Professional Documents
Culture Documents
THIS PAGE IS A RECORD OF ALL SPECIFICATION REVISIONS. NORMALLY, REVISED SHEETS ONLY ATTACHED
EACH TIME THE SPECIFICATION IS CHANGED ONLY THE NEW OR ENTIRE SPECIFICATION RE-ISSUED
REVISED PAGES ARE ISSUED. ENTIRE SPECIFICATION REVISED
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. TABLE OF CONTENTS
CAIRO - EGYPT 000010 - 2839 1
CONTENTS
DIVISION 0: INFORMATION
DIVISIONS 03 CONCRETE
DIVISIONS 04 MASONRY
DIVISIONS 09 FINISHES
DIVISION 10 SPECIALTIES
101400 Signage
DIVISION 11 EQUIPMENT
DIVISION 31 EARTHWORK
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. METHOD OF MEASUREMENT
CAIRO - EGYPT 012700 - 2839 1
METHOD OF MEASUREMENT
1. These notes are intended as a guide only to the method adopted in the preparation of the
Bill of Quantities and the measurement of the Works. Contractors must note that rates
for items must include furnishing and everything necessary for the proper execution,
erection, completion and maintenance of each item and that all auxiliary work is included
unless specifically otherwise stated, measured or excluded in writing by the Engineer.
3. Rates must include work at all levels, furnishing, transportation and installation, materials
and goods, scaffolding and testing where applicable. Each item includes also, unless
otherwise specifically stated, all labor in making, materials, goods and all costs in
connection therewith (e.g. conveyance, delivery, unloading, storing, unpacking, returning
packing, handling, hoisting, lowering and the like), fitting, setting and fixing materials and
goods in position, all square raking and curved cutting, waste of and laps in materials, use
of plant, temporary works, patterns, models, templates, samples and establishment and
overhead charges and profit.
4. Quantities are billed to the nearest whole unit. Fractions of a unit less than half are
disregarded and all other fractions are regarded as whole units.
7. Attention is also directed to the Specifications and Drawings, which contain further notes
on all work, required and which are deemed to be included in rates quoted in attached
Bills of Quantities.
9. Rates include cost of removal of rubbish and debris from the site.
11. Rates for all equipment include testing at manufacturer’s premises and all spare parts
needed during the Defects Liability Period.
12. Rates shall represent full compensation for all plant, materials, transport, labor,
equipment, temporary works, establishment, overhead, profit, and tax charges required
to complete the work described in this sub-section of the specification and/or on the
drawings.
13. Rates shall include all facilities and equipment for testing and inspection by the Employer's
representatives, including transportation.
CONCRETE
Plain Concrete
MASONRY
Measurements shall be for net areas; areas less than 0.25 sq.m will not be
deducted.
Furnishing of all materials, which include but are not limited to stone,
special pieces, end and corner units.
Setting materials, grout and sealants.
Grinding, mitering, and beveling.
Fixing in position and scaffolding.
FINISHES
099100 Painting
Furnishing and applying the paint system including primer, intermediate, top
coats, preparing surfaces, rubbing down between each coat, stopping,
knotting.
Covering of floors, with sheets while painting is being executed, removing paint
splashes, spots, and stains and completion of work to perfection.
Painting on other items such as metal and wood shall not be measured
separately for payment and shall be paid as part of the item.
Repairing of damaged parts.
Cleaning.
Any other required items as per Drawings and Specifications.
SPECIALTIES
101400 Signage
EQUIPMENT
No Rising Arm
EARTHWORK
Section Description
Excavation m3
Backfilling m3
EXTERIOR IMPROVEMENTS
m Fence.
No. Gates
Steel leaves side frames, hardware, fixing, painting, wiring and electrical
requirements.
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. CAST-IN-PLACE CONCRETE
CAIRO - EGYPT 033000- 2839 0
SECTION 033000
CAST-IN-PLACE CONCRETE
Page
PART 1 GENERAL 2
1.1 Related Documents 2
1.2 Summary 2
1.3 Reference Standards 2
1.4 Related Sections 3
1.5 Submittals 4
1.6 Quality Assurance 4
1.7 Delivery, Storage And Handling 4
PART 2 PRODUCTS 5
2.1 Cement 5
2.2 Aggregates 5
2.3 Mixing Water 6
2.4 Steel Reinforcing Bars 6
2.5 Tie Wire 6
2.6 Form Release Agent 6
2.7 Curing Materials 6
2.8 Formwork 6
2.9 Admixtures 7
2.10 Concrete Mixes 7
2.11 Designed Mixes 7
2.12 Quality Control 8
2.13 Standard Mixes 9
PART 3 EXECUTION 9
3.1 Concrete 9
3.2 Steel Reinforcement 10
3.3 Formwork 10
3.4 Testing And Inspection 13
3.5 Tolerances Of Reinforced Concrete 14
PART 1 GENERAL
A. Drawings and General Provisions of the Contract, including Contract Conditions and
Division-1 Specification Sections, apply to work of this Section.
1.2 SUMMARY
A. This section covers the specifications for cast-in-situ structural concrete work re-
quired by the Contract including formwork, reinforcement, mix design, placement
procedures and finishes, for the following:
1. Footings.
A. Concrete works shall be performed in strict accordance with the Specifications, Draw-
ings and the stipulations of the latest editions of the Egyptian Standard Specifications
(ES), and the specifications of the American Society for Testing and Materials (ASTM)
and the designations of the American Association of State Highway and Transporta-
tion Officials (AASHTO) as referenced to throughout the section.
ES No.
ACI NO.
ASTM No.
A 497 Specifications for Welded Deformed Steel Wire Fabric for Concrete Rein-
forcement
C 31 Practice for Making and Curing Concrete Test Specimens in the Field
C 1059 Specification for Latex Agents for Bonding Fresh to Hardened Concrete
In the event of conflict between various codes and standards, the most stringent
shall apply.
A. The following specification sections includes requirements which relate to this sec-
tion:
A. Submit the following in accordance with Conditions of the Contract and Division-1
Specification Sections:
A. Materials and installed work may require testing and retesting at any time during the
progress of the Works. Tests, including retesting of rejected materials or installed
work, shall be done at the Contractor's expense.
1. Contractor’s superintendent.
2. Laboratory responsible for concrete design mixes.
3. Laboratory responsible for field quality control.
4. Ready-mix concrete producer.
5. Concrete subcontractor.
6. Primary admixture manufacturers.
A. Cement shall be delivered to Site in sealed bags bearing the manufacturer's name
and the type of cement. Bulk cement delivered directly from factory in special con-
tainer trucks and stored in steel, elevated weather-tight silos is acceptable.
B. Cement shall be fully protected during handling and transport from adverse weather
C. Cement shall be stored in piles not more than ten bags high in perfectly dry weather-
proof sheds, clear from the ground on planks or other damp-proofing supports. Free
passages, minimum one meter wide, shall be left between stored bags and sidewalls
of buildings (if any) so that each bag shall be visible.
D. Each consignment of cement shall be stored apart from earlier ones, and consign-
ments shall be used in the order they were delivered. Any consignment which has
become lumped caked or otherwise adversely affected shall be removed from Site
immediately.
PART 2 PRODUCTS
2.1 CEMENT
B. For below-grade castings, cement type shall be ordinary Portland cement to ES No.
4756 and ASTM C 150 type I unless otherwise indicated on Geotechnical report rec-
ommendations and Drawings.
C. Use one brand of cement throughout the project. The source of supply of cement
shall be subject to the Engineer's approval. The date of manufacture must be rec-
orded. Follow-up tests shall be performed by an approved testing laboratory and the
Contractor shall at all times furnish test certificates and proof that the required
standard specification has been complied with.
D. Cement used in concrete work shall be less than six months old from date of manu-
facture.
2.2 AGGREGATES
A. Aggregates shall not contain harmful materials which may reduce the strength or du-
rability of concrete nor materials which may attack the reinforcement. Mixed coarse
and fine aggregates together shall not contain more than 0.05% (by weight) chloride
ions.
C. Coarse aggregates shall not contain more than 0.04% (by weight) chloride ions.
D. Quality test on the fine and coarse aggregate material shall be complied with
C136 Test Method for Sieve Analysis of Fine and Coarse Aggregates.
E. Fine Aggregate: Furnish natural siliceous sands from approved pits, free from Opal-
ine, Felspar, mica, fool's gold, siliceous magnesium, limestone or other deleterious or
F. All specified quality testing on the aggregate material shall be carried out by an inde-
pendent testing agency approved by the Engineer.
G. Fine, Coarse and All-in Aggregates: Used for concrete shall comply with the require-
ments of their corresponding Egyptian Standard Specifications.
A. The mixing water shall meet the requirements of the Egyptian code of practice for
design and construction of reinforced concrete ECP 203-2020
A. Reinforcement shall be as shown on Drawings and shall comply with the require-
ments of the Egyptian Standard Specifications ES No. 262 for:
A. Tie wire shall be annealed steel. Except where otherwise required, tie wire shall be
minimum 1.2 mm diameter.
