Ref : PFE/3JT/SS-1001

Date : 24-12-2022

To,
Managing Director

Project: Narayngonj

Sub : Offer for supply, installation, testing & commissioning of 400KVA (320Kw) Sub-station
equipment include of HT Switchgear, Transformer, LT switchgear and PFI Plant for the Project.

PART-A (EQUIPMENTS)
SL # Descriptions Qty. Unit Unit price Total price
In Taka In Taka
1 11KV Lightning Arrestor 1 Set 12,000.00 12,000.00
2 11KV Drop Out Fuse 1 Set 12,000.00 12,000.00
3 11KV HT Heat Shrink Tubing Kit 4 Set 3,000.00 12,000.00
4 11KV, 630A HT Swithchgear(LBS) 1 Set 220,000.00 220,000.00
5 400KVA Oil Immersed Transformer 1 No 750,000.00 750,000.00
6 630A LT Switchgear Panel 1 No. 240,000.00 240,000.00
7 240kVAr Auto/Manual PFI plant 1 Set 220,000.00 220,000.00
8 Earthing for Substation 4 Set 20,000.00 80,000.00
Miscellaneous Expenses for License (ELB), with
9 Govt. fee (Govt. Fee-17910 Tk). 1 Job 75,000.00 75,000.00
At Ground Floor
Transportation, Installation, Testing &
10 1 Job 50,000.00 50,000.00
Commisioning
Total Amount in Taka Part (A) 1,671,000.00
In words: Sixteen Lac Seventy One Thousand BDT Only.

TERMS & CONDITIONS :

01) Validity : Our offer will remain valid for a period of 30 days from the date of this offer.
02) Delivery : Within 25 working days after receipt of confirmed order & payment asper clause # 3.
03) Payment : 60% with work order , 20% at the time of delivery & rest 20% after installation.
04) Warranty : 24 Months all Equipments.
05) VAT & AIT: Our offer Excluded All VAT & AIT.

Thanking you.
For, Powerfast Engineering

Arafat Hossen Nadim


Milon Hossain B.Sc in EEE
B.Sc in EEE Director
Proprietor Cell: 01996647714
Cell: 01996647712
TECHNICAL SPECIFICATIONS OF 400KVA SUBSTATION

01) 11KV DROUP OUT FUSE

11KV drop-out fuse complete with all fitting, fixing and


necessary accessories etc.

11KV Drop-out fuse has the following specifications :

Rated voltage (nominal) : 11KV


Rated max.voltage : 12KV
Rated current(conti.)RMS : 60A
Interrupt current RMS : 10KA
Rated frequency : 50 Hz
BIL : 75KV
Withstand test voltage
Dry, 1 Min. : 33KV
Wet, 10 sec. : 30KV
Brand: Siemens/Equivalent

02) 11KV LIGHTINING ARRESTER

11KV Lightning arrestor of following specifications :

Rated Voltage (Nominal) : 11 KV


Rated System Voltage : 12 KV
Frequency : 50 Hz
Minimum spark over (RMS) : 14 KV
Maximum spark over (RMS) : 40 KV
Maximum implus spark (crest) : 45 KV
BIL (Peak) : 75V
Power frequency 1 min. dry : 28 KV
Power frequency 10 sec wet : 24 KV
Niminal descharge current : 5 KA
implus current with stand : 55 KA
Brand: Siemens/Equivalent
03) 11KV, 630A HT SWITCHGEAR PANEL

Manufacture of sheet steel metal clad, 14/16 SWG powder coated, dust &
vermin proof, floor mounting, HT Switchgear Panel 11KV, 50 Hz with hard
drawn electrolytic TP copper bus bars comprising:

Load Break Switch (LBS), 11KV, 50Hz, 20KA, Interlocked with Earth Switchand
1 inter tripping arrangements whenever any of the fuse blows.

Brand: F&G, Germany

2 11 KV Potential Transformer
Ratio : 11000 / 110 V
Burden : 30 (50) VA
Class : 0.5P
Brand: Siemens, India

3 11 KV Current Transformer
Ratio : 30 / 5 / 5 A
Burden : 15 VA
Class : 0.5P
Brand: Siemens, India

1 Digital KV Meter (0 – 15 KV) With Selector switch


Brand: Risesun, Taiwan

1 Digital Ammeter (0 – 30 A) With Selector switch


Brand: Risesun, Taiwan

3 Phase Indicating lamp(R/Y/B)

1 6A TP, MCB for Control Circuit


Brand: Made by Schneider Electric

1 Set HT Linking Copper Busbar (40X10)mm

1 Lot Fan, Louver, Heat Shrink, Busbar Supporter, Heat Shrink Tube, Nut-Bolt etc.

Panel Size: (H:1900 x W: 900 x D:900)mm

ASSEMBLED BY POWERFAST ENGINEERING


04) 11KV, 400KVA OIL TYPE TRANSFORMER

Three phased transformers ground mounted,oil


immersed, with standard accessories. Indoor use.

Routine tests and first filling oil included.

Design, manufacturing, routine tests & tolerances


according to IEC 76 standards.

Standard fittings : 4 flat bi-directional rollers.


