Professional Documents
Culture Documents
Ex 303
Ex 303
Electrical Instrumentation
EX-303
Name:
Enrollment No:
Branch:
Semester:
Batch:
Institute:
INDEX
SIGNATURE &
S.NO. EXPERIMENT NAME DATE
REMARKS
2
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
EXPERIMENT NO. 1
OBJECT :- Calibration of wattmeter with the help of standard voltmeter and ammeter.
APPARATUS REQUIRED :-
CIRCUIT DIAGRAM :-
3
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
THEORY:-
WATTMETERS:-
In d.c. circuit power is given by the product of voltage (V) and current (I). However in case of a.c.
circuits it is not true. The real power in a.c. circuit is given by the expression V I Cosф , Where Cosф is
power factor. The measurement of real power in a.c. circuits is done by using an instrument which is
known as wattmeter.
A wattmeter comprises of two coils namely current coil and pressure coil. The current coil is
connected in series with the load and the pressure coil is connected across the load. The most
commonly used wattmeters are of dynamo-meter indicating type. The current coil is fixed and
pressure coil is moving coil. The working of this type of wattmeters depends up on the electro
magnetic forces exerted between the current coil and pressure coil.
Wattmeter are also available in triple range for voltages as well as for current e.g. 2.5/5A,
125/250/500V. There is only one scale on the wattmeter. For different combinations of ranges of
voltage s and currents, the ratings of wattmeter would be different. In order to take down the correct
reading from wattmeter a multiplying factor is to be used. The various value of multiplying factors
are mentioned on the meter. These are an accordance to the range used for voltages and currents.
Many a times it happens that the wattmeter gives –ve reading. In such a case the connections of
either the current coil or the pressure coil should be reversed. Then the wattmeter will start reading
+ve . the readings so indicated should be recorded with a –ve sign.
The terminals of current coil are marked as M – L abbreviation for mains and load. The terminals of
pressure coil are marked V1 and V2. the terminals M of the current coil and V1 of the pressure coil are
joined together, and junction is known as common terminal.
The connections of a wattmeter in an a.c. circuit are made as shown in fig. below
4
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
The current coil of wattmeter has a low resistance and hence the symbol is inductive. The pressure
coil of wattmeter has high resistance and hence the symbol is resistive.
PROCEDURE :-
(A) Connect the voltmeter, ammeter and wattmeter to the load through single phase autotransformer
according to the circuit diagram and setup.1 phase auto transformer to zero position.
(B) Switch on the single phase a.c. supply and adjust the auto transformer till a suitable voltage .At this
stage note down all the readings of equipments.
(C) Vary or increase the voltage by auto transformer and note the various reading and calculate the
power by wattmeter and voltmeter, ammeter and then find out limiting error for wattmeter.
OBSERVATIONS TABLE :-
1.
2.
3.
4.
CALCULATION:-
Actual Value
5
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
RESULT:-
The power measure in the circuit is shown in test and actual value calculated by voltmeter reading
into ammeter reading and there corresponding limiting error (%) in last column.
REPORT:-
PRECAUTION :-
6
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
EXPERIMENT NO. 2
OBJECT: -
Measurement of power in three phase A.C. circuit by Two Wattmeter method and determine :-
Active and Reactive Power.
Power Factor of The Load.
Limiting Error For Power Measurement.
APPARATUS REQUIRED :-
CIRCUIT DIAGRAM :-
7
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
THEORY:-
Two wattmeter method employed to measurement power in three phase star or delta connected
balanced or unbalanced load. The current coil of the wattmeters are connected in any two line
(R,Y)and potential coil of each wattmeters is joined across the same line and third phase(B)Which
left(Common to both wattmeter) ……. of the power measurement by two wattmeters W1 and W2 is
equal to the power measured by three phase load.
PROCEDURE :-
Connect the voltmeter ,Ammeter, and Wattmeters to the load through three phase auto-
transformer as shown in fig. and reset the auto-transformer at zero position.
Switch on the three phase supply and adjust the auto-transformer till suitable voltage. Note
down readings of Wattmeters, Voltmeters, and Ammeter.
]vary the voltage by auto-transformer and noted various readings of Wattmeters, Voltmeter,
and Ammeter.
