This penetrant test report from PT. Argacita Damai Sejahtera summarizes an inspection of welds on a waste water tank for PT. Kamanjaya Teknik Indonesia. The inspection found no defects in welds on the top angle, shell, center ring, gusset ring, extension, rafter, or gusset parts of the tank. The penetrant test was performed on the as-welded surfaces using a solvent removable penetrant and following the applicable ASME VIII code.
This penetrant test report from PT. Argacita Damai Sejahtera summarizes an inspection of welds on a waste water tank for PT. Kamanjaya Teknik Indonesia. The inspection found no defects in welds on the top angle, shell, center ring, gusset ring, extension, rafter, or gusset parts of the tank. The penetrant test was performed on the as-welded surfaces using a solvent removable penetrant and following the applicable ASME VIII code.
This penetrant test report from PT. Argacita Damai Sejahtera summarizes an inspection of welds on a waste water tank for PT. Kamanjaya Teknik Indonesia. The inspection found no defects in welds on the top angle, shell, center ring, gusset ring, extension, rafter, or gusset parts of the tank. The penetrant test was performed on the as-welded surfaces using a solvent removable penetrant and following the applicable ASME VIII code.
INSPECTION AND CERTIFICATION Office : Griya Kebraon Tengah 14 Blok Y.32, Surabaya Phone /Facs. 031 7666844, Hp. 081330959514 E-mail. nbhartanto_argacita@yahoo.com
PENETRANT TEST REPORT
Customer : PT. KAMANJAYA TEKNIK INDONESIA Report No : 01/ADS-PT/IV/22 Project : Replacement Roof Tank of Waste Water Tank RN Ref. No : Unit No : Tank TK 14 NCR Ref No : User : PT. AGIP LUBRINDO PRATAMA Drawing No. : 96030014 -08 Procedure No. : P-ADS-04 Applicable CODE : ASME VIII Material Spec. : Carbon Steel Welding Process : SMAW Penetrant Method : X Solvent Removable Water Washable Post Emulsifier Penetrant Material : X Visible Fluorescent Dual Sensitivity Brand’s Name/Type: Magnaflux Penetrant : SKL - SP1 Cleaner: SKC - S Developer: SKD - S2 Light Intensity : 1500 Lux Surface Condition : X As Welded As Machine As Ground Others Time of Examination : X After Welding After Hydro-test After PWHT Others Scope of Examination : Base Metal Edge Prep Back Chipping X Weld Part Repair Weld Others Thickness Result Types Of Part Name Weld No. Remarks ( mm ) Accepted Rejected Discontinuities 1. Top Angle RT-FJ01 10 Acc - 2. Shell TS-FJ-01 5 Acc - 3. Center 12 Acc - Center Ring CR-BJ-01 20 Acc - Gusset Ring CRGB-FJ-01-02 20 Acc - 4. Extension 20 Acc - Rafter RFGR-BJ-01-02 8 Acc - Gusset GGR-FJ01-02 8 Acc -
Sketch ( Identify discontinuities listed above ) if necessary : Please see attachment