A. Commercially formulated form release agent that shall not bond with stains or ad-
versely affect concrete surface. Formulate form release agent with rust inhibitor for
steel form facing materials.
C. Use membrane-curing compounds that will not affect surfaces to be covered with
finish materials applied directly to concrete.
2.8 FORMWORK
A. Form for concrete work can be of timber, plywood or metal, lumber or wrought
2.9 ADMIXTURES
A. Admixtures may be used, with the written approval of the Engineer, in concrete for
special reasons such as waterproofing, retarding initial setting time, improve worka-
bility, reduce amount of water, etc. Use admixtures strictly in accordance with man-
ufacturer's instructions.
A. Designed mixes shall be used throughout the Works, unless otherwise shown on
Drawings and Bill of Quantities. Standard concrete mixes can be used, if specifically
called for and noted on Drawings.
A. General: The Contractor shall design concrete mixes ECP 203-2020 and in compliance
with ACI 211.1 and ACI 301 standards to satisfy the strength requirements of various
classes of concrete to be used in the Works.
B. Mix designs shall satisfy the specified characteristic concrete strength requirements
given in Table 4. In order to allow for unavoidable variations, the mix shall be de-
signed in accordance to ECP 203-2020 conditions and limits as mentioned in Clause
(2-2-4-2).
D. Trial Mixes: Before commencement of work, trial mixes shall be prepared under full-
scale conditions and tested in accordance with ES 1658, Methods of Testing Con-
crete.
E. If the number of cubes test is more than 20 cubes, the number of results less than
the required characteristic strength shall not exceed one (1) for every 20 results, and
the difference between the highest and the lowest results shall not exceed 25% of
the average of all the results.
Table 4
Non-Air Entrained Concrete Grades
G. Should tests prove that concrete is unsatisfactory then the condemned concrete shall
be cut out, removed and replaced by the Contractor.
H. When works cube tests show concrete strengths consistently higher than those spec-
ified, the contractor may reduce the number of tests to be made to the minimum re-
quired by the Referenced Standards.
I. Minimum Water Cement Ratio should be complied with Egyptian Code of Practice for
Design and Construction of Reinforced Concrete, ECP 203-2020.
J. For Pumpable concrete, slump values shall be achieved using chemical admixtures
approved by the Engineer.
K. Pumpable concrete slump values shall be not less than 125 mm and not more than
200 mm according to ECP 203.
A. Supervision: Employ a competent person and permanently keep him on Site until the
completion of concreting work. His first duty shall be to supervise all stages in prepa-
ration and placing of concrete. He shall be responsible for supervising all tests of ma-
terials, molding and testing of concrete cubes and maintaining and calibrating all mix-
ing and measuring plant.
B. Aggregates: Separate storage bins with adequate provision for drainage shall be pro-
vided for each size of aggregate used (40-20 mm, 30-20 mm, 25-20 mm, 20-10 mm,
10-5 mm, and 5 mm down).
C. Batching and Mixing Plant: Concrete shall be machine mixed by appropriate drum-
type batch machine mixer.
D. If centralized batching plant is planned for use by the Contractor, concrete shall be
mixed dry, transported in transit mixers to place of work where water is to be added
and final mixing is to be carried. If haulage distances are very short, mixing can take
place at the batching plant and concrete transported in agitators or transit mixers.
E. If concreting work is done by using ready mixed concrete it shall conform to ASTM C
94 and concrete shall be mixed dry, transported in transit mixers to place of work
where water is to be added and final mixing is to be carried. If haulage distances are
very short, mixing can take place at the batching plant and concrete transported in
agitators or transit mixers.
F. Provide batch ticket for each batch discharged and used in the work, indicating pro-
ject identification, name and number, date, time, mix type, mix quantity, and amount
of water added.
PART 3 EXECUTION
3.1 CONCRETE
A. Transporting: Concrete shall be handled from the place of mixing to the place of final
deposit as rapidly as practicable by methods that will prevent segregation or contam-
ination of the ingredients.
C. Placing
D. Curing shall start immediately after the disappearance of free surface water. For
special purposes additional extra test cubes of each portion or member, if requested
by the Engineer, shall be cured in the same place and exactly in the same manner as
the portions or members they represent. After seven days, they shall be transported
to the laboratory where they shall be kept in water until tested.
E. Fresh concrete placed at these temperatures shall be carefully shaded from sunrays
and wind.
G. In case of temperature more than 35C, pouring shall be instructed by the Engineer
A. Cleaning: Before placing reinforcement into forms, all steel for reinforcement shall be
cleaned and freed from loose mill scale, loose rust, oil and grease or other harmful
matter that may destroy or reduce bond strength.
B. Bending: All bars shall be bent cold and in accordance with bending schedules.
C. Bending by heat may be allowed for large diameter bars only after receiving a written
permission from the Engineer.
3.3 FORMWORK
A. General: Design, erect, support, brace and maintain formwork to support vertical and
lateral, static and dynamic loads that might be applied until concrete structure can
support such loads. It shall be constructed to the correct size, and shape, to remain
sufficiently tight to prevent loss of grout or mortar of concrete. Forms for concrete
surfaces can be of timber, plywood, or metal. Wrought formwork shall be used
where shown on Drawings or directed by the Engineer.
B. Provide top forms for inclined surfaces where slope is too steep to place concrete
with bottom forms only.
C. Bolts and rods shall be used for internal ties. They shall be so arranged that when the
forms are removed no metal shall exist within 30 mm of any surface. All holes shall
be filled with mortar after the removal of the bolts and all external parts of the metal
ties.
E. Forms in contact with concrete shall be cleaned and treated with approved composi-
tion or form oil. Care shall be taken not to spatter reinforcement with such composi-
tion.
F. Metal Formwork: Metal forms shall be selected for their surface flatness and
smoothness. Where metal forms are selected for use, provide metal forms of stand-
ard manufactured units with a system to function easily and properly, to comply with
the dimension, design loads of the project and of sufficient strength to withstand
pressure of concrete placing operations.
I. Provide forms easy to remove without hammering or prying against concrete surface.
K. Reuse of Formwork: Clean surfaces of forms to be reused in work, remove fins and
laitance.
M. Strutting: The design and erection of the formwork together with the adequacy of all
bracing and strutting shall be the responsibility of the Contractor. The Contractor
shall ensure that there shall be no deformations or failure of the shuttering during
concreting and shall include in his rates for all necessary scaffolding or staging, box-
ing out for fittings and all other works incidental to the shuttering to be erected.
N. The Contractor shall submit to the Engineer detailed drawings and calculation of spe-
cial strutting-work, if so requested, for his approval. Said approval shall not relieve
the Contractor from his responsibilities in case of failure and his obligation to repair
all defects at his own expense.
P. Embedded articles shall be built-in as the work proceeds. Where impractical, steel in-
R. After concreting, the threaded bolt projections, with attached nuts and washers shall
be protected against corrosion with similar sealing tape and protected against me-
chanical change with a timber shield or otherwise approved method until the erec-
tion of the steel works.
T. Form coating shall be applied to provide a thin uniform coating without contaminat-
ing the reinforcement.
U. Cleaning: All rubbish, particularly chippings, shavings, tie wire trim, and sawdust
shall be removed from interior of forms before concrete is placed. Provide tempo-
rary openings in wall forms for cleaning. Prior to pouring, clean interior of walls as
specified hereinbefore and patch openings.
V. Removal of Forms: In any case, forms shall not be removed until the concrete has at-
tained sufficient strength to ensure structural stability and to carry both dead load
and any construction loads that may be imposed on it. Concrete shall be hard
enough so that surfaces will not be injured in any way when reasonable care is used
in removing forms.
W. The minimum period of time that shall elapse between pouring concrete and remov-
al of forms shall be in no case less than the age shown in ECP 203-2020.
Y. Forms shall be removed with due care and attention avoiding all shock or vibration
that would damage concrete.
Z. The Contractor shall make good all concrete surfaces after removal of forms.
AA. Shores and Supports: Before removal of forms temporary shore and brace suspended
slabs with suitable members of sufficient strength to withstand imposed loads.
BB. After removal of forms, shore the produced slab so that, the employed supports are
concentric on the shores supporting the underlying slab.
CC. Keep shores in place until concrete has attained its required strength and heavy loads
due to construction operation have been removed.
B. Sampling Concrete: Concrete for the test specimens shall be taken at point of deposit
to ensure that specimens are representing concrete cast into structure members, a
number of concrete samples shall be taken from different points.
C. The quantity of each concrete sample shall be enough to mould the number of test
specimens required and shall be taken from one work point. The location from
which each sample is taken shall be noted.
G. Core Testing of In Place Concrete: When strength tests of cube specimens have failed
to meet the specified acceptance criteria, perform core testing and take samples of
in-place concrete as required. Results of in-place concrete core testing shall be eval-
uated in accordance with ACI 318.