After taking observation switch of the power supply and disconnect all the equipment and
remove lead wire.
OBSERVATION TABLE :-
1.
2.
3.
4.
5.
8
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
CALCULATION:-
RESULT:-
[Average of Reading]
PRECAUTION:-
9
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
EXPERIMENT NO. 3
APPARATUS REQUIRED: -
Multi Meter
Auto – Transformer
Rheostat (0-6 Ω)
Rheostat (0-252 Ω)
Triple Power Supply
THEORY:-
An electronic multi meter is one of the most versatile instrument which capable of measurement of
A.C. & D.C. Current, Voltage, and Resistance. All quantities other than D.C. Voltage is first converted
into an equivalent. D.C. Voltage by some device. It consists of following element:-
A balance bridge
D.C. amplifier and PMMC indicating instrument
A range switch which is an attenuator to limit the value of input Voltage to desire
value
A function switches to select various measurement function of the instrument like
Current, Voltage and Resistance.
An analog to digital converter which converts the receiving analog quantities into
digital from which are then display on the screen i.e. display unit.
PROCEDURE:-
To measure A.C. Voltage by Multi – Meter first of all we take the Auto – Transformer and connect to
Multi – Meter and adjust the Multi – Meter to take reading of A.C. Voltage. Note down the supply
Voltage reading and corresponding the Multi – Meter reading and so on.
To measure D.C. Voltage by Multi – Meter first of all we connect the Multi – Meter with triple Power
supply. Note down the D.C. supply voltage reading and corresponding the Multi – Meter reading
increase the D.C. supply Voltage by triple power supply and note down the D.C. supply Voltage
reading and corresponding the Multi – Meter reading and so on.
10
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
To measurement of resistance of rheostats by Multi–Meter. First Of all we note down the total
resistance offered by of rheostats. Than to take different reading by varying the rheostats by Multi–
Meter reading.
CALCULATION :-
OBSERVATION TABLE :-
1.
2.
3.
4.
11
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
1.
2.
3.
4.
MEASUREMENT OF RESISTANCE :-
1.
2.
3.
4.
COMMENTS :-
The reading of the supply Voltage and Measure Voltage by Multi m- Meter are Different
because the least count of Transformer is 2 Volt.
Also due to Voltage fluctuation reading does not remain constant.
PRECAUTION :-
12
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
EXPERIMENT NO. 4
Osaw portable wheat stone bridge ratio multipliers resistance dials, galvanometer,
galvanometer selector, galvanometer sensitivity control list terminals, battery key,
galvanometer key battery selector, battery terminals, galvanometer terminals, earth
terminals, operation switches, battery compartment.
CIRCUIT DIAGRAM:-
13
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
14
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
OPERATING PRINCIPAL :-
It is the best and commonest method to measure resistance and is first described by Christi’s
1833. However it did not become widely known until Wheatstone called attention to Christi’s
work in 1843 and wheat stone’s name has been associated with the network in its
subsequent general use.
P & Q are two known fixed resistances, R being a known variable resistance and S is the
unknown resistance. G is the sensitive galvanometer whose sensitivity may be controlled by a
shunt across its terminals. B is the battery of two or three cells. KB and KA are press keys fitted
with insulating press button so that it doesn’t come in contact with metal parts of the circuit,
thus introducing thermo e.m.f The battery keys KB should be closed first followed by closing
of KG after a short interval. This avoids a sudden galvanometer deflection due to self-induced
e.m.f. When unknown resistance S has appreciable self inductance at balance obtained by
adjustment of R the same current flow in both the arm P & Q. Since galvanometer takes no
current and the same current I2 flow also in the arms R & S.
Thus,
I 1Q = I2R …………………………….(1)
I 1P = I2S …………………………….(2)
i.e.
S = R(P/Q)
From which S is found in terms of P, Q and R the arms of P and Q are the ratio arms of the
bridge and ratio P/Q may be varied as required to increase the range.
15
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
OBSERVATION TABLE:-
1.
2.
3.
4.
OPERATING INSTRUCTION:-
Press B & G keys and adjust the four decade resistance dials on the panels unit the
galvanometer pointer reaches zero. Set the galvanometer sensitivity a control to direct
position and repeat step 6 to obtain final balance point position.
