than T5percent of the vertical height of the manufacturers' installation instructions.

vent.
Exception: Systems designed and sized as 802.6.2.5 All gas vents shall extend through
provided in Section 803.0 or in accordance the roof flashing, roof jack, or roof thimble
with other approved engineering methods. and terminate with a listed cap or listed roof
assembly. [NFPA 54:12.7.2 (6)l
Vents serving Category I fan assisted
appliances shall be installed in accordance 802-6.2.6 A gas vent shall terminate at least
with the appliance manufacturer's instruc- three (3) feet (0.9 m) above a forced air inlet
tions and Section 803.0 or other approved located within ten (10) feet (3.0 m). [NFPA
engineering methods. 5a:12.7.2 (7)l

802.6.2 A gas vent shall terminate in 802.6.3 Size of Gas Vents. Venting systems
accordance with one of the following: shall be sized and constructed in accordance
(1) Above the roof surface with a listed capor with Section 803.0 or other approved
listed roof assembly. Gas vents twelve (12) engineering methods and the gas vent and gas
inches (300 mm) in size or smaller with equipment manufacturers' instructions.
listed caps shall be permitted to be
terminated in accordance with Figure 82, 802.6.3.1 Gategory I Appliances. The
provided they are at least eight (8) feet (2.4 sizing of natural draft venting systems
m) from a vertical wall or similar obstruction. serving one or more listed appliances
All other gas vents shall terminate not less equipped with a dr:aft hood or appliances
than two (2) feet (0.6 m) above thb highest listed for use with Type B gas vent, installed
point where they pass through the roof and in a single story of a building, shall be in
at least two (2) feet (0.6 m) higher than any accordance with one of the following
portion of a building within ten (10) feet (3.1 methods.
m). (1) The provisions of Section 803.0.
(2) lndustrial gas utilization equipment as (2) Vents serving fan assisted combustion
provided in Section 802.2.4. system appliances, or combinations of
(3) Direct vent systems as provided in Section fan assisted combustion system and
802.2.5. draft hood equipped appliances shall be
(4) Equipment with integral vents as provided in sized in accordance with Section 803.0
Section 802.2.6. or other approved engineering
(5) Mechanica,l draft systems as provided in methods.
Section 802.3.4. (3) For sizing an individual gas vent for a
(6) Ventilating hoods and exhaust systems as single, draft hood equipped appliance,
provided in Section 802.3.5. the effective area of the vent connector
and the gas vent shall be not less than
802.6.2.1 A Type B or a Type L gas vent the area of the appliance draft hood
shall terminate at least five (5) feet (1.S m) outlet or greater than seven times the
in vertical height above the highest draft hood outlet area.
connected equipment draft hood or flue (4) For sizing a gas vent connected to two.
collar. appliances, with draft hoods, the
effective area of the vent shall be not
802.6.2.2 A Type BW gas vent shail less than'the area of the larger draft
terminate at least twelve (12) feet (3.7 m) in hood outlet plus 50 percent of the area
vertical height above the bottom of the wall of the smaller draft hood outlet or
furnace. greater than seven times the smaller
draft hood outlet area.
802.6.2.3 A gas vent extending through an (5) Approved engineering practices.
exterior wall shall not terminate adjacent to ,
the wall or below eaves or parapets, except ' 802.6.3.2 Gategory II, Category lll, and
as provided in Sections 802.2.5 and Category lV Appliances. The sizing of gas
802.3.4. vents for Category ll, Category lll, and
Category IV gas utilization equipment shail
802.6.2.4 Decorative shrouds shall not be be in accordance with the equipment
installed at the termination of gas vents manufacturers' instructions.
except where such shrouds are listed for
use with the specific gas venting system 802.6.3.3 Sizing. Chimney venting systems
and are installed in accordance with using mechanical draft shall be sized in

140 2012 PHILIPPINE MECHANICAL ENGINEERING CODE