You are on page 1of 1

INFRARED THERMOGRAPHY REPORT

PT. MAXXIS INTERNATIONAL INDONESIA

VISUAL IMAGE PHOTO No. 81


DATE 15 AGUSTUS 2018
LOCATION 6PS GEDUNG 120
OBJECT PANEL 6MP2-1

EQUIPMENT MCCB

WITNESS Bp. RIZKI ADITAMA

Temperature Data ( ° C )
TEMPERATURE MAXIMUM 30.5
TEMPERATURE REFERENCE 30.4

TEMP.MAKS.YANG DIIJINKAN 70.0

KENAIKAN DARI TEMP.MAKS -

Classification Of Rise in Temperature


From Permitted Maximum Temperature
NORMAL DATA (≤ MAX. TEMP.) A
NEED ATTENTION (≥1 – 10 °C) B
REPAIR DURING NEXT MAINT.PERIOD (≥11 - 20°C) C
REPAIR AS SOON AS POSSIBLE (≥21 – 40 °C) D
REPAIR IMMEDIATELY (≥ 40 °C) E
Probable Cause
THERMAL IMAGE FAULTY CONNECTION (LOOSE OR DIRTY)
OVERLOADED
UNBALANCED LOAD
INTERNAL COMPONENT / PARTS FAILURE
ELECTROMAGNETIC INDUCTION
NORMAL OPERATING TEMPERATURE X
Comment / Suggestion
TEMPERATUR NORMAL.

PHOTO UNTUK DATA MONITORING.

INSPEKSI ULANG : 6 – 12 BULAN MENDATANG.

CATATAN PENGAWAS LAPANGAN :

PT. TRUNOJOYO SUMBER LISTRINDO – Infrared Thermography Div. 81