CONTROL LOGIC FOR ENZYME SYSTEM

LIGNOCELLULOSIC BIOMASS PILOT PLANT


India Glycols Ltd., Kashipur

Logic for Enzyme Membrane system.

A. MF SYSTEM

1. Fix set points for Flow controller PID-607 & PID-608 as permeate and retentate flow
respectively.
2. Start the pump P-604 & P -607
3. Differential pressure difference of PT-607 & PT-608 and PT-608 & PT-610 needs to be
indicated in panel
4. Trans pressure difference of PT-607 & PT-610 needs to be indicated in panel.
5. If Actual permeate flowrate or retentate flowrate is less then set flowrate at PID-607
& PID-608 due to which there will be some changes in Trans pressure difference. In
that case it can be adjusted by throttling recycle line through AV-613 from the panel
whose flowrate can be manually seen through FM-607.
6. If Actual Permeate is more then set flowrate it is automatically adjusted by control
valve PID-607.
7. if Actual Retentate is more then set flowrate it is automatically adjusted by PID-608.
8. CIP of the membranes should be separate from CIP of the Tanks and its isolation
needs to be considerate.
9. CIP of Tanks, Pipes & Pumps should be either integrated with CIP logic of
Fermentation system or its in the scope of IGL.

B. UF SYSTEM

1. Fix set points for Flow controller PID-609 as retentate flow respectively.
2. Start the pump P-609 & P -610.
3. Trans pressure difference of PT-611 & PT-612 needs to be indicated in panel.
4. If Actual permeate flowrate or retentate flowrate is less then set flowrate at PID-607
due to which there will be some changes in Trans pressure difference. In that case it
can be adjusted by throttling recycle line through AV-624 from the panel whose
flowrate can be seen manually through FM-608.
5. If Actual Permeate is more then set flowrate it is adjusted by throttling manual valve
AV-621 from Panel whose flowrate is indicated on panel by FT-609.
6. if Actual Retentate is more then set flowrate it is automatically adjusted by PID-609.