2 lifting lugs
2 earthing points.
1 rating plate(on HV side)
1 Silica Gel Breather
HV connections : porcelain bushing
LV connections : porcelain bushing

Rated power in KVA :400kVA


Frequency : 50 Hz
System voltage : 12 kV
Primary voltage : 11000V
HV tapping by links(off circuit) in :±2.5%,-5%,
Secondary voltage : 415V
HV impulse KV peak in KV : 75 kV
Power frequency KV rms : 28 kV
Vector group : Dyn11
Max. ambient temp. in Deg. C : 40
Altitude lower thank in meter : 1000
Temp. rise in winding/oil in Deg. C : 65/55
No load loss : 841W
Load loss at 75 Deg. C : 4800W
Impedance voltage : 4%

Brand & ORIGIN:


Core: JFE, Japan
Insulation: ABB, Italy (Ramob Board)
Transformer Oil: Savita, India
Super Enamelled Copper : SQ wire, Bangladesh

ASSEMBLED BY POWERFAST ENGINEERING


05) 630A LT SWITCHGEAR PANEL
16 SWG Sheet steel fabricated, floor mounting, tropicalized design, indoor
type, low tension switchgear for 3 phase, 4 wire, 50 Hz, 380/
415V AC system & shall be supplied complete TPNE busbars
suitably sized & properly insulated arrange to withstand & short
current of 50KA for 1 sec.
The boards are designed & constructed in accordance with
BS 5486/IEC439.

The panel shall comprise of :

INCOMING :
1 630A, TP, MCCB, 65KA, 415V, 50Hz, with Adjustable thermal
overload & Electronic adjustable magnetic short circuit protection.
Brand: Hyundai, Korea

3 Current transformer:630/5A with suitable accuracy and burden.


3 Ammeter, 0-600 A.
1 Voltmeter, 0-500V with selector switch.
Brand: Mikrowell, China.

3 Phase indicator RED/YELLOW/BLUE.


Origin: China

OUTGOING:

1 400A, TP, MCCB, 65KA, 415V, 50Hz, with Adjustable Thermal FOR PFI
overload & magnetic short circuit protection.
Brand: Hyundai, Korea

1 350A, TP, MCCB, 65KA, 415V, 50Hz, with Adjustable thermal FOR BDB
overload & magnetic short circuit protection.
Brand: Hyundai, Korea

1 125A, TP, MCCB, 25KA, 415V, 50Hz, with Adjustable thermal FOR CMDB
overload & magnetic short circuit protection.
Brand: Hyundai, Korea

1 63A, TP, MCCB, 25KA, 415V, 50Hz, with Adjustable thermal FOR SOLAR INVERTER
overload & magnetic short circuit protection.
Brand: Hyundai, Korea

1 63A, TP, MCCB, 25KA, 415V, 50Hz, with Adjustable thermal FOR SPARE
overload & magnetic short circuit protection.
Brand: Hyundai, Korea
1 40A, TP, MCCB, 25KA, 415V, 50Hz, with Adjustable thermal FOR SPARE
overload & magnetic short circuit protection.
Brand: Hyundai, Korea

1 SET TPN Copper Busbar Suitable Sized.


2 SET Earthing Terminal

1 SET Control fuse with base


3 Phase Indication ON/OFF/TRIP

1 Accessories(Cable, Fan with thermostate, Louver, Heat Shrink, Busbar Supporter, Heat Shrink Tube, Nut-Bolt etc.)

Panel Size: H: 1700mm X 800mm X 600mm

ASSEMBLED BY POWERFAST ENGINEERING

06) 240KVAR AUTOMATIC PFI PLANT

Automatic power factor improvement plant of 240KVAR. 16 SWG


Sheet steel fabricated,floor mounting, tropicalized design, indoor type,
power coated low tension switchgear for 3 phase, 4 wire, 50 Hz
380/415V AC system and shall be supplied complete TP + N busbars
suitably sized & properly insulated arrange to withstand and
short current of 50KA for 1 sec.
The boards are designed & constructed in accordance with
BS5486/IEC298
-
The panel shall comprise of :
1 5 KVAR,415V,50Hz ,3 phase , self healing
compact PF capacitors bank with discharge resistor. Fixed

1 5 KVAR,415V,50Hz ,3 phase , self healing


compact PF capacitors bank with discharge resistor.

4 7.5 KVAR,415V,50Hz ,3 phase , self healing


compact PF capacitors bank with discharge resistor.

2 12.5KVAR,415V,50Hz ,3 phase , self healing


compact PF capacitors bank with discharge resistor.

3 25 KVAR,415V,50Hz ,3 phase , self healing


compact PF capacitors bank with discharge resistor.

2 50(25X2) KVAR,415V,50Hz ,3 phase , self healing


compact PF capacitors bank with discharge resistor.

Brand: Schneider Electric, India (Brand of Europe)


1 12A (Ith 25A) TP Magnetic Contactor
4 18A (Ith 40A) TP Magnetic Contactor
2 25A (Ith 45A) TP Magnetic Contactor
3 50A (Ith 70A) TP Magnetic Contactor
2 100A (Ith 145A) TP Magnetic Contactor
Brand: Hyundai, Korea

6 16A, 6KA, TP MCB


2 25A, 6KA, TP MCB
3 63A, 6KA, TP MCB
2 100A, 25KA, TP MCCB
Brand: Hyundai, Korea

12 Indicating lamp.
Brand: Chint, China
12 Stop Push Button.
Brand: Chint, China

2 4 No & 4 NC Auxiliary contact for damping of in rush current


Brand: Siemens
1 Auto Manual selector switch with adder block
Brand: China
3 Fuse carrier with fuse for control circuit protection
Brand: Linder, China
4 Control relay with base.
Brand: Omron/Equivalent

1 12 Steps reactive power regulator which performs the switching


of capacity bank in automatic power factor correction equipments
depending on changes of reactive power complete with p. f. I
Luminiescent indicators and digital power factor meter.
Brand: Mikro, Malaysia

1 400/5A CT
Brand: Raisesun, Taiwan

1 SET TP+E Busbar suitably sized.

1 Accessories (Cable, Fan with thermostate, Louver, Heat Shrink, CT, Busbar Supporter, Heat Shrink Tube, Nut-Bolt etc.)
Panel Size: (H:1700 x W: 800 x D:600)mm
ASSEMBLED BY POWERFAST ENGINEERING