You are on page 1of 5

PT.

GINTAM INSPEKSI TEHNIK


NDT Service Solution
Cert. No. IND-
QMS00006
Jl. Bunga mawar komplek citra sembada No. 8 I, Kota Medan - Sumatera Utara 20131
Email : gintaminspeksi@gmail.com I Mobile : 0812 6455 9599

RADIOGRAPHY EXAMINATION REPORT


Owner : PT. Pertamina Patra Niaga Project : Perbaikan Tanki Timbun No.
08 Kap 5.000 KL
Report No. : 001-RT/ITU/III/2023

Contractor : PT. Indoteknik Tjandra Utama Location : Fuel Terminal Sibolga Date Exam : 27 Maret 2023

Procedure No : GIT-RT-API650-02 Radiation Type : Ir- 192 Work Order No. :


Material : Carbon Steel ASTM A36 Curie : 35 Ci Radiographic Technique :
Accept Criteria : ASME VIII kV / mA : -
SWSI
Weld Process : SMAW Source or Film Side : Source Side
Exp. Time : 1.00 Minute Source Size : 0,106 mm Screen Type : Lead
S.F.D : 300 MM Penetrameter / IQI : ASTM 1B Screen Thickness : 0.125 mm
Film Merk : FUJI Shim Thickness : - Density : 2-4
Film Type : IX 100 Sensitivity : 2%

Welder Film Dimenti Thick


Part Identification Joint No. WELD DEFECT RESULT Remark
Stamp Location on MM

JT. 1 A - B Plate 10 ic Acc


JT. 2 A - B Plate 10 slag Acc
JT. 3 A - B Plate 10 por Acc
JT. 4 A - B Plate 10 Acc
JT. 5 A - B Plate 10 Acc
JT. 6 A - B Plate 10 por Acc
JT. 7 A - B Plate 10 Acc
JT. 8 A - B Plate 10 por Acc
JT. 9 A - B Plate 10 slag Acc
BOTTOM PLATE JT. 10 A - B Plate 10 Acc
"ANNULAR"

CR: Crack, IP : Incomplete Penetration, POR : Porosity, IF : Incomplete Fusion, SI : Slag Inclusion, U/C : Under Cut, BT : Burn Through, IC : Internal Concavity

Total Films : 4 X 10" = Sheets 4 X 15" = 10 Sheets 7 X 17" = Sheets

PT. Gintam Inspeksi Tehnik PT. Indoteknik Tjandra Utama PT. Pertamina Patra Niaga FT Sibolga
Ahli Radiography/Interpreter Reviewed / Witnessed by Witnessed / Approved by

Name : Vrengky Tampubolon Name : Name :


Date : 28 Maret 2023 Date : Date :
PT. GINTAM INSPEKSI TEHNIK
NDT Service Solution
Cert. No. IND-
QMS00006
Jl. Bunga mawar komplek citra sembada No. 8 I, Kota Medan - Sumatera Utara 20131
Email : gintaminspeksi@gmail.com I Mobile : 0812 6455 9599

RADIOGRAPHY EXAMINATION REPORT


Owner : PT. Pertamina Patra Niaga Project : Perbaikan Tanki Timbun No.
08 Kap 5.000 KL
Report No. : 002-RT/ITU/III/2023

Contractor : PT. Indoteknik Tjandra Utama Location : Fuel Terminal Sibolga Date Exam : 27 Maret 2023

Procedure No : GIT-RT-API650-02 Radiation Type : Ir- 192 Work Order No. :


Material : Carbon Steel ASTM A36 Curie : 35 Ci Radiographic Technique :
Accept Criteria : ASME VIII kV / mA : -
SWSI
Weld Process : SMAW Source or Film Side : Source Side
Exp. Time : 1.00 Minute Source Size : 0,106 mm Screen Type : Lead
S.F.D : 300 MM Penetrameter / IQI : ASTM 1B Screen Thickness : 0.125 mm
Film Merk : FUJI Shim Thickness : - Density : 2-4
Film Type : IX 100 Sensitivity : 2%

Welder Film Dimenti Thick


Part Identification Joint No. WELD DEFECT RESULT Remark
Stamp Location on MM

JT. 11 A - B Plate 10 por Acc


JT. 12 A - B Plate 10 Acc
JT. 13 A - B Plate 10 Acc
JT. 14 A - B Plate 10 Acc
JT. 15 A - B Plate 10 Acc
JT. 16 A - B Plate 10 ic Acc
JT. 17 A - B Plate 10 por Acc
JT. 18 A - B Plate 10 Acc
JT. 19 A - B Plate 10 ic Acc
BOTTOM PLATE JT. 20 A - B Plate 10 Acc
"ANNULAR"

