17
9 Flow strainghtener (where necessary) 18 Flexible connecting duct

Figure 4 — General test arrangement showing flow measuring equipment

27
prEN 1366-10:2004 (E)
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

25 2

25
Ts
T1

3
T1
Ts

Key

1 Furnace
2 Duct EN 1366-8 or EN 1366-9
3 Damper
4 Supporting construction
TS Maximum surface on supporting construction
T1 Surface thermocouples for determining maximum temperature
Ts,T1 Minimum of one each side of the duct
Surface thermocouples

NOTE Supporting construction and location of surface thermocouples to fire resisting

Figure 5 — Location of surface thermocouples to test Figure 3 + 4

28
prEN 1366-10:2004 (E)

3
2
1
4 8
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

100
5 6

500 ±50
7

9 G1 9
10

H
11

250 ±50

12

14
5 13
500

11
7 15

G1
9 9 W
10
500

4 000
250 ±50
500 2 500
3 000

Key

1 Furnace roof 10 Duct


2 Observation window 11 Duct surface EN 1366-8
3 Mirror 12 Supporting construction (wall)
4 Video camera 13 Fire stopping as in practice
5 Furnace chamber 14 Thermocouples see Figure 8
6 Damper, open during the test 15 Detail Figure 13
7 Perforated plate W Width
8 Damper, closed during the test H Height
9 Joints G1 Gas sample sensor at the perforated plate
Figure 6 — Test arrangement for smoke control damper EN 1363-1, mounted to the surface of the
duct EN 1366-8

29
prEN 1366-10:2004 (E)

1
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

4 000
2
2

250±50
100

3 4
G1 G1
5 500 500 500 500

250 ±50
6

250 ±50
7
8

3 000
9
10 11 10
H
W

12 12

10

13
Key

1 Damper, closed during the test 9 Observation window


2 Perforated plate 10 Duct
3 Furnace roof 11 Furnace wall
4 Fire stopping as in practice 12 Furnace chamber
5 Video camera 13 Smoke control damper in the open position
6 Duct surface W Width
7 Damper, open during the test H Height
8 Mirror G1 Gas sample sensor at the perforated plate

Figure 7 — Test arrangement for smoke control damper EN 1363-1, mounted to the surface of
the vertical duct EN 1366-8

30
prEN 1366-10:2004 (E)

1 1 5
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

A-A

2
3 3

2 3 2

A 1 1 A

3 3
2

14 1
NOTE For walls consisting of grills, the measuring points are arranged on the grills.

Key

1 on the inside of the housing (or on the stop), 25 mm away from the lamination
2 on the lamination, 25 mm away from the housing (or on the stop)
3 on the lamination (remaining surfaces)
4 within the motor box
5 grill

Figure 8 — Arrangement of surface thermocouples for damper 4, see Figure 1,6 and 7

31
prEN 1366-10:2004 (E)
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

NOTE The test results during the test Figure 1 are applicable to spiral piping when using a saddle piece

Figure 9 — Connection of smoke control dampers with spiral duct

32
prEN 1366-10:2004 (E)

B + 2d

d
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

c
a

b
H + 2d

H
d

e
B

Material: Heat resisting steel


Percentage of chrome minimum 19 %
Percentage of nickel minimum 11 %

NOTE For d see Figure 1, 6 and 7.

Pressure stage
Pressure differential at ambient temperature (Pa) - 1500
Pressure differential during the fire test (Pa) - 500
Diameter of hole (mm) 10
Number of holes horizontal (piece) 36
Number of holes vertical (piece) 9
Total number of holes 324
Distance rim horizontal e (mm) minimum 20
maximum 100
Distance rim vertical c (mm) minimum 20
maximum 100
Mounting hole a separation (mm) minimum 27,4
Mounting hole b separation (mm) minimum 26,3

NOTE The table given in value for rectangular duct minimum size 1000 mm x 250 mm. For smaller sizes the
number of holes will be reduced proportional to the smaller cross section.

Figure 10 — Test arrangement for test A, B and C see EN 1366-8

33
prEN 1366-10:2004 (E)

a) Installation of the perforated plate into the


duct of sheet steel
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

2 3
1 4
2

d
5

b) Installation of the perforated plate into the


duct of fire resisting boards

100 6

5
20

≈5

≈5

Key

1 Duct 4 Ceramic felt strip


2 Flange 5 Perforated plate
3 Screwed 6 Ceramic wool stuffed

Figure 11 — Mounting of perforated plate

34
prEN 1366-10:2004 (E)

1
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

100
2 4
3 5
6

250
G1 G2

9
250 ±50
7 8
10
11 12

13
14
4 G2
12
D1
3
G1
1 000

6
11 A
A

7 250 ±50
9 15

16
Key

1 Furnace roof 10 Test duct


2 Fire stopping as in practice 11 Flow pressure control
3 Perforated plate 12 Fan
4 Thermocouple 1,5 mm diameter 13 Supporting construction (wall)
5 Connecting tube 14 Piezometric ring
6 Joints 15 Distance: Inlet nozzle to thermocouple = 2d
7 Furnace chamber 16 Detail see Figure 13
8 Duct surface G1 Gas-testing probe at the perforate plate
9 Inlet nozzle G2 Gas-testing probe

Figure 12 — Arrangement of gas-testing probes

35
prEN 1366-10:2004 (E)