H. Load Testing of Structures: Should the Engineer have any doubts as to the workman-
ship and quality of the concrete of floor systems based on his evaluation for results
of testing of concrete specimens and results of concrete core samples, then he may
order the load testing of parts or whole sections of the structures, such testing shall
be performed in full compliance with the requirements of the Egyptian Code of Prac-
tice for Design and Construction of Reinforced Concrete as amended herein.
I. During the test, struts strong enough to sustain the whole load shall be placed in po-
sition leaving a gap under members to allow for the expected deflection. If deflection
value is more than the above mentioned limit and if within 24 hours of the removal
of the load, the structure does not show a recovery of at least 75% of the maximum
deflection shown during the 24 hours under load and the crack width is within allow-
able limits the test loading shall be repeated. The part of structure shall be consid-
ered rejected if the recovery after the second test is not at least 75% of the maxi-
mum deflection shown during the second test. If during the test, or upon removal of
the load, the structure shows signs of weakness, undue deflection or faulty construc-
tion, it shall be reconstructed or strengthened as necessary and instructed by the En-
gineer at the Contractor's own expense.
J. All such load testing shall be performed by the Contractor and at his own expense.
A. The following are the allowable tolerances in Reinforced Concrete which shall be ap-
plicable as mentioned in the Egyptian Code of Practice for design and construction of
reinforced concrete, ministerial Decree No. 203-2018.
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. UNIT MASONRY
CAIRO - EGYPT 042000 - 2839 0
SECTION 042000
UNIT MASONRY
Page
PART 1 - GENERAL 2
1.1 Related Documents 2
1.2 Summary 2
1.3 Submittals 2
1.4 Quality Assurance 2
1.5 Project Conditions 2
PART 2 - PRODUCTS 3
2.1 Concrete Masonry Units (CMU) 3
2.2 Mortar And Grout Materials 3
2.3 Ties And Anchors 3
2.4 Miscellaneous Anchors 4
2.5 Miscellaneous Masonry Accessories 5
2.6 Miscellaneous Masonry Accessories 5
2.7 Mortar And Grout Mixes 5
2.8 Masonry Joint Reinforcement 6
PART 3 - EXECUTION 6
3.1 Installation General 6
3.2 Laying Masonry Walls 6
3.3 Mortar Bedding And Jointing 7
3.4 Masonry Joint Reinforcement 7
3.5 Anchoring Masonry To Structural Concrete Members 8
3.6 Repairing, Pointing, And Cleaning 8
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplemen-
tary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
D. Joint Reinforcement.
1.3 SUBMITTALS
C. Samples: Samples for each type and color of exposed masonry units, accessories em-
bedded in the masonry:
D. Mix Designs: For each type of mortar and grout. Include description of type and pro-
portions of ingredients.
A. Sample Panels: Build sample panels for each type of unit masonry construction and
typical wall in sizes approximately 1200 mm long by 1200 mm high.
A. Hot-Weather Requirements: Protect unit masonry work when temperature and hu-
midity conditions produce excessive evaporation of water from mortar and grout.
Provide artificial shade as required.
PART 2 - PRODUCTS
A. Shapes: Provide special shapes for lintels, corners, jambs, sashes, movement joints,
headers, bonding, and other special conditions.
1. Unit Compressive Strength: Provide units according to the Egyptian code 204
and the compressive strength indicated on structural Drawings.
2. Size (Width): As indicated on Drawings.
3. Provide moisture-controlled units, all masonry units shall be factory cured.
C. Aggregate for Mortar: ASTM C 144 or E.S.S. No. 1108; except for joints less than 6.5
mm thick, use aggregate graded with 100 percent passing the No. 26 (1.41-mm)
sieve.
D. Aggregate for Grout: ASTM C 404 or E.S.S. No. 1109, fine aggregate located in second
grade zone, with maximum size of aggregates of 5 mm passing the number 19 sieve.
E. Water: Potable.
A. Provide ties and anchors, specified in subsequent articles, made from materials that
comply with this Article, unless otherwise indicated.
1. Hot-Dip Galvanized Carbon-Steel Wire: ASTM A 82; with ASTM A 153, Class B-2
coating.
2. Steel Sheet, Galvanized after Fabrication: ASTM A 366/A 366M cold-rolled,
carbon-steel sheet hot-dip galvanized after fabrication to comply with
ASTM A 153.
B. Corrugated Metal Ties: Metal strips not less than 22 mm wide with corrugations hav-
ing a wavelength of 7.6 to 12.7 mm and an amplitude of 1.5 to 2.5 mm made from
steel sheet, galvanized after fabrication not less than 1.3 mm thick.
C. Anchors for Connecting to Structure: Provide anchors that allow vertical or horizontal
1. Anchor Section for Welding to Steel Frame: Crimped 3.0- diameter, hot-dip
galvanized steel wire.
2. Tie Section for Steel Frame: Triangular-shaped wire tie, sized to extend within
25 mm of masonry face, made from 4.8-mm diameter, hot-dip galvanized steel
wire.
3. Connector Section for Concrete: Dovetail tabs for inserting into dovetail slots
in concrete and attached to tie section; formed from 2.5-mm- thick, steel
sheet, galvanized after fabrication, unless otherwise indicated.
4. Tie Section for Concrete: Corrugated metal ties with dovetail tabs for inserting
into dovetail slots in concrete and sized to extend to within 25 mm of masonry
face.
D. Partition Top anchors: 2.5-mm- thick metal plate with 10-mm- diameter metal rod
150 mm long welded to plate and with closed-end plastic tube fitted over rod that al-
lows rod to move in and out of tube. Fabricate from steel, hot-dip galvanized after
fabrication.
E. Rigid Anchors: Fabricate from steel bars 38 mm wide by 6.4 mm thick by 600 mm
long, with ends turned up 50 mm or with cross pins, unless otherwise indicated].
B. Dovetail Slots in Concrete: Furnish dovetail slots with filler strips, of slot size indicat-
ed, fabricated from 0.9-mm, galvanized steel sheet.
C. Anchor Bolts: Headed or L-shaped steel bolts complying with ASTM A 307, Grade A
(ASTM F 568M, Property Class 4.6); with ASTM A 563 (ASTM A 563M) hex nuts and,
where indicated, flat washers; hot-dip galvanized to comply with
ASTM A 153/A 153M, Class C; of dimensions indicated.
E. Reinforcing Bar Positioners: Wire units designed to fit into mortar bed joints span-
ning masonry unit cells with loops for holding reinforcing bars in center of cells.
Units are formed from 3.6-mm steel wire, hot-dip galvanized after fabrication. Pro-
vide units with either two loops or four loops as needed for number of bars indicat-
ed.
B. Precast Rainwater Scupper: Provide precast rainwater scupper in ground floor of di-
mensions and details indicated on Drawings, to comply with PCI MNL 120
PART 3 - EXECUTION
A. Thickness: Build walls and other masonry construction to the full thickness shown.
Build single-Wythe walls to the actual widths of masonry units, using units of widths
indicated.
B. Leave openings for equipment to be installed before completing masonry. After in-
stalling equipment, complete masonry to match the construction immediately adja-
cent to the opening.
C. Cut masonry units with motor-driven saws to provide clean, sharp, unchipped edges.
Cut units as required to provide a continuous pattern and to fit adjoining construc-
tion. Where possible, use full-size units without cutting. Install cut units with cut
surfaces and, where possible, cut edges concealed.
1. For conspicuous vertical lines, such as external corners, door jambs, reveals,
and control joints, do not vary from plumb by more than 3 mm in 3 m, 6 mm in
6 m, or 12 mm maximum.
2. For conspicuous horizontal lines, such as lintels, sills, parapets, and reveals, do
not vary from level by more than 3 mm in 3 m, 6 mm in 6 m, or 12 mm maxi-
mum.
A. Lay out walls in advance for accurate spacing of surface bond patterns with uniform
joint thicknesses and for accurate location of openings, movement-type joints, re-
turns, and offsets. Avoid using less-than-half-size units, particularly at corners,
B. Bond Pattern for Exposed Masonry: Unless otherwise indicated, lay exposed masonry
in running bond; do not use units with less than nominal 100-mm horizontal face di-
mensions at corners or jambs.
C. Built-in Work: As construction progresses, build in items specified in this and other
Sections. Fill in solidly with masonry around built-in items.
D. Fill space between steel frames and masonry solidly with mortar, unless otherwise
indicated.
E. Fill cores in hollow concrete masonry units with grout 600 mm under bearing plates,
beams, lintels, posts, and similar items, unless otherwise indicated.
1. With face shells fully bedded in mortar and with head joints of depth equal to
bed joints.
2. With webs fully bedded in mortar in all courses of piers, columns, and pilas-
ters.
3. With webs fully bedded in mortar in grouted masonry, including starting
course on footings.