CR: Crack, IP : Incomplete Penetration, POR : Porosity, IF : Incomplete Fusion, SI : Slag Inclusion, U/C : Under Cut, BT : Burn Through, IC : Internal Concavity

Total Films : 4 X 10" = Sheets 4 X 15" = 10 Sheets 7 X 17" = Sheets

PT. Gintam Inspeksi Tehnik PT. Indoteknik Tjandra Utama PT. Pertamina Patra Niaga FT Sibolga
Ahli Radiography/Interpreter Reviewed / Witnessed by Witnessed / Approved by

Name : Vrengky Tampubolon Name : Name :


Date : 28 Maret 2023 Date : Date :
PT. GINTAM INSPEKSI TEHNIK
NDT Service Solution
Cert. No. IND-
QMS00006
Jl. Bunga mawar komplek citra sembada No. 8 I, Kota Medan - Sumatera Utara 20131
Email : gintaminspeksi@gmail.com I Mobile : 0812 6455 9599

RADIOGRAPHY EXAMINATION REPORT


Owner : PT. Pertamina Patra Niaga Project : Perbaikan Tanki Timbun No.
08 Kap 5.000 KL
Report No. : 003-RT/ITU/III/2023

Contractor : PT. Indoteknik Tjandra Utama Location : Fuel Terminal Sibolga Date Exam : 27 Maret 2023

Procedure No : GIT-RT-API650-02 Radiation Type : Ir- 192 Work Order No. :


Material : Carbon Steel ASTM A36 Curie : 35 Ci Radiographic Technique :
Accept Criteria : ASME VIII kV / mA : -
SWSI
Weld Process : SMAW Source or Film Side : Source Side
Exp. Time : 1.00 Minute Source Size : 0,106 mm Screen Type : Lead
S.F.D : 300 MM Penetrameter / IQI : ASTM 1B Screen Thickness : 0.125 mm
Film Merk : FUJI Shim Thickness : - Density : 2-4
Film Type : IX 100 Sensitivity : 2%

Welder Film Dimenti Thick


Part Identification Joint No. WELD DEFECT RESULT Remark
Stamp Location on MM

JT. 21 A - B Plate 10 slag Acc


JT. 22 A - B Plate 10 Acc
JT. 23 A - B Plate 10 Acc
JT. 24 A - B Plate 10 Acc
JT. 25 A - B Plate 10 Acc
JT. 26 A - B Plate 10 Acc
JT. 27 A - B Plate 10 por Acc
JT. 28 A - B Plate 10 Acc
JT. 29 A - B Plate 10 Acc
BOTTOM PLATE JT. 30 A - B Plate 10 por Acc
"ANNULAR"

CR: Crack, IP : Incomplete Penetration, POR : Porosity, IF : Incomplete Fusion, SI : Slag Inclusion, U/C : Under Cut, BT : Burn Through, IC : Internal Concavity

Total Films : 4 X 10" = Sheets 4 X 15" = 10 Sheets 7 X 17" = Sheets

PT. Gintam Inspeksi Tehnik PT. Indoteknik Tjandra Utama PT. Pertamina Patra Niaga FT Sibolga
Ahli Radiography/Interpreter Reviewed / Witnessed by Witnessed / Approved by

Name : Vrengky Tampubolon Name : Name :


Date : 28 Maret 2023 Date : Date :
PT. GINTAM INSPEKSI TEHNIK
NDT Service Solution
Cert. No. IND-
QMS00006
Jl. Bunga mawar komplek citra sembada No. 8 I, Kota Medan - Sumatera Utara 20131
Email : gintaminspeksi@gmail.com I Mobile : 0812 6455 9599

RADIOGRAPHY EXAMINATION REPORT


Owner : PT. Pertamina Patra Niaga Project : Perbaikan Tanki Timbun No.
08 Kap 5.000 KL
Report No. : 004-RT/ITU/III/2023

Contractor : PT. Indoteknik Tjandra Utama Location : Fuel Terminal Sibolga Date Exam : 27 Maret 2023

Procedure No : GIT-RT-API650-02 Radiation Type : Ir- 192 Work Order No. :