1
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

2 G2 3

4
5
6
3
G2

D1
500

225
2
4

225

7
40

R4 5
6

0 A
R4
292

248
240

160

A
A-A
40
120
400

Key

1 Connecting tube (tightly welded, inlet 5 Piezometric ring


nozzles pos. 20 welded on) 6 Thermocouble 1,5 m diameter
2 Inlet nozzle 7 Distance: Inlet nozzle to thermocouple = 2d
3 Fan 8 Detail Pos. 20 and 22
4 Flow pressure control G2 Gas-testing probe

Figure 13 — Detail to Figure 1, 6 and 12

36
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

A-A
A

40
B

A-A
240

248
240
160

Figure 14 — Inlet nozzle


R4
0
A

40

R4

40
120

400
prEN 1366-10:2004 (E)

37
prEN 1366-10:2004 (E)
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

2 3

Key

1 Insulation
2 Inlet nozzle
3 Furnace roof
4 Test duct

Figure 15 — Method of mounting nozzles to the duct symbol

38
prEN 1366-10:2004 (E)

Annex A

Cycling test
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

A.1 General
Three different requirements are placed on smoke control dampers as described in 6.1.2.

The results of the tests shall record that the cycles from the closed position to the open position and
from the open position to the closed position (where required) were fully completed and that each
travel took not longer than 60 seconds.

A.2 Purpose of the test


For fire dampers, which have the closed position as safety position, any torque supports the closing
process, so no test is required in the case of flow.

Due to their nature, Smoke control dampers have to open against pressure and flow. Their ability to
do this must be confirmed by test.

To do this economically without the use of actual flow the smoke control damper must be subjected to
a resistive force.

A.3 Method of Application

A.3.1 General

For each smoke control damper the following torque shall be applied to each blade.
2
T = 34.4 x (BW/1000) x (BH/1000)

where 34.4 is the base value, BW = the damper blade width in mm and BH = damper blade height in
mm.

See section 4 for background.

A.3.2 Smoke Control Damper with single blade

As an example, the torque on a damper with a large single blade area may be determined.

Blade size = 1500 mm wide x 800 high


2
T = 34.4 x (1500/1000) x (800/1000) = 33 Nm

39
prEN 1366-10:2004 (E)

The test arrangement is shown in Figure A.1 and the load is determined as follows:

torque
L=
a × 9.81
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

α = Opening angle at the greatest torque has been obtained

a = Lever arm length (m)

L = Load (kg)

Torque = (Nm)

The number of cycles shall then be made as per the requirements stated in 6.1.2.

The surface of the blade shall be made good only if necessary, without compromising or increasing
the damper’s ability to perform in the fire test.

45 ˚

Key

1 Load

Figure A.1 — Testing method large single blade dampers

40
prEN 1366-10:2004 (E)

A.3.3 Smoke Control Damper with multi blades of smaller area

As an example, the torque on a damper with a large single blade area may be determined.

Blade size = 1000 mm wide x 75 high


Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

2
T = 34.4 x (1000/1000) x (75/1000) = 0.19 Nm

The load shall be applied to each individual blade to give the prescribed torque.

Methods to do this may include the addition of metal strips or similar to the surface of the blade by
means of removable adhesives / magnets etc. or on large units a method similar to 3.2 above may be
used.

torque
L=
a × 9.81

α = Opening angle at the greatest torque has been obtained

a = Moment distance

L = Load (kg)

Torque = (Nm)

The number of cycles shall then be made as per the requirements stated in 6.1.2.

The surface of the blade shall be made good only if necessary, without compromising or increasing
the damper’s ability to perform in the fire test.

A.3.4 Report

The test report shall include

a) a drawing of the test specimen (see 3.2), so that it is possible to check the applied load;

b) details of any making good/ blade cleaning/fixing.

A.4 Background for the Torque Value

A.4.1 Threshold rates of the working condition of the system

In conformity with standard designed systems, a flow rate of 10 m/s (at ambient temperature) in the
open position and a differential pressure of 1500 Pa in the closed position were considered.

Considering the above the volumetric flow rate passing through a smoke and heat exhaust damper
with largest dimensions of 1500 mm x 800 mm in the open position would be

3 3
V& = 1,5m ⋅ 0.8m ⋅ 10 m = 12 m = 43200 m
s s h

A.4.2 Previous experience

Several tests with smoke and heat exhaust dampers, designed like fire dampers (single blade
dampers) with closing elements in the form of only one approximately 50 mm thick damper blade,

41
prEN 1366-10:2004 (E)

have shown that the greatest torque working against the opening process was in case of damper
blades for smoke and heat exhaust dampers at an aperture angle of 40° and 65°. It could also be
established that for the lifting of the damper blade from the closed position only minor torques are
necessary, if the housing is not deformed by the prevailing pressure.
Licensed Copy: lapdwilliams1 lapdwilliams1, University of Central Lancashire JISC, 27 February 2005, Uncontrolled Copy, (c) BSI

In the laboratory, the torques of dampers of sizes (Height x Width) 800 x 500 and 400 x 100 mm have
been tested at a flow rate of 10 m/s. It can be deduced from the test results that following torques act
on 50 mm thick damper blades:

For H = 800 mm 22 Nm per 1 m width

For H = 400 mm 10,5 Nm per 1 m width

Using the above figures the base value of 34.4 Nm, for use in the equation, was determined.

42

You might also like