4. With entire units, including areas under cells, fully bedded in mortar at starting
course on footings where cells are not grouted.
5. Maintain joint widths indicated, except for minor variations required to main-
tain bond alignment. If not indicated, lay walls with 10-mm joints.
B. Lay solid masonry units with completely filled bed and head joints; butter ends with
sufficient mortar to fill head joints and shove into place. Do not deeply furrow bed
joints or slush head joints.
C. Walls to be plastered shall have the horizontal joints raked out to a depth of 12 mm
to form a key.
B. Interrupt joint reinforcement at control and expansion joints, unless otherwise indi-
cated.
A. In-Progress Cleaning: Clean unit masonry as work progresses by dry brushing to re-
move mortar fins and smears before tooling joints.
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. EXTERIOR STONE CLADDING
CAIRO - EGYPT 044200– 2839 0
SECTION 044200
Page
PART 1 GENERAL 2
1.1 Related Documents 2
1.2 Summary 2
1.3 Submittals 2
1.4 Quality Assurance 2
1.5 Delivery, Storage, and Handling 3
1.6 Project Conditions 3
1.7 Coordination 3
PART 2 GENERAL 3
2.1 Granite 3
2.2 Limestone 3
2.3 Marble 3
2.4 Quartz-Based Stone 3
2.5 Slate 3
2.6 Setting Materials 3
2.7 Grout 4
2.8 Sealants 4
2.9 Stone Anchors and Attachments 4
2.10 Stone Accessories 4
2.11 Stone Fabrication, General 5
2.12 Stone [Paneling] [and] [Column Facing] 5
2.13 Stone Base 6
2.14 Stone Benches 6
2.15 Stone Countertop 6
2.16 Mixes 6
PART 3 EXECUTION 7
3.1 Examination 7
3.2 Preparation 7
3.3 Setting of Stone, General 7
3.4 Construction Tolerances 8
3.5 Installation of Stone [Paneling] [and] [Column Facing] 8
3.6 Installation of Stone Base 9
3.7 Installation of Stone Benches 9
3.8 Grouting Joints 9
3.9 Pointing Joints with Mortar 9
3.10 Joint-Sealant Installation 9
3.11 Adjusting and Cleaning 9
3.12 Protection 9
PART 1 GENERAL
1.2 SUMMARY
1. Exterior stone facing set with wire ties and cement sand grout.
1. Division 04 Section "Unit Masonry" for installing masonry inserts for anchoring
interior stone facing.
2. Division 07 Section "Joint Sealants" for sealing joints with elastomeric sealants
in expansion joints of interior stone facing.
1.3 SUBMITTALS
B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other
work.
C. Samples for Initial Selection: For joint materials involving color selection.
1. For each stone type indicated, in sets of Samples not less than 300 mm square.
Include four or more Samples in each set and show the full range of variations
in appearance characteristics expected in completed Work.
2. For each color of grout and sealant required.
C. Source Limitations for Stone: Obtain each variety of stone, regardless of finish, from
a single quarry with resources to provide materials of consistent quality in
appearance and physical properties and to cut and finish material without delaying
the Work.
1. Obtain each variety of stone from a single quarry, whether specified in this
Section or in another Section of the Specifications.
D. Build mockups to demonstrate aesthetic effects and set quality standards for
materials and execution.
A. Lift stone with wide-belt slings; do not use wire rope or ropes that might cause
staining. Move stone, if required, using dollies with cushioned wood supports.
PART 2 GENERAL
2.1 MARBLE
D. Water: Potable.
2.3 SEALANTS
A. Temporary Setting Shims: Rigid plastic shims, nonstaining to stone, sized to suit joint
thickness.
D. Setting Shims: are to be resilient shims, nonstaining to stone, sized to suit joint
thickness.
A. Select stone for intended use to prevent fabricated units from containing cracks,
seams, and starts that could impair structural integrity or function.
B. Fabricate interior stone facing in sizes and shapes required to comply with
requirements indicated, including details on Drawings and Shop Drawings.
C. Cut stone to produce pieces of thickness, size, and shape indicated and to comply
with fabrication and construction tolerances recommended by applicable stone
association.
1. Where items are installed with adhesive or where edges of stone is visible in
the finished work, make items uniform in thickness and of identical thickness
for each type of item; gage back of stone if necessary.
2. Clean sawed backs of stones to remove rust stains and iron particles.
3. Dress joints straight and at right angle to face, unless otherwise indicated.
4. Provide openings, reveals, and similar features as needed to accommodate
adjacent work.
D. Finish exposed faces and edges of stone to comply with requirements indicated for
finish of each type of stone required and to match approved Samples and mockups.
E. Carefully inspect finished stone units at fabrication plant for compliance with
requirements for appearance, material, and fabrication. Replace defective units.
A. Arrange panels in shop or other suitable space in proposed orientation and sequence
for examination by Engineer. Mark units with temporary sequence numbers to
indicate position in proposed layout.
C. Quirk-miter corners, unless otherwise indicated. Install anchorage in top and bottom
bed joints of corner units.
E. Pattern Arrangement: Fabricate and arrange panels with veining and other natural
markings to comply with the following requirements:
2.8 MIXES
Cement Sand Mortar: Mortar shall consist of 350 kg Ordinary Portland cement to
each 1 m3 sand. Add water as required to attain mortar in slurry consistency.
3.1 EXAMINATION
A. Examine surfaces indicated to receive interior stone facing and conditions under
which interior stone facing will be installed, with Installer present, for compliance
with requirements for installation tolerances and other conditions affecting
performance.
1. For the record, prepare written report, endorsed by Installer, listing conditions
detrimental to performance of interior stone facing.
2. Proceed with installation only after unsatisfactory conditions have been
corrected.
3.2 PREPARATION
A. Clean dirty or stained stone surfaces by removing soil, stains, and foreign materials
before setting. Clean stone by thoroughly scrubbing with fiber brushes and then
drenching with clear water. Use only mild cleaning compounds that contain no
caustic or harsh materials or abrasives.
A. Do necessary field cutting as stone is set. Use power saws with diamond blades to
cut stone. Cut lines straight and true, with edges eased slightly to prevent snipping.
C. Set stone to comply with requirements indicated on Drawings and Shop Drawings.
Install anchors, supports, fasteners, and other attachments indicated or necessary to
secure stone in place. Shim and adjust anchors, supports, and accessories to set
stone accurately in locations indicated, with edges and faces aligned according to
established relationships and indicated tolerances.
D. Erect stone units level, plumb, and true with uniform joint widths. Use temporary
shims to maintain joint width.
A. Variation from Plumb: For vertical lines and surfaces, do not exceed 3 mm in 2400
mm, 6 mm maximum.
B. Variation from Level: For lintels, sills, chair rails, horizontal bands, horizontal
grooves, and other conspicuous lines, do not exceed 3 mm in 3 m, 6 mm in 6 m, 10
mm maximum.
C. Variation of Linear Building Line: For position shown in plan and related portion of
walls and partitions, do not exceed 3 mm in 2400 mm, 6 mm in 6 m, 10 mm
maximum.
E. Variation in Joint Width: Do not vary joint thickness more than 1.5 mm or 1/4 of
nominal joint width, whichever is less.
F. Variation in Plane between Adjacent Stone Units (Lipping): Do not exceed 0.8-
mmdifference between planes of adjacent units.
G. Set units firmly against setting spots. Locate setting spots at anchors and spaced not
more than 450 mm apart across back of unit, but provide no fewer than 1 setting
spot per 0.18 sq. m, unless otherwise indicated.
1. Moisture Exposure: Use portland cement mortar for setting spots where stone
is applied to inside face of exterior walls and at other locations where stone or
cavity will be exposed to moisture.
A. Fixing of stone facing units shall be with thick wet setting grout in the following
sequence:
A. Prepare joints and apply sealants of type and at locations indicated to comply with
applicable requirements in Division 07 Section "Joint Sealants." Remove temporary
shims before applying sealants.
D. Clean interior stone facing no fewer than six days after completion of grouting and
pointing, using clean water and soft rags or stiff-bristle fiber brushes. Do not use
wire brushes, acid-type cleaning agents, cleaning compounds with caustic or harsh
fillers, or other materials or methods that could damage stone.
E. Sealer Application: Apply stone sealer to comply with stone producer's and sealer
manufacturer's written instructions and recommendations.
3.9 PROTECTION
A. Protect stone surfaces, edges, and corners from construction damage. Use securely
fastened untreated wood, plywood, or heavy cardboard to prevent damage.
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. CAST-IN-PLACE CONCRETE
CAIRO - EGYPT 071340 - 2839 0
SECTION 071340
POLYETHYLENE SHEET
Page
PART 1 GENERAL 2
1.1 Summary 2
1.2 Submittals 2
1.3 Quality Assurance 2
PART 2 PRODUCTS 2
2.1 Polyethylene Sheets 2
PART 3 EXECUTION 3
PART 1 GENERAL
1.1 SUMMARY
A. This section covers the work of polyethylene sheet under slabs on grade.
1.2 SUBMITTALS
A. Product Data: Include data substantiating that employed materials comply with
requirements specified in this section, and written instructions for preparing, and
treating substrate, and testing physical and performance properties.
