You are on page 1of 4

1/11/23, 4:06 PM Gmail - Material Approval Request 33 - Air Condition System from Metropolitan Technologies (Pvt) Ltd

Lahiru PM <lahirupm.dc@gmail.com>

Material Approval Request 33 - Air Condition System from Metropolitan


Technologies (Pvt) Ltd
Lahiru PM <lahirupm.dc@gmail.com> Thu, Jan 5, 2023 at 12:37 PM
To: Mohamed Infiyaz HYDER <mohamedh@unops.org>
Cc: Gamini KALUPE RANAWEERA <gaminik@unops.org>, Himath Mithsara Sirimevan WERADUWA
<himathw@unops.org>, darinton npqs <npqs.darinton@gmail.com>

Dear Mr.Infiyaz ,

We  will be able to arrange a field visit for the following locations where the Samsung VRF systems are functioning.
Let us know your convenient time and date in advance to arrange a visit .

1. Siyapatha Finance at Rajagiriya 


2. Prudential Shipping line Office building at Rajagiriya 

And also attached amended equipment schedule here with( proposed next higher capacity for 2nd floor business
center and upgrated Outdoor unit capacity also in order to maintain good performance in the system)

Best Regards ,

On Fri, Dec 30, 2022 at 10:12 AM Mohamed Infiyaz HYDER <mohamedh@unops.org> wrote:
Dear Mr.Ranawaka,
The proposed products are acceptable
Can you please take action on the below points.

1. Please ensure the proposed capacity is equal or slightly higher than the required capacity of the AC
equipment. I noticed this in the Business Centre in 2F.
2. Prefer to visit a few installations of the proposed products to see their functional performance.

BR!

Infiyaz Hyder GMICE| Senior Associate Civil Engineer | Operational Hub - Bangladesh, Bhutan, India,
Nepal, Pakistan I SAMCO Sri Lanka | AR BDMCO | Colombo, Sri Lanka | Tel: +94 7135 03812 |
www.unops.org 
Keep up-to-date with UNOPS. Follow us on Facebook, LinkedIn, Twitter, Instagram, YouTube.
Subscribe to our external newsletter in English, French or Spanish. 

---------- Forwarded message ---------


From: Gamini KALUPE RANAWEERA <gaminik@unops.org>
Date: Fri, Dec 30, 2022 at 9:36 AM
Subject: Re: Material Approval Request 33 - Air Condition System from Metropolitan Technologies (Pvt) Ltd
To: Mohamed Infiyaz HYDER <mohamedh@unops.org>
Cc: Himath Mithsara Sirimevan WERADUWA <himathw@unops.org>

Dear all,

https://mail.google.com/mail/u/1/?ik=8d17925756&view=pt&search=all&permmsgid=msg-a%3Ar5609653509308387174&dsqt=1&simpl=msg-a%… 1/4
1/11/23, 4:06 PM Gmail - Material Approval Request 33 - Air Condition System from Metropolitan Technologies (Pvt) Ltd

Good morning!
The proposed products are acceptable. However, pl ensure the proposed capacity is equal or slightly higher than
the required capacity of the AC equipment. I noticed this in the Business Centre in 2F.
Additionally, I prefer to visit few installations of the proposed products to see their functional performance.
Hope the details are helpful.
BR
K.G. Ranaweera

On Thu, Dec 29, 2022 at 8:00 PM Mohamed Infiyaz HYDER <mohamedh@unops.org> wrote:
Dear Mr.Ranaweera,
The AC supplier has forwarded responses to your concerns.
I hope everything is OK to finalize and sign off the approval now.
Can you please have a quick look and confirm the acceptance so that the final version can be compiled ?
Thanks & BR!

Infiyaz Hyder GMICE| Senior Associate Civil Engineer | Operational Hub - Bangladesh, Bhutan, India,
Nepal, Pakistan I SAMCO Sri Lanka | AR BDMCO | Colombo, Sri Lanka | Tel: +94 7135 03812 |
www.unops.org 
Keep up-to-date with UNOPS. Follow us on Facebook, LinkedIn, Twitter, Instagram, YouTube.
Subscribe to our external newsletter in English, French or Spanish. 

---------- Forwarded message ---------


From: Lahiru PM <lahirupm.dc@gmail.com>
Date: Thu, Dec 29, 2022 at 7:44 PM
Subject: Fwd: Material Approval Request 33 - Air Condition System from Metropolitan Technologies (Pvt) Ltd
To: Mohamed Infiyaz HYDER <mohamedh@unops.org>
Cc: Himath Mithsara Sirimevan WERADUWA <himathw@unops.org>, Shanmuganathan SYLEASE
<shanmuganathans@unops.org>, <dinushapc.darintonc@gmail.com>, darinton npqs
<npqs.darinton@gmail.com>

Dear Mr. Infiyaz,


Please find the trailing email from the Metropolitan Technologies (Pvt) Ltd for  review and approval. 
I will submit the complete document according to the confirmation for the AC system for final approval.
Hope this will meet your requirement.
Thank You.

