You are on page 1of 4

LIQUID PENETRANT EXAMINATION REPORT

Job/Contract No. : PO-13433082 Work Order No. : PO-13433082 Page : 1 of 4


Project : Square Tank 1 M3 - S/N.TK-DKE-002 Report No. : 02-PT-DKE-VIII-2022
Location : PT.Karya Baja Indonesia - Bekasi Drawing No. : KBI-ENG-DWG-001
Customer : PT.Unilever Indonesia Tbk - Walls Factory Procedure No. : QP-DKE-05 Rev.0
Lighting Equipment : HALOGEN
Light Meter Type : KRISBOW S.N. 170909865 Light Intensity : 1230 Lux
Surface Condition : Welded Ground Flush Other ( )
Stage of Exam. : After welding After Hydrostatic Other ( )
Welding Process : GTAW SMAW Other ( )
Scope of Base Metal Back Chipping Weld Part
Examination Edge Prep. Repair Weld Other ( )
Penetrant Water Was. Post Emulsifier Solvent Removable )
Batch No. (B.N.) : SKL-SP1 Other ( MAGNAFLUX ) Dwell Time ; 5 Minutes
Application By Brushing Other ( ) Temp. : 35 0C
Developer Type of Developer Dry Developer Aqueous Dev. Non Aqueous Dev.
B.N. : SKD-S2 Other ( ) Interpretation Time5 :Minutes
……
Cleaner SKC-S Applicable Code :
B.N. : Other ( )
ASME SECTION VIII DIV 1
Type of Penetrant Visible Fluorescent
Part / Welding Material &
Welder ID Judgement Type of Discontinuity Remark
Identification Thickness (mm)
Square Tank 1 M3 Unit #2

Top LS 1 S/S X 3 mm W 01 ACC None No Defect Indication

Top LS 2 S/S X 3 mm W 01 ACC None No Defect Indication

Top LS 3 S/S X 3 mm W 01 ACC None No Defect Indication

Top LS 4 S/S X 3 mm W 01 ACC None No Defect Indication

Shell LS 1 S/S X 3 mm W 01 ACC None No Defect Indication

Shell LS 2 S/S X 3 mm W 01 ACC None No Defect Indication

Bottom LS 1 S/S X 3 mm W 01 ACC None No Defect Indication

Bottom LS 2 S/S X 3 mm W 01 ACC None No Defect Indication

Bottom LS 3 S/S X 3 mm W 01 ACC None No Defect Indication

Bottom LS 4 S/S X 3 mm W 01 ACC None No Defect Indication

Bottom LS 5 S/S X 3 mm W 01 ACC None No Defect Indication

Bottom LS 6 S/S X 3 mm W 01 ACC None No Defect Indication

Bottom LS 7 S/S X 3 mm W 01 ACC None No Defect Indication

Bottom LS 8 S/S X 3 mm W 01 ACC None No Defect Indication

Examined By Reviewed/Witnessed By Client's :

Subarsono Indra Heriaman


NDE ASNT Level : II
Date: 06 September 2022 Date: 08 September 2022
LIQUID PENETRANT EXAMINATION PHOTO
Project : Square Tank 1 M3 - S/N.TK-DKE-002 Page : 2 of 4
Location : PT.Karya Baja Indonesia - Bekasi
Customer : PT.Unilever Indonesia Tbk - Walls Factory

Examined By Reviewed/Witnessed By Client's :

Indra Heriaman
NDE ASNT Level : II
Date: 06 September 2022 Date: 08 September 2022
LIQUID PENETRANT EXAMINATION REPORT
Job/Contract No. : PO-13433082 Work Order No. : PO-13433082 Page : 3 of 4
Project : Square Tank 1 M3 - S/N.TK-DKE-002 Report No. : 02-PT-DKE-VIII-2022
Location : PT.Karya Baja Indonesia - Bekasi Drawing No. : KBI-ENG-DWG-001
Customer : PT.Unilever Indonesia Tbk - Walls Factory Procedure No. : QP-DKE-05 Rev.0
Lighting Equipment : HALOGEN
Light Meter Type : KRISBOW S.N. 170909865 Light Intensity : 1230 Lux
Surface Condition : Welded Ground Flush Other ( )
Stage of Exam. : After welding After Hydrostatic Other ( )
Welding Process : GTAW SMAW Other ( )
Scope of Base Metal Back Chipping Weld Part
Examination Edge Prep. Repair Weld Other ( )
Penetrant Water Was. Post Emulsifier Solvent Removable )
Batch No. (B.N.) : SKL-SP1 Other ( MAGNAFLUX ) Dwell Time ; 5 Minutes
Application By Brushing Other ( ) Temp. : 35 0C
Developer Type of Developer Dry Developer Aqueous Dev. Non Aqueous Dev.
B.N. : SKD-S2 Other ( ) Interpretation Time5 :Minutes
……
Cleaner SKC-S Applicable Code :
B.N. : Other ( )
ASME SECTION VIII DIV 1
Type of Penetrant Visible Fluorescent
Part / Welding Material &
Welder ID Judgement Type of Discontinuity Remark
Identification Thickness (mm)
Square Tank 1 M3 Unit #2

M1 S/S X 3 mm W 01 ACC None No Defect Indication

N1 S/S X 3 mm W 01 ACC None No Defect Indication

N2-1 S/S X 3 mm W 01 ACC None No Defect Indication

N2-2 S/S X 3 mm W 01 ACC None No Defect Indication

N2-5 S/S X 3 mm W 01 ACC None No Defect Indication

N2-6 S/S X 3 mm W 01 ACC None No Defect Indication

N3 S/S X 3 mm W 01 ACC None No Defect Indication

N4 S/S X 3 mm W 01 ACC None No Defect Indication

Examined By Reviewed/Witnessed By Client's :

Subarsono Indra Heriaman


NDE ASNT Level : II
Date: 06 September 2022 Date: 08 September 2022
LIQUID PENETRANT EXAMINATION PHOTO
Project : Square Tank 1 M3 - S/N.TK-DKE-002 Page : 4 of 4
Location : PT.Karya Baja Indonesia - Bekasi
Customer : PT.Unilever Indonesia Tbk - Walls Factory

Examined By Reviewed/Witnessed By Client's :

Indra Heriaman
NDE ASNT Level : II
Date: 06 September 2022 Date: 08 September 2022