PART 2 PRODUCTS
A. General: Provide polyethylene sheet which comply with the specified requirements
or provide other similar alternative products which are certified in writing by
manufacturer to be superior in performance for application indicated
A. Substrate shall be uniform well compacted soil, with surface graded and smooth.
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. COLD FLUID-APPLIED
CAIRO - EGYPT WATERPROOFING 071416 - 2839 0
SECTION 071416
Page
PART 1 GENERAL 2
1.1 Related Documents 2
1.2 Summary 2
1.3 Reference Standards 2
1.4 Submittals 2
1.5 Quality Assurance 3
1.6 Project Conditions 3
1.7 Delivery, Storage And Handling 3
1.8 Special Warranty 4
PART 2 PRODUCTS 4
2.1 Cold-Applied Bitumen Emulsion Damp-Proofing 4
2.2 Primer 5
2.3 Joint Sealant 5
2.4 Backer Rod 5
PART 3 EXECUTION 5
3.1 Preparation Of Substrate 5
3.2 Protection Of Other Work 5
3.3 Application 6
3.4 Protection Course And Field Test 6
3.5 Protection And Clean-Up 7
PART 1 GENERAL
A. Drawings and General Provisions of the Contract, including Contract Conditions and
Division-1 Specification Sections, apply to work of this Section.
1.2 SUMMARY
A. This section covers the work of cold fluid-applied waterproofing for concealed
application as required by the Contract.
ASTM No.
B. In the event of conflict between the various codes and standards the most stringent
conditions shall apply.
1.4 SUBMITTALS
A. Submit the following in accordance with Conditions of the Contract and Division-1
Specification Sections:
1. Product Data: For each type of waterproofing specified provide technical data
and tested physical and performance properties and include manufacturer's
printed instructions for evaluating, preparing and treating the substrate.
C. Weather: Proceed with fluid-applied waterproofing work only when existing and
forecast weather conditions shall permit work to be performed in accordance with
manufacturer's recommendations.
E. Handle materials carefully during delivery or transit. Do not cut or break original
packages.
A. The Contractor agrees to repair or replace waterproofing that does not meet
requirements or does not remain watertight within a period of 5 years after date of
Substantial Completion.
PART 2 PRODUCTS
A. Provide waterproofing fully compatible with, and able to develop bond to substrate
and with less than 90% solids.
D. The emulsion shall be in such a condition that, with only light stirring, it is suitable for
application either by brushing or rollers or by spraying as ordered, or by dip
application when thinned if necessary, in accordance with the manufacturer's
instructions.
E. The emulsion shall allow for its application on dry and damp surfaces. It shall have
excellent adhesion properties to all surfaces and good elastic-plastic properties, and
be sufficiently thick and flexible to bridge minor joints and cracks in the wall or deck.
F. The emulsion shall not flash at any temperature below 32C, resistant to cold and
heat. It shall have high resistance to aggressive salts and chemicals, contain no
solvents, and shall have very good weather resistance.
G. The emulsion when stored in the original sealed containers at normal room
temperature, shall retain its properties for a period of not less than 12 months from
date of delivery.
PART 3 EXECUTION
C. Fill voids, seal joints and cracks exceeding 1.6 mm wide and apply bond breakers (if
any) as recommended by materials manufacturer, with particular attention to
construction joints.
D. All vertical surfaces shall be firm, hard, smooth and dry and shall be thoroughly
chipped, wire brushed and washed with clean water to present a new fresh and clean
surface to which material shall bond.
H. Apply a double thickness of waterproofing and embed a joint reinforcing strip where
recommended.
I. Install sheet flashing and bond to slab and wall substrates where required.
A. Close off drains and other deck penetrations. Do not allow liquid compounds to enter
and clog drains and conduits. Prevent spillage and migration onto other surfaces of
work, by masking or otherwise protecting adjoining work.
A. Proceed with installation only after the minimum recommended concrete curing
period.
1. Retaining Walls.
2. Foundations of retaining walls.
3. Footings interpenetrated with retaining walls foundations.
4. Water features and concrete elements under landscape works.
G. Bituminous Emulsion on Exterior and Interior Surfaces: Shall be applied all around
concrete and wall elements under the ground surface and in moist areas indicated
height. Emulsion shall be stirred and mixed to a homogeneous liquid before use.
I. Apply over prepared substrate as a primer a coat diluted with water at a percentage
according to porosity and dampness of the surface and as recommended by the
manufacturer and let to dry for one or two hours before subsequent application.
L. Care shall be taken not to injure the vertical damp-proofing treatment either during
application or after completion, and all finished surfaces shall be approved by the
Engineer before construction of permanent work.
C. Engage a testing agency to perform field inspections, test materials being used,
observe flood test and report whether tested work conforms to or deviates from
requirements.
C. Clean spillage and soiling from adjacent construction using cleaning agents.
D. Cleaning: The Contractor shall remove all equipment, rubbish, debris and clean the
Site to the satisfaction of the Engineer.
E. Clean spillage and soiling from adjacent construction using cleaning agents.
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. JOINT SEALANTS
CAIRO - EGYPT 079200 – 2839 0
SECTION 079200
JOINT SEALANTS
Page
PART 1 GENERAL 2
1.1 Related Documents 2
1.2 Summary 2
1.3 Performance Requirements 2
1.4 Submittals 2
1.5 Quality Assurance 3
1.6 Project Conditions 3
1.7 Warranty 3
PART 2 PRODUCTS 4
2.1 Materials, General 4
2.2 Elastomeric Joint Sealants 4
2.3 Solvent-Release Joint Sealants 5
2.4 Acrylic Latex Joint Sealants 6
2.5 Acoustical Joint Sealants 6
2.6 Preformed Joint Sealants 6
2.7 Preformed Tape Sealants 6
2.8 Joint-Sealant Backing 7
2.9 Miscellaneous Materials 7
PART 3 EXECUTION 7
3.1 Examination 7
3.2 Preparation 8
3.3 Installation Of Joint Sealants 8
3.4 Cleaning 10
3.5 Protection 10
3.6 Joint-Sealant Schedule 10
PART 1 GENERAL
1.2 SUMMARY
1. Division 4 Section "Unit Masonry" for masonry control and expansion joint
fillers and gaskets.
2. Division 7 Section "Through Penetration Firestop Systems” for fire-resistant
building joint-sealant systems.
3. Division 8 Section "Aluminum Entrances".
4. Division 8 Section "Aluminum Windows".
5. Division 8 Section "Glazing" for glazing sealants.
6. Division 9 Section "Gypsum Board" for sealing perimeter joints of gypsum
board partitions to reduce sound transmission.
7. Division 9 Sections of suspended ceilings for sealing edge moldings at
perimeters of acoustical ceilings.
A. Provide elastomeric joint sealants that establish and maintain watertight and airtight
continuous joint seals without staining or deteriorating joint substrates.
B. Provide joint sealants for interior applications that establish and maintain airtight
and water-resistant continuous joint seals without staining or deteriorating joint
substrates.
1.4 SUBMITTALS
B. Samples for Initial Selection: Manufacturer's color charts consisting of strips of cured
sealants showing the full range of colors available for each product exposed to view.
C. Samples for Verification: For each type and color of joint sealant required. Install
joint sealants in 13-mm- wide joints formed between two 150-mm- long strips of
D. Product Certificates: For each type of joint sealant and accessory, signed by product
manufacturer.
E. Product Test Reports: From a qualified testing agency indicating sealants comply
with requirements, based on comprehensive testing of current product formulations.
B. Source Limitations: Obtain each type of joint sealant through one source from a
single manufacturer.
A. Do not proceed with installation of joint sealants under the following conditions:
1.7 WARRANTY
PART 2 PRODUCTS
A. Compatibility: Provide joint sealants, backings, and other related materials that are
compatible with one another and with joint substrates under conditions of service
and application, as demonstrated by sealant manufacturer based on testing and field
experience.
A. Elastomeric Sealant Standard: Comply with ASTM C 920 and other requirements
indicated for each liquid-applied chemically curing sealant in the Elastomeric Joint-
Sealant Schedule at the end of Part 3, including those referencing ASTM C 920
classifications for type, grade, class, and uses.
C. Suitability for Immersion in Liquids. Where elastomeric sealants are indicated for
Use I for joints that will be continuously immersed in liquids, provide products that
have undergone testing according to ASTM C 1247 and qualify for the length of
exposure indicated by reference to ASTM C 920 for Class 1 or 2. Liquid used for
testing sealants is deionized water, unless otherwise indicated.