---------- Forwarded message ---------


From: Ravi Buddika <ravibuddika88@gmail.com>
Date: Thu, Dec 29, 2022 at 4:20 PM
Subject: Re: Material Approval Request 33 - Air Condition System from Metropolitan Technologies (Pvt) Ltd
To: Lahiru PM <lahirupm.dc@gmail.com>
Cc: rislan risvi <rislanqs.darintonc@gmail.com>

Dear Mr. Lahiru ,

Please find attached amended equipment schedule sheet and here with confirming that we will provide 2Nos split
units having capacity of 12000 Btu ( Haier Brand) operated with R410Gas .

Best Regards,
Ravi

On Wed, Dec 28, 2022 at 10:22 AM Lahiru PM <lahirupm.dc@gmail.com> wrote:


https://mail.google.com/mail/u/1/?ik=8d17925756&view=pt&search=all&permmsgid=msg-a%3Ar5609653509308387174&dsqt=1&simpl=msg-a%… 2/4
1/11/23, 4:06 PM Gmail - Material Approval Request 33 - Air Condition System from Metropolitan Technologies (Pvt) Ltd

Dear Mr. Ravi,


Please find the trailing email for your reference and comments.
Your immediate response in this regard is highly appreciated.
Thank You.

---------- Forwarded message ---------


From: Mohamed Infiyaz HYDER <mohamedh@unops.org>
Date: Wed, Dec 28, 2022 at 10:12 AM
Subject: Re: Material Approval Request 33 - Air Condition System from Metropolitan Technologies (Pvt) Ltd
To: darinton npqs <npqs.darinton@gmail.com>
Cc: Himath Mithsara Sirimevan WERADUWA <himathw@unops.org>, <lahirupm.dc@gmail.com>,
<shanmuganathans@unops.org>, <dinushapc.darintonc@gmail.com>, Gamini KALUPE RANAWEERA
<gaminik@unops.org>

Dear Mr.Ranawaka,
Given the super urgency of this requirement, the UNOPS consultant has quickly reviewed the submission and
forwarded the below comments.

"The proposal can be technically accepted. However, please include and clarify the following points.
1. Country of origin of all proposed equipment and materials have to be defined.
2. The proposed Split type AC units are of make VOLTAS with higher capacity. It is preferred to have the same
brand for all units with suitable capacity (VRF & Split type) to ensure easy maintenance.
3. It is better to have a single Refrigerant for all units (for the maintenance purpose).
4. It is better to include a table indicating all MVAC equipment with locations for installation etc. for easy
identification.
5. The refrigerant piping should be of Hard Drawn Copper tubes with fittings recommended by the respective
manufacturer."

Please attend to the above comments and submit the final version as soon as possible.
If you have any concerns, please reach out prior to finalizing the document.
BR!

Infiyaz Hyder GMICE| Senior Associate Civil Engineer | Operational Hub - Bangladesh, Bhutan, India,
Nepal, Pakistan I SAMCO Sri Lanka | AR BDMCO | Colombo, Sri Lanka | Tel: +94 7135 03812 |
www.unops.org 
Keep up-to-date with UNOPS. Follow us on Facebook, LinkedIn, Twitter, Instagram, YouTube.
Subscribe to our external newsletter in English, French or Spanish. 

On Tue, Dec 27, 2022 at 12:40 PM darinton npqs <npqs.darinton@gmail.com> wrote:


Dear Mr. Himath,
We are submitting herewith the Air Condition System from Metropolitan Technologies (Pvt) Ltd for your
review and approval as per your request made for  another supplier.
Please find the attachments for the approval request and relevant details. 
Your early response in this matter will be highly appreciated.
Thank You.

Lahiru Ranawaka
Project Manager
Construction of New Building for NPQS in Sea Port

https://mail.google.com/mail/u/1/?ik=8d17925756&view=pt&search=all&permmsgid=msg-a%3Ar5609653509308387174&dsqt=1&simpl=msg-a%… 3/4
1/11/23, 4:06 PM Gmail - Material Approval Request 33 - Air Condition System from Metropolitan Technologies (Pvt) Ltd

--
Best Regards
D.R.B.L.R.Ranawaka,
B.Sc.Eng (Hons), MIE(SL),
Project Manager,
Construction of New Building for NPQS in Sea Port
Darinton Construction (Pvt) Ltd
Mobile:- 0702764860,0714334907

--
Best Regards
D.R.B.L.R.Ranawaka,
B.Sc.Eng (Hons), MIE(SL),
Project Manager,
Construction of New Building for NPQS in Sea Port
Darinton Construction (Pvt) Ltd
Mobile:- 0702764860,0714334907

--
Best Regards
D.R.B.L.R.Ranawaka,
B.Sc.Eng (Hons), MIE(SL),
Project Manager,
Construction of New Building for NPQS in Sea Port
Darinton Construction (Pvt) Ltd
Mobile:- 0702764860,0714334907

2 attachments
Equipment Shedule -Amended AC VRF (1)-converted.pdf
29K
Latest Sea Port Colombo.pdf
14747K

https://mail.google.com/mail/u/1/?ik=8d17925756&view=pt&search=all&permmsgid=msg-a%3Ar5609653509308387174&dsqt=1&simpl=msg-a%… 4/4

You might also like