Note reading of four decade dial and the ratio Multiplier. Thus, the unknown resistance can
be calculated as follow:-
16
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
Internal 3 V batteries may not give good resolution for high resistance measurement. High
voltage battery or D.C. source may be used
Connect the external battery or a D.C. source to the battery terminal B –ve and B +ve.
Set the battery selector to extent position
Proceed as usual
Connect the galvanometer through a series resistance box to the terminals G –ve and G
+ve.
set the galvanometer selector to extent position
Observe all the prequation required for the galvanometer for used.
Galvanometer series resistance may be gradually decrease to zero for obtaining final balance
points.
Questions
1. What problems can you foresee with using a Wheatstone bridge for resistance
measurements? What are the principle uncertainties?
2. What limits your ability to make precise measurements in this experiment?
17
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
EXPERIMENT NO. 5
Stop Watch.
Theory:-
Energy meter is an instrument which measure electrical energy. It is also Known as watt-hour
(wh) meter. It is an integrating meter . There are several type of energy meters. Single –phase
induction type energy meters are very commonly used to measure electrical energy
consumed in domestic and commercial installation. Electrical energy is measured in Kilo
watt-hours (kwh) by these energy meters.
Construction:-
A single –phase induction type energy meter consists of Driving system, Moving system,
Braking system and Registration system . Each of the systems is briefly explained below:
Driving System:-
This system of the energy meter consists of two silicon steel laminated
electromagnets M1 and M2 as shown in fig. 2.35. The electromagnet M2 is called the
shunt magnet. The series magnet M1 carries a coil consisting of a few turns of thick
wire. This coil is called the current coil (CC) and it is connected in series with the
circuit. The load current flows through this coil. The shunt magnet M2 carries a coil
consisting of many turns of thin wire. This coil is called the voltage coil (VC) and is
connected across the supply. It carries a current proportional to the supply voltage.
Short-circuited copper bends are provided on the lower part of the central limb
of the shunt magnet. By adjusting the position of these loops the shunt magnet flux
can be made to lag behind the supply voltage exactly by 900 .These copper bands are
called power factor compensator (PFC).
18
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
A copper shading band is provided on each outer limb of the shunt magnet (FC1
and FC2). These bands provide frictional compensation.
Moving System:-
The moving system consists of a thin aluminum disc mounted on a spindle and is placed in
the air gap between the series and shunt magnets. It cuts the fluxes of both the magnets.
Forces are provided by the fluxes of each of the magnets with the eddy current induced in
the disc by the flux of the other magnet. Both these forces act on the disc. These two forces
constitute a deflecting torque.
Braking System:-
The braking system consists of a permanent magnet called brake magnet. It is placed near
the edge of the aluminum disc. As the disc rotates in the field of the brake magnet, eddy
currents are induced in it. These eddy currents react with the flux and exert a torque. This
torque acts in a direction so that it opposes the motion of disc. The braking torque is
19
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
Registering System:-
The disc spindle is connected to a counting mechanism. This mechanism records a number
which is proportional to the number of revolutions of the disc. The counter is calibrated to
indicate the energy consumed directly in Kilowatt-hours (kwh).
In this experiment the purpose is to calibrate the energy meter. This means we wish to find
out the error/correction in the energy meter readings. This calibration is possible only if some
other source /instrument, to know the correct readings is available ; Here the voltmeter,
ammeter and the stop watch are assumed to be correct viz, these are taken as reference.
Energy meter is now, to be calibrated with respect to voltmeter, ammeter and stopwatch.
We would perform this experiment by supplying the electric energy to a load. This energy
would be measured by two means i.e., by energy meter and by using combination of
voltmeter, ammeter and stop watch
= kWh
= kWh
The time ‘t’ is measured in seconds for a given number of revolution (say 20) of the disc of
the energy meter. Induction type energy meters have a constant marked on the meters. It is
in terms of number of revolutions per kWh. Let us say it is 1200 revolutions per kWh. Then
the energy recorded by the energy meter is given by 20/1200 kWh. The error in the
instrument can be calculated as under.
A graph of error vs the load current is plotted. This is also known as the calibration curve of
the energy meter.