D. Suitability for Contact with Food: Where elastomeric sealants are indicated for joints
that will come in repeated contact with food, provide products that comply with
E. Suitability for Installation in Wet Areas: For grouting of ceramic tiles, sealing shower
trays, tubs and other plumbing fixtures and for similar applications in wet areas,
provide sanitary-sealant, mildew-resistant, silicone-based of color as selected by the
Engineer from manufacturers standard colors.
F. Sealants Designations:
a. Class: 50.
a. Type and Grade: S (single component) and NS (nonsag).
b. Uses Related to Joint Substrates: M, G, A, O
c. Neutral, non staining , non Bleeding, fungicide –containing
a. Class: 25
b. Type and Grade: S (single component) and NS (nonsag).
c. Uses Related to Joint Substrates: M, G, A, O
d. Neutral, non staining , non Bleeding , fungicide –containing
a. Class: 25
b. Type and Grade: (M (multicomponent)) and NS (nonsag).
c. Uses Related to Joint Substrates: M, G, A, O
d. Chemical curing , non Staining and non bleeding
e. Sealant containing mercury not allowed
a. Class: 25.
b. Grade: P (Pourable).
c. Classification Related to Exposure: T.
d. Shore Hardness: 50, minimum, when tested in accordance ASTM C661.
A. Acrylic Latex Sealant Standard: Comply with ASTM C 834, Type P, Grade NF, non-
bleeding.
1. Class: ± 7.5%.
A. General: Provide sealant backings of material and type that are nonstaining; are
compatible with joint substrates, sealants, primers, and other joint fillers; and are
approved for applications indicated by sealant manufacturer based on field
experience and laboratory testing.
B. Cylindrical Sealant Backings: ASTM C 1330, of type indicated below and of size and
density to control sealant depth and otherwise contribute to producing optimum
sealant performance:
PART 3 EXECUTION
3.1 EXAMINATION
A. Examine joints indicated to receive joint sealants, with Installer present, for
compliance with requirements for joint configuration, installation tolerances, and
other conditions affecting joint-sealant performance.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
A. Surface Cleaning of Joints: Clean out joints immediately before installing joint
sealants to comply with joint sealant manufacturer's written instructions and the
following requirements:
1. Remove all foreign material from joint substrates that could interfere with
adhesion of joint sealant, including dust, paints (except for permanent,
protective coatings tested and approved for sealant adhesion and
compatibility by sealant manufacturer), old joint sealants, oil, grease,
waterproofing, water repellents, water, surface dirt, and frost.
2. Clean porous joint substrate surfaces by brushing, grinding, blast cleaning,
mechanical abrading, or a combination of these methods to produce a clean,
sound substrate capable of developing optimum bond with joint sealants.
Remove loose particles remaining from above cleaning operations by
vacuuming or blowing out joints with oil-free compressed air. Porous joint
surfaces include the following:
a. Concrete.
b. Masonry.
c. Unglazed surfaces of ceramic tile.
a. Metal.
b. Glass.
c. Porcelain enamel.
d. Glazed surfaces of ceramic tile.
B. Joint Priming: Prime joint substrates where recommended in writing by joint sealant
manufacturer, based on preconstruction joint-sealant-substrate tests or prior
experience. Apply primer to comply with joint sealant manufacturer's written
instructions. Confine primers to areas of joint-sealant bond; do not allow spillage or
migration onto adjoining surfaces.
C. Masking Tape: Use masking tape where required to prevent contact of sealant with
adjoining surfaces that otherwise would be permanently stained or damaged by such
contact or by cleaning methods required to remove sealant smears. Remove tape
immediately after tooling without disturbing joint seal.
D. Install sealant backings of type indicated to support sealants during application and
at position required to produce cross-sectional shapes and depths of installed
sealants relative to joint widths that allow optimum sealant movement capability.
E. Install bond-breaker tape behind sealants where sealant backings are not used
between sealants and back of joints.
F. Install sealants by proven techniques to comply with the following and at the same
time backings are installed:
1. Place sealants so they directly contact and fully wet joint substrates.
2. Completely fill recesses provided for each joint configuration.
3. Produce uniform, cross-sectional shapes and depths relative to joint widths
that allow optimum sealant movement capability.
3.4 CLEANING
A. Clean off excess sealants or sealant smears adjacent to joints as the Work progresses
by methods and with cleaning materials approved in writing by manufacturers of
joint sealants and of products in which joints occur.
3.5 PROTECTION
A. Protect joint sealants during and after curing period from contact with contaminating
substances and from damage resulting from construction operations or other causes
so sealants are without deterioration or damage at time of Substantial Completion.
If, despite such protection, damage or deterioration occurs, cut out and remove
damaged or deteriorated joint sealants immediately so installations with repaired
areas are indistinguishable from the original work.
A. Interior Locations:
B. Exterior Locations:
1. Wall Joints
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. PORTLAND CEMENT PLASTER
CAIRO - EGYPT 092400 – 2839 0
SECTION 092400
Page
PART 1 GENERAL 2
1.1 Related Documents 2
1.2 Summary 2
1.3 Submittals 2
1.4 Quality Assurance 2
1.5 Delivery, Storage, And Handling 2
PART 2 PRODUCTS 3
2.1 Lath 3
2.2 Accessories 3
2.3 Plaster Materials 4
2.4 Miscellaneous Materials 4
2.5 Plaster Mixes And Compositions 5
2.6 Mixing 5
PART 3 EXECUTION 5
3.1 Preparation 5
3.2 Preparation For Plastering 5
3.3 Installation Of Plastering Accessories 6
3.4 Plaster Application 7
PART 1 GENERAL
1.2 SUMMARY
1.3 SUBMITTALS
A Mockups: Prior to installing plaster work, construct panels for each type of finish and
application required to verify selections made under Sample submittals and to
demonstrate aesthetic effects as well as qualities of materials and execution. Build
mockups to comply with the following requirements, using materials indicated for
final unit of Work.
1. Locate mockups on-site in the location and of the size as directed by Engineer.
2. Erect mockups 1200 by 1200 mm by full thickness in presence of Engineer
using materials, including lath, support system, and control joints, indicated for
final Work.
B Store materials inside, under cover, and dry, protected from weather, direct sunlight,
surface contamination, aging, corrosion, and damage from construction traffic and
other causes.
2.1 LATH
A Expanded-Metal Lath: Comply with ASTM C 847 for material, type, configuration, and
other characteristics indicated below.
2.2 ACCESSORIES
A General: Comply with material provisions of ASTM C 1063 and the requirements
indicated below; coordinate depth of accessories with thicknesses and number of
plaster coats required.
D Cornerbeads: Small nose cornerbeads fabricated from the following metal, with
expanded flanges of large-mesh diamond-metal lath allowing full plaster encasement.
E Casing Beads: Square-edged style, with expanded flanges of the following material:
D Sand Aggregate for Base Coats: E.S.S. No. 1108, Table 1, Gradation for scratch and
base coats.
1. External Plaster: High quality premixed smooth plaster, reinforced with fiber,
can be applied by hand or by spraying machines.
2. Internal Plaster: High quality premixed smooth plaster, can be applied by hand
or by spraying machines.
A Fiber for Base Coat: Alkaline-resistant glass or polypropylene fibers, 13 mm long, free
of contaminants, manufactured for use in Portland cement plaster.
B Dash-Coat Material: 400 kg Portland cement to 1 m3 fine sand, mixed with water to
a mushy-paste consistency.
C Fiber Content: Add fiber to mixes after ingredients have mixed at least 2 minutes.
Comply with fiber manufacturer's written instructions but do not exceed 16 kg/cu. m
of cementitious materials. Reduce aggregate quantities accordingly to maintain
workability.
1. External Plaster: Minimum cement content shall be 350 kg per each cubic
meter of sand.
2. Plasticiser as per manufacturer’s printed instructions
2.6 MIXING
A Mechanically mix cementitious and aggregate materials for plasters to comply with
applicable referenced application standard. Hand mixing is not permitted.
PART 3 EXECUTION
3.1 PREPARATION
A Examine areas and substrates, with Installer present, for compliance with
requirements and other conditions affecting performance.
B Protect adjacent work from soiling, spattering, moisture deterioration, and other
harmful effects caused by plastering.
A Clean plaster bases and substrates for direct application of plaster, removing loose
material and substances that may impair the Work.
B Etch concrete and concrete unit masonry surfaces indicated for direct plaster
application. Scrub with acid-etching solution on previously wetted surface and rinse
thoroughly with clean water. Repeat application, if necessary, to obtain adequate
suction and mechanical bond of plaster (where dash coat, bonding agent, or additive
is not used).
D Apply dash coat on concrete surfaces indicated for direct plaster application. Moist-
cure dash coat for at least 24 hours after application and before plastering.
E Install temporary grounds and screeds to ensure accurate rodding of plaster to true
surfaces; coordinate with scratch-coat work.