Material : Carbon Steel ASTM A36 Curie : 35 Ci Radiographic Technique :
Accept Criteria : ASME VIII kV / mA : -
SWSI
Weld Process : SMAW Source or Film Side : Source Side
Exp. Time : 1.00 Minute Source Size : 0,106 mm Screen Type : Lead
S.F.D : 300 MM Penetrameter / IQI : ASTM 1B Screen Thickness : 0.125 mm
Film Merk : FUJI Shim Thickness : - Density : 2-4
Film Type : IX 100 Sensitivity : 2%

Welder Film Dimenti Thick


Part Identification Joint No. WELD DEFECT RESULT Remark
Stamp Location on MM

JT. 31 A - B Plate 10 por Acc


JT. 32 A - B Plate 10 Acc
JT. 33 A - B Plate 10 Acc
JT. 34 A - B Plate 10 Acc
JT. 35 A - B Plate 10 Acc
JT. 36 A - B Plate 10 slag Acc
JT. 37 A - B Plate 10 Acc
JT. 38 A - B Plate 10 Acc
JT. 39 A - B Plate 10 ip Acc
BOTTOM PLATE JT. 40 A - B Plate 10 Acc
"ANNULAR"

CR: Crack, IP : Incomplete Penetration, POR : Porosity, IF : Incomplete Fusion, SI : Slag Inclusion, U/C : Under Cut, BT : Burn Through, IC : Internal Concavity

Total Films : 4 X 10" = Sheets 4 X 15" = 10 Sheets 7 X 17" = Sheets

PT. Gintam Inspeksi Tehnik PT. Indoteknik Tjandra Utama PT. Pertamina Patra Niaga FT Sibolga
Ahli Radiography/Interpreter Reviewed / Witnessed by Witnessed / Approved by

Name : Vrengky Tampubolon Name : Name :


Date : 28 Maret 2023 Date : Date :
PT. GINTAM INSPEKSI TEHNIK
NDT Service Solution
Cert. No. IND-
QMS00006
Jl. Bunga mawar komplek citra sembada No. 8 I, Kota Medan - Sumatera Utara 20131
Email : gintaminspeksi@gmail.com I Mobile : 0812 6455 9599

RADIOGRAPHY EXAMINATION REPORT


Owner : PT. Pertamina Patra Niaga Project : Perbaikan Tanki Timbun No.
08 Kap 5.000 KL
Report No. : 005-RT/ITU/III/2023

Contractor : PT. Indoteknik Tjandra Utama Location : Fuel Terminal Sibolga Date Exam : 27 Maret 2023

Procedure No : GIT-RT-API650-02 Radiation Type : Ir- 192 Work Order No. :


Material : Carbon Steel ASTM A36 Curie : 35 Ci Radiographic Technique :
Accept Criteria : ASME VIII kV / mA : -
SWSI
Weld Process : SMAW Source or Film Side : Source Side
Exp. Time : 1.00 Minute Source Size : 0,106 mm Screen Type : Lead
S.F.D : 300 MM Penetrameter / IQI : ASTM 1B Screen Thickness : 0.125 mm
Film Merk : FUJI Shim Thickness : - Density : 2-4
Film Type : IX 100 Sensitivity : 2%

Welder Film Dimenti Thick


Part Identification Joint No. WELD DEFECT RESULT Remark
Stamp Location on MM

JT. 41 A - B Plate 10 ip Acc


JT. 42 A - B Plate 10 Acc
JT. 43 A - B Plate 10 ic Acc
JT. 44 A - B Plate 10 Acc
JT. 45 A - B Plate 10 Acc
JT. 46 A - B Plate 10 Acc
JT. 47 A - B Plate 10 slag Acc
JT. 48 A - B Plate 10 Acc
JT. 49 A - B Plate 10 Acc
BOTTOM PLATE JT. 50 A - B Plate 10 Acc
"ANNULAR"

CR: Crack, IP : Incomplete Penetration, POR : Porosity, IF : Incomplete Fusion, SI : Slag Inclusion, U/C : Under Cut, BT : Burn Through, IC : Internal Concavity

Total Films : 4 X 10" = Sheets 4 X 15" = 10 Sheets 7 X 17" = Sheets

PT. Gintam Inspeksi Tehnik PT. Indoteknik Tjandra Utama PT. Pertamina Patra Niaga FT Sibolga
Ahli Radiography/Interpreter Reviewed / Witnessed by Witnessed / Approved by

Name : Vrengky Tampubolon Name : Name :


Date : 28 Maret 2023 Date : Date :

You might also like