20
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
Procedure:-
The experiment for calibration of energy meter should be conducted in the following steps:
1. Connect the circuit as shown in Fig. 2.36, and apply constant a.c. voltage.
2. Switch on one of the loads.
3. Records the time taken for 20 revolution of the disc with the help of stop watch.
4. Take voltmeter and ammeter readings.
5. Repeat for more number of readings.
6. Record the reading as per Table 2.13
7. Dial Test Adjust the load resistance so that a current of 8-10 A flows in the circuit. Allow this
current to flow for half an hour. Take voltmeter and ammeter readings at regular intervals say
after each 5 minutes. Note the dial reading in the beginning of the test and end of half an hour.
The difference of the two reading gives the energy indicated by energy meter. Calculate the
actual value of energy consumed by using
V I * (0.5)
E = ---------------- kW hrs.
1000
Calculate the error % using
21
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
The observation taken during the experiment can be recorded as shown in Table 2.13
1.
2.
Precaution:-
22
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
EXPERIMENT NO. 6
Apparatus Required:-
Theory:-
Kelvin Double Bridge (KDB) is suitable for measurement of low resistance in the range 0.0001
ohm to 110 ohm.
Main dial:-
Slide wire:-
100 division of slide wire are equal to 0.1 ohm. Key K2 is provided for
Contacts.
Galvanometer Terminals:-
Battery:-
Terminals for battery are provided with key. A 2-6 volts battery is used.
Test Sample:-
23
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
Working:-
Connect a sensitive Galvanometer between terminals of ratio box marked “1”. Connect a
battery of 6 volts between battery terminals. Connect the unknown Resistance between C1P1
and C2P2. (if resistance is of two terminals than short C1with P1 and C2 with P2). Now press
battery key and check the slide of deflection of galvanometer. Keeping slide wire key at “O”
press both battery key and slide wire key. Check the deflection of galvanometer. Move the
key along slide wire and check if galvanometer comes at balance point at any point of slide
wire. If not than change main dial to “1” and repeat the process till you find null point . If still
you don’t find null point than change the position of Galvanometer at ratio box one terminal
ahead OR back and repeat the process.
24
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
Calculation:
Precautions:-
25
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
EXPERIMENT NO. 7
Object: Study and Measurement of Insulation resistance with the help of Megger
Theory: Megger has become the generic description for a high voltage, low current insulation tester. The
word is short for megohm-meter. Although any Ohmmeter or Multimeter may appear capable of
similar measurements, only a Megger type instrument can test the quality of the insulation at or
above its operating voltage. Choice of test voltage is normally determined by the operating
voltage of the circuit under test; usually twice the operating voltage is sufficient. Two basic
insulation tests are possible: Insulation to ground and insulation between conductors.
Good insulation has high resistance; poor insulation, relatively low resistance. The actual
resistance values can be higher or lower, depending upon such factors as the temperature or
moisture content of the insulation (resistance decreases in temperature or moisture). Megger
insulation tester measures insulation resistance directly in ohms or meg-ohms. For good
insulation, the resistance usually reads in the meg-ohm range. The Megger insulation tester is
essentially a high-range resistance meter (ohmmeter) with a built-in direct-current generator.
This meter is of special construction with both current and voltage coils, enabling true ohms to be
read directly, independent of the actual voltage applied. This method is nondestructive; that is, it
does not cause deterioration of the insulation.
26
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
The generator can be hand-cranked or line-operated to develop a high DC voltage which causes a
small current through and over surfaces of the insulation being tested (Fig. 1). This current
(usually at an applied voltage of 500 volts or more) is measured by the ohmmeter, which has an
indicating scale. Fig. 2 shows a typical scale, which reads increasing resistance values from left up
to infinity, or a resistance too high to be measured.
Current that starts out high and drops after the insulation has been charged to full
voltage (much like water flow in a garden hose when you first turn on the spigot).
2. Absorption Current
A small essentially steady current both through and over the insulation.
27
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
EXPERIMENT N O: 8
Object: - To measure active and reactive power in three phase balanced load by one wattmeter method.
PRIOR CONCEPTS:
NEW CONCEPTS
1. Three single phase wattmeter - This method is used for a star connected, 4 wire system, balanced or
unbalanced load.
2. Two 1 phase wattmeter - This method is suitable for 3 phase, 3 wire system and widely used. It is
applicable to both delta and star system, balanced or unbalanced load.