H Before starting preparation and applying plaster coats ensure that backgrounds are
secure, adequately true and level to achieve specified tolerances, free from
contamination and loose areas, reasonably dry and in a suitable condition to receive
specified coatings. Ensure also that all cutting, chasing, fixing of concealed conduits,
service outlets, fixing pads and the like and making good of the background are
completed.
B General: Comply with referenced lathing and furring installation standards for
provision and location of plaster accessories of type indicated. Miter or cope
accessories at corners; install with tight joints and in alignment. Attach accessories
securely to plaster bases to hold accessories in place and in alignment during
plastering. Install accessories of type indicated at following locations:
B Do not use materials that are caked, lumpy, dirty, or contaminated by foreign
materials.
D Flat Surface Tolerances: Do not deviate more than plus or minus 3 mm in 3 m from a
true plane in finished plaster surfaces, as measured by a 3-m straightedge placed at
any location on surface.
E Full grout hollow-metal frames, bases, and similar work occurring in plastered areas,
with base-coat plaster material, and before lathing where necessary.
F Sequence plaster application with installation and protection of other work so that
neither will be damaged by installation of other.
G Plaster flush with frames and other built-in items or metal accessories that act as a
plaster ground, unless otherwise indicated.
H Corners: Finish external corners flush with corner beads, square and true with
plaster faces on exterior work.
J Finish Coats: Apply finish coats to comply with the following requirements:
K Total thickness of plaster: Excluding dash-coat, apply plaster to the following total
thickness:
M If dubbing out is necessary to correct inaccuracies, dub out in thicknesses of not more
than 10 mm in same mix as undercoat; total thickness of dubbing must not exceed 25
mm unless otherwise approved. Comb surface of each dubbing out coat as specified;
allow each coat to dry before the next is applied.
N Cut, patch, replace, repair, and point up plaster as necessary to accommodate other
work. Repair cracks and indented surfaces. Point-up finish plaster surfaces around
items that are built into or penetrate plaster surfaces. Repair or replace work to
eliminate blisters, buckles, check cracking, dry outs, efflorescence, excessive pinholes,
and similar defects. Repair or replace work as necessary to comply with required
visual effects.
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. PAINTING
CAIRO - EGYPT 099100 – 2839 0
SECTION 099100
PAINTING
Page
PART 1 GENERAL 2
1.1 Related Documents 2
1.2 Summary 2
1.3 Submittals 3
1.4 Quality Assurance 3
1.5 Delivery, Storage, And Handling 4
1.6 Project Conditions 5
PART 2 PRODUCTS 5
2.1 Paint Materials, General 5
PART 3 EXECUTION 5
3.1 Examination 5
3.2 Preparation 6
3.3 Application 7
3.4 Field Quality Control 10
3.5 Cleaning 11
3.6 Protection 11
3.7 Exterior Paint Schedule 11
PART 1 GENERAL
1.2 SUMMARY
A. This Section includes surface preparation and field painting of the following:
B. Paint exposed surfaces, except where the paint schedules indicate that a surface or
material is not to be painted or is to remain natural. If the paint schedules do not
specifically mention an item or a surface, paint the item or surface the same as
similar adjacent materials or surfaces whether or not schedules indicate colors. If the
schedules do not indicate color or finish, the Engineer will select from standard colors
and finishes available.
1. Painting includes field painting of exposed bare and covered pipes and ducts
(including color coding), hangers, exposed steel and iron work, and primed
metal surfaces of mechanical and electrical equipment.
a. Furred areas.
A. Product Data: For each paint system specified. Include block fillers and primers.
B. Material List: Provide an inclusive list of required coating materials. Indicate each
material and cross-reference specific coating, finish system, and application. Identify
each material by manufacturer's catalog number and general classification.
D. Samples for Initial Selection: Manufacturer's color charts showing the full range of
colors available for each type of finish-coat material indicated.
E. Samples for Verification: Of each color and material to be applied, with texture to
simulate actual conditions, on representative Samples of the actual substrate.
1. Provide stepped Samples, defining each separate coat, including block fillers
and primers. Use representative colors when preparing Samples for review.
Resubmit until required sheen, color, and texture are achieved.
2. Provide a list of materials and applications for each coat of each sample. Label
each sample for location and application.
3. Submit Samples on the following substrates for the Engineer's review of color
and texture only:
4. Concrete: Provide two 100-mm- square samples for each color and finish.
5. Concrete Masonry: Provide two 100-by-200-mm samples of masonry, with
mortar joint in the center, for each finish and color.
6. Painted Wood: Provide two 300-mm- square samples of each color and
material on hardboard.
7. Stained or Natural Wood: Provide two 100-by-200-mm samples of natural- or
stained-wood finish on actual wood surfaces.
8. Ferrous Metal: Provide two 100-mm- square samples of flat metal and two
200-mm- long samples of solid metal for each color and finish.
F. Qualification Data: For firms and persons specified in the "Quality Assurance" Article
to demonstrate their capabilities and experience. Include lists of completed projects
with project names and addresses, names and addresses of engineer’s and
employers, and other information specified.
G. Certificate Test.
D. Source Limitations: Obtain block fillers, primers, and undercoat materials for each
coating system from the same manufacturer as the finish coats.
1. The Engineer will select one room or surface to represent surfaces and
conditions for each type of coating and substrate to be painted.
a. After finishes are accepted, the Engineer will use the room or surface to
evaluate coating systems of a similar nature.
1. Keep storage area neat and orderly. Remove oily rags and waste daily. Take
necessary measures to ensure that workers and work areas are protected from
fire and health hazards resulting from handling, mixing, and application.
A. Apply water-based paints only when the temperature of surfaces to be painted and
surrounding air temperatures are between 10 and 32 deg C.
C. Do not apply paint in rain, fog, or mist; or when the relative humidity exceeds 85
percent; or at temperatures less than 3 deg C above the dew point; or to damp or
wet surfaces.
PART 2 PRODUCTS
C. Colors: Provide color selections made by the Engineer, from manufacture full range.
PART 3 EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with the Applicator present, under which
painting will be performed for compliance with paint application requirements.
B. Do not begin to apply paint until unsatisfactory conditions have been corrected and
surfaces receiving paint are thoroughly dry.
E. Notify the Engineer about anticipated problems using the materials specified over
substrates primed by others.
B. Cleaning: Before applying paint or other surface treatments, clean the substrates of
substances that could impair the bond of the various coatings. Remove oil and
grease before cleaning.
1. Schedule cleaning and painting so dust and other contaminants from the
cleaning process will not fall on wet, newly painted surfaces.
3. Wood: Clean surfaces of dirt, oil, and other foreign substances with scrapers,
mineral spirits, and sandpaper, as required. Sand surfaces exposed to view
smooth and dust off.
a. Scrape and clean small, dry, seasoned knots, and apply a thin coat of
white shellac or other recommended knot sealer before applying
primer. After priming, fill holes and imperfections in finish surfaces with
putty or plastic wood filler. Sand smooth when dried.
b. Prime, stain, or seal wood to be painted immediately on delivery. Prime
4. Ferrous Metals: Clean ungalvanized ferrous-metal surfaces that have not been
shop coated; remove oil, grease, dirt, loose mill scale, and other foreign
substances. Use solvent or mechanical cleaning methods.
E. Maintain containers used in mixing and applying paint in a clean condition, free of
foreign materials and residue.
F. Tinting: Tint each undercoat a lighter shade to simplify identification of each coat
when multiple coats of the same material are applied. Tint undercoats to match the
color of the finish coat, but provide sufficient differences in shade of undercoats to
distinguish each separate coat.
3.3 APPLICATION
B. Scheduling Painting: Apply first coat to surfaces that have been cleaned, pretreated,
or otherwise prepared for painting as soon as practicable after preparation and
before subsequent surface deterioration.
1. The number of coats and film thickness required are the same regardless of
application method. Do not apply succeeding coats until previous coat has
cured as recommended by manufacturer. If sanding is required to produce a
smooth, even surface according to manufacturer's written instructions, sand
between applications.
2. Omit primer over metal surfaces that have been shop primed and touchup
painted.
3. If undercoats, stains, or other conditions show through final coat of paint,
apply additional coats until paint film is of uniform finish, color, and
appearance. Give special attention to ensure that edges, corners, crevices,
welds, and exposed fasteners receive a dry film thickness equivalent to that of
flat surfaces.
4. Allow sufficient time between successive coats to permit proper drying. Do
not recoat surfaces until paint has dried to where it feels firm, and does not
deform or feel sticky under moderate thumb pressure, and until application of
another coat of paint does not cause undercoat to lift or lose adhesion.
C. Application Procedures: Apply paints and coatings by brush, roller, spray, or other
applicators according to manufacturer's written instructions.
1. Brushes: Use brushes best suited for type of material applied. Use brush of
appropriate size for surface or item being painted.
2. Rollers: Use rollers of carpet, velvet-back, or high-pile sheep's wool as
recommended by manufacturer for material and texture required.
3. Spray Equipment: Use airless spray equipment with orifice size as
recommended by manufacturer for material and texture required.