3. One single phase wattmeter - This method is applicable to balanced load only.
4. One 3 phase wattmeter - 3 phase wattmeter consists of two or three wattmeter elements mounted
together in one case with moving coils mounted on the same spindle
Proposition 2 :
One wattmeter method for measurement of active power is for 3 phase balanced load only. The current coil
of the wattmeter is connected in one of the lines and one end of pressure coil is connected to the same line.
The readings are taken by connecting other terminal of pressure coil alternately to other 2 lines. The sum of
the two readings gives active power.
28
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
Proposition 3 :
It is often convenient and even essential that reactive power be measured. For example in load monitoring,
such a measurement gives the operator the information of the nature of load. Also the reactive power serves
as a check on power factor measurements, since ratio of reactive and active power is tan f = Q/P Where Q &
P are the reactive and active power respectively.
Proposition 4 :
One wattmeter method for measurement of reactive power is for 3 phase balanced load only. The current
coil of the wattmeter is connected in one of the lines. The pressure coil is connected across two lines. The
reactive power is Ö3 times the wattmeter reading.
29
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
LEARNING OBJECTIVES:
Intellectual Skills:
CIRCUIT DIAGRAM :
Part A
(Students shall draw the circuit diagram in the space provided. The diagram shall include the following
things)
30
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
Part B
(Students shall draw the circuit diagram in the space provided. The diagram shall include the following
things.)
Apparatus Required:-
• A. C. Ammeter (0 - 5A)
• A. C. Voltmeter (0 - 300V)
STEPWISE PROCEDURE :
Part A
31
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
Part B
Observations :
32
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
QUESTIONS :
2. Active power in 3 phase balanced load circuit with one wattmeter method is to be measured.Draw phasor
diagram for the same.
5. A single phase wattmeter is used for measurement of reactive power in 3 phase balanced load. If the total
reactive power is 173kvar calculate the reading of wattmeter.
6. Reactive power in 3 phase balanced load circuit with one wattmeter method is to be measured. Draw
phasor diagram for the same.
7. Suggest suitable method to measure power consumed by a three phase induction motor used for pumping
the water.
8. A wattmeter has a current coil resistance of 0.05W and a pressure coil resistance of 10KΩ. The load current
is 10A and load voltage is 230V. The power taken by the load is 130W. Show two types of wattmeter
connections & the reading of wattmeter in each case.
33
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
EXPERIMENT N O: 9
Object: Calibration of LPF Wattmeter by Phantom Loading
Testing and Calibration of the given LPF wattmeter by using a sub-standard Wattmeter by
phantom loading method.
APPARATUS :
7 Connecting wires 1s
C IRCUIT D IAGRAM:
34
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
THEORY:
Electrodynamometer type wattmeter has two coils connected in different circuits for measurement of
power. The fixed coils or “field coils” are connected in series with the load and so carry the current in th e
circuit. The fixed coils, therefore, form the “current coil” or simply C.C of the wattmeter.
The moving coil is connected across the voltage and, therefore, carries a current proportional to the
voltage. A high non-inductive resistance is connected in series with the moving coil to limit
the current to a small value. Since the moving coil carries a current proportional to the voltage, it is
called the ‘pressure coil” or “voltage coil” or simply called P.C. of the wattmeter. Both fixed and moving
coils are air cored. The voltage rating of the wattmeter is limited to about 600 V by the power
requirements of the voltage circuit since most of the power is absorbed by the resistance in series with
the moving coil and considerable heat is generated. For higher voltages, the pressure coil circuit is
designed for 110V, and a potential transformer is used to step down the voltage.
The deflection is directly proportional to the power being measured and the scale is essentially uniform
over the range in which (dM/dӨ ) is constant. By suitable design, the mutual inductance between fixed
and moving coil and be made to vary linearly with angle over a range of 40 o to 50o on either side of zero
mutual inductance position. On lagging loads the wattmeter will read high, as the effect of the inductance
of the pressure coil circuit is to bring the pressure coil current more nearly into phase with the load
current than would be the case if this inductance were zero. Very serious errors may b e
introduced by pressure coil inductance at low power factors unless special precautions are taken.
Many wattcmeters are compensated for errors caused by inductance of pressure coil by means of a
capacitor connected in parallel with a portion of multiplier (series resistance).Measurement of power in
circuits having low power factor by ordinary electrodynamometer wattmeter is difficult and inaccurate
because:
i. The deflecting torque on the moving system is small (owing to low power factor) even when the
current and pressure coils are fully excited;
ii. Errors introduced because of inductance of pressure coil tend to be large at low power factors.
35
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
Special features are incorporated in an electrodynamometer wattmeter to make it a low power factor type
of wattmeter. These features are discussed in details below:
1. Pressure Coil Current. The pressure coil circuit is designed to have a low value of resistance, so that the
current, flowing through it, is increased to give an increased operating torque. The pressure coil current in a
low power factor wattmeter may be as much as 10 times the value employed for high power factor
wattmeter.
2. Compensation for Pressure coil Current. The power being measured in a low power factor circuit is small
and current is high on account of low power factor. It is absolutely necessary to compensate for the pressure
coil current in low power factor wattmeter.
When the current rating of meter under test is high a test with actual loading arrangements would involve a
considerable waste of power. In order to avoid this Phantom loading as Fictitious loading is done. Phantom
loading consists of supplying the pressure coil from a circuit of required normal voltage and the current coil
from a separate low voltage supply. It is possible to circulate the rated current through the current coil with a
low voltage supply as the impedance of this circuit is very low, with this arrangement. The total power
supplied for the test is that due to the small pressure coil current at normal voltage, plus that due to
thecurrent circuit current applied at low voltage. The total power therefore, required for testing the meter
with phantom loading is comparatively small.
P ROCEDURE:
2. With variac ‘I’ and ‘II’ in minimum position and the rheostat in minimum position, close the DPST-I switch
to connect the supply-I.
3. Vary the variac-I gradually to apply the rated voltage (230V). to pressure coils of both p.f meter and
wattmeter.
4. Close the DPST-II switch and vary the variac-II to adjust a suitable current of (1A or 2A) in the current coils
of LPF wattmeter and p.f meter. as indicated by ammeter. Note down the readings of all the instruments
5. Now vary the current (up to 4A) in current coils of both wattmeter and p.f meter in steps using single
phase variac & rheostat and note down readings for each step. Tabulate the readings.
6. Bring the rheostat to minimum position, vary the variac-II and variac-I to minimum position and open the
DPST switches.
36
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
OBSERVATION TABLE:
S.No Voltmeter Ammeter P.F meter Wattmeter True power % Error %Correction
Reading V Reading, I reading Reading (S2) (S1)
(S1-S2) /S1 (S2-S1) /S1
(volts) (Amps) (Watts)
VI Cosø (Watts)
C ALCULATIONS :
GRAPH:
% Error
Load Current
RESULT:
The LPF wattmeter is calibrated using phantom loading and calibration curve is plotted for the given
wattmeter
37
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
P RECAUTIONS:
4 Vary the variac such that the current and voltage are within the rated value
7 If any wattmeter reads, reading, change either current coil or pressure coil connections.
11 Take proper care, such that the ammeter reading, should not exceed the current rating of LPF
wattmeter.
38
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
QUESTIONS:
3. Why are the LPF wattmeter designed to have a smaller controlling torque?
9. What are the different methods used for measurement for 3-phase power?
39
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
EXPERIMENT NO: 10
OBJECT:
APPARATUS REQUIRED:
THEORY:
A dynamometer three phase wattmeter consist of two separate wattmeter movements mounted
together in one case with the two moving coils mounted on the spindle. The arrangement is shown in
figure –
A current coil together with its pressure coil is known as one element. Therefore a three phase
wattmeter has two elements. The connection of two elements of three phase wattmeter is the same as
that for two wattmeter method using two single phase wattmeter. The torque on each element
proportional to the power being measured by it. The total torque deflecting the moving system is the
sum of the deflecting torque of two elements.
Hence the total deflecting torque on moving system is proportional to the total power. In order that
three phase wattmeter should read correctly, there should not be any mutual interference between the
two elements. A laminated iron shield may be placed between the two elements to eliminate the
mutual effects.
40
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
Circuit Diagram-
41
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
Observation table-
Calculations-
Precautions:
4. Don’t switch on the supply without verifying the circuit by lab in charge.
42
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
Lab Quiz:
43
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
A. 0
B. 1600Watt
C. 800Watt
D. 400Watt
Ans: C
[7] The probes of a non-isolated, two channel oscilloscope are clipped to points A,B and C in the circuit of
the adjacent figure. Vin is a square wave of a suitable low frequency. The display on Ch1 and Ch2 are
as shown on the right. Then the "signal" and "ground" probes S1, G1 and S2, G2 of Ch1 and Ch2
respectively are connected to points [GATE 2007]
A. A, B, C, A
B. A, B, C, B
C. C, B, A, B
D. B, A, B, C
Ans: B
44
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
[8] An analog voltmeter uses external multiplier settings. With a multiplier setting of 20kΩ, it reads 440V
and-with a multiplier setting of 80kΩ it reads 352V. For a multiplier setting of 40kΩ,voltmeter
reads [GATE2012]
A. 371V
B. 383V
C. 394V
D. 406V
Ans: D
[12] A transfer instrument employed in the standardization of a polar type ac potentiometer is [Gate 1997]
(a) An electrostatic instrument
(b) A thermal instrument
(c) A dynamometer instrument
(d) A moving coil instrument
Ans: C
[13] Transformers used in conjunction with measuring instruments for measuring purposes are called
(a) Measuring transformers
(b) transformer meters
(c) power transformers
(d) instrument transformers
(e) pulse transformers.
45
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
Ans: d
[14] Swamping resistance is used in moving coil instruments to reduce error due to
(a) thermal EMF
(b) temperature
(c) power taken by the instrument
(d) galvanometer sensitivity.
Ans: b
[17] The insulation resistance of a transformer winding can be easily measured with
(a) Wheatstone bridge
(b) megger
(c) Kelvin bridge
(d) voltmeter
Ans: b
[19] Which of the following meters are not used on D.C. circuits
(a) Mercury motor meters
(b) Commutator motor meters
(c) Induction meters
(d) None of the above
Ans: c
46
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
[22] _____ instruments are those which measure the total quantity of electricity delivered in a particular
time.
(a) Absolute
(b) Indicating
(c) Recording
(d) Integrating
Ans: d
[23] What are the effects of moving a closed wire loop through a magnetic field?
(a) A voltage is induced in the wire.
(b) A current is induced in the wire.
(c) The polarity across the wire depends on the direction of motion.
(d) All of the above
Ans: d
[24] Which of the following instruments indicate the instantaneous value of the electrical quantity being
measured at the time at which it is being measured ?
(a) Absolute instruments
(b) Indicating instruments
(c) Recording instruments
(d) Integrating instruments
ANSWER : Indicating instruments
47
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
[26] For handling greater currents induction wattmeters are used in conjunction with
(a) potential transformers
(b) current transformers
(c) power transformers
(d) either of the above
ANSWER : current transformers
[27] A moving-coil permanent-magnet instrument can be used as _____ by using a low resistance shunt.
(a) ammeter
(b) voltmeter
(c) flux-meter
(d) ballistic galvanometer
ANSWER : ammeter
[30] Most common form of A.C. meters met with in every day domestic and industrial installations are
(a) mercury motor meters
(b) commutator motor meters
(c) induction type single phase energy meters
(d) all of the above
ANSWER : : induction type single phase energy meters
48
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
[34] 16.Induction type single phase energy meters measure electric energy in
(a) kW
(b) Wh
(c) kWh
(d) VAR
ANSWER : : kWh
49
Name of Laboratory : Electrical Instrumentation
Lab Subject Code : EX 303
Name of Department : Electrical Engineering
[39] A _____ device prevents the oscillation of the moving system and enables the latter to reach its final
position quickly
(a) deflecting
(b) controlling
(c) damping
(d) any of the above
ANSWER : : damping
[40] is an instrument which measures the insulation resistance of an electric circuit relative to earth and
one another,
(a) Tangent galvanometer
(b) Meggar
(c) Current transformer
(d) None of the above
ANSWER : : Meggar
[41] An ammeter is a
(a) secondary instrument
(b) absolute instrument
(c) recording instrument
(d) integrating instrument
ANSWER : : secondary instrument
50