E. Mechanical and Electrical Work: Painting of mechanical and electrical work is limited
to items exposed in equipment rooms and occupied spaces.
F. Mechanical items to be painted include, but are not limited to, the following:
G. Electrical items to be painted include, but are not limited to, the following:
1. Switchgear.
2. Panelboards.
3. Electrical equipment that is indicated to have a factory-primed finish for field
painting.
4. As indicated on Drawings.
H. Block Fillers: Apply block fillers to concrete masonry block at a rate to ensure
complete coverage with pores filled.
I. Prime Coats: Before applying finish coats, apply a prime coat, as recommended by
manufacturer, to material that is required to be painted or finished and that has not
been prime coated by others. Recoat primed and sealed surfaces where evidence of
suction spots or unsealed areas in first coat appears, to ensure a finish coat with no
burn-through or other defects due to insufficient sealing.
M. Completed Work: Match approved samples for color, texture, and coverage.
Remove, refinish, or repaint work not complying with requirements.
A. Testing of Paint Materials: Employer reserves the right to invoke the following
procedure at any time and as often as Employer deems necessary during the period
when paints are being applied:
a. Brush / roller marks, streaks, laps, runs, sags, drips, heavy stippling,
hiding or shadowing by inefficient application methods, skipped or
missed areas, and foreign materials in paint coatings.
b. Evidence of poor coverage at rivet heads, plate edges, lap joints,
crevices, pockets, corners and re-entrant angles.
c. Damage due to touching before paint is sufficiently dry or any other
contributory cause.
d. Damage due to application on moist surfaces or caused by inadequate
protection from the weather.
e. Damage and/or contamination of paint due to blown contaminants
(dust, spray paint, etc.).
3.5 CLEANING
A. Cleanup: At the end of each workday, remove empty cans, rags, rubbish, and other
discarded paint materials from the site.
3.6 PROTECTION
A. Protect work of other trades, whether being painted or not, against damage by
painting. Correct damage by cleaning, repairing or replacing, and repainting, as
approved by Engineer.
B. Provide "Wet Paint" signs to protect newly painted finishes. Remove temporary
protective wrappings provided by others to protect their work after completing
painting operations.
A. Coordinate the following paint coats with surface preparation steps as specified.
1. Acrylic Paint system for application onto external Portland cement plaster, fair
face concrete, shall be 100% - acrylic water based binder to provide excellent
color retention, UV resistant, very durable, having the ability of bridging the
hairline cracks, offers outstanding protection against destructive effect of UV
rays present in Sunlight and also tested for carbon dioxide diffusion, chloride
ion diffusion water vapor transmission and liquid water transmission.
C. Ferrous Metal and Zinc-Coated Metals: Provide the following finish system over
exterior ferrous metal.
D. Wood Works
1. Clear Varnish for external wood surfaces shall be moisture curing, single
component, polyurethane – based, clear colored as directed by the Engineer
varnish with gloss or matt finish to the selection of the Engineer.
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. SIGNAGE
CAIRO - EGYPT 101400 – 2839 0
SECTION 101400
SIGNAGE
Page
PART 1 GENERAL 2
1.1 Related Documents 2
1.2 Summary 2
1.3 Submittals 2
1.4 Quality Assurance 3
1.5 Project Conditions 3
1.6 Coordination 3
1.7 Warranty 3
PART 2 PRODUCTS 3
2.1 Materials 3
2.2 Dimensional Characters 4
2.3 Panel Signs 4
2.4 Dimensional Characters 5
2.5 Accessories 6
2.6 Fabrication 6
2.7 Finishes, General 6
2.8 Aluminum Finishes 7
2.9 Acrylic Sheet Finishes 7
PART 3 EXECUTION 7
3.1 Examination 7
3.2 Installation 7
3.3 Cleaning And Protection 8
PART 1 GENERAL
1.2 SUMMARY
1. Panel signs.
2. Signage accessories.
1. Division 26 Sections for electrical service and connections for illuminated signs.
1.3 SUBMITTALS
C. Samples for Initial Selection: Manufacturer's color charts consisting of actual units or
sections of units showing the full range of colors available for the following:
1. Aluminum.
2. Acrylic sheet.
D. Samples for Verification: For each type of sign, include the following Samples to
verify color selected:
C. Source Limitations for Signs: Obtain each sign type indicated from one source from a
single manufacturer.
1.6 COORDINATION
1.7 WARRANTY
PART 2 PRODUCTS
2.1 MATERIALS
B. Aluminum Sheet and Plate: ASTM B 209, alloy and temper recommended by
aluminum producer and finisher for type of use and finish indicated, and with at least
the strength and durability properties of Alloy 5005-H32.
D. Acrylic Sheet: ASTM D 4802, Category A-1 (cell-cast sheet), Type UVA (UV absorbing).
A. Cast Characters: Produce characters with smooth flat faces, sharp corners, and
precisely formed lines and profiles, free of pits, scale, sand holes, and other defects.
Cast lugs into back of characters and tap to receive threaded mounting studs. Alloy
and temper recommended by sign manufacturer for casting process used and for use
and finish indicated. Comply with the following requirements.
1. Finish: Anodized.
2. Thickness: As recommended by manufacture.
3. Color(s): As selected by Engineer from manufacturer's full range.
A. Interior Panel Signs: Provide smooth sign panel surfaces constructed to remain flat
under installed conditions within a tolerance of plus or minus 1.5 mm measured
diagonally from corner to corner, complying with the following requirements:
B. Exterior Panel Signs: Provide smooth sign panel surfaces constructed to remain flat
under installed conditions within a tolerance of plus or minus 1.5 mm measured
diagonally from corner to corner, complying with the following requirements:
C. Brackets: Fabricate brackets and fittings for bracket-mounted signs from extruded
aluminum to suit panel sign construction and mounting conditions indicated. Factory
paint brackets in color selected by Engineer.
E. Engraved Copy: Machine engrave letters, numbers, symbols, and other graphic
devices into panel sign on face indicated to produce precisely formed copy, incised to
uniform depth.
1. Use reverse silk-screen process to print copy; overspray the copy with an
opaque background color coating.
B. Aluminum Extrusions: ASTM B 221 (ASTM B 221M), alloy and temper recommended
by the aluminum producer and finisher for type of use and finish indicated, and with
not less than the strength and durability properties of 6063-T5.
1. Material: Aluminum.
D. Cutout Characters: Cut characters from solid plate of thickness and metal indicated.
Produce precisely cut characters with square cut, smooth, eased edges. Comply with
requirements indicated for finish, style, and size.
2.5 ACCESSORIES
2.6 FABRICATION
B. Graphic Content and Style: Provide sign copy that complies with requirements
indicated in the Drawings and in Door Schedule for size, style, spacing, content,
mounting height and location, material, finishes, and colors of signage.
A. Colored Coatings for Acrylic Sheet: For copy and background and frame colors,
provide colored coatings, including inks, dyes, and paints, that are recommended by
acrylic manufacturers for optimum adherence to acrylic surface and that are UV and
water resistant for three years for application intended.
PART 3 EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer present, for compliance
with requirements for installation tolerances and other conditions affecting
performance of work.
B. Verify that items, including anchor inserts, and electrical power are sized and located
to accommodate signs.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Locate signs and accessories where indicated, using mounting methods of types
described and complying with manufacturer's written instructions.
1. Install signs level, plumb, and at heights indicated, with sign surfaces free of
distortion and other defects in appearance.
2. Interior Wall Signs: Install signs on walls adjacent to latch side of door where
applicable. Where not indicated or possible, such as double doors, install signs
on nearest adjacent walls. Locate to allow approach within 75 mm of sign
B. Wall-Mounted Signs: Attach panel signs to wall surfaces using methods indicated
below:
1. Silicone-Adhesive Mounting: Attach signs to irregular, porous, or vinyl-
covered surfaces.
2. Shim Plate Mounting: Provide 3 mm thick, concealed aluminum shim plates
with predrilled and countersunk holes, at locations indicated, and where other
mounting methods are not practicable. Attach plate with fasteners and
anchors suitable for secure attachment to substrate. Attach panel signs to
plate using method specified above.
3. Concealed Mechanical Fasteners: Use nonremovable mechanical fasteners
placed through predrilled holes. Attach signs with fasteners and anchors
suitable for secure attachment to substrate as recommended in writing by the
sign manufacturer.
4. Signs Mounted on Glass: Provide matching opaque plate on opposite side of
glass to conceal mounting materials.
1. Flush Mounting: Mount characters with backs in contact with wall surface.
2. Projected Mounting: Mount characters at projection distance from wall
surface indicated.
A. After installation, clean soiled sign surfaces according to the manufacturer's written
instructions. Protect signs from damage until acceptance by the Employer.
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. PEDESTRIAN CONTROL EQUIPMENT
CAIRO - EGYPT 111400 – 2839 0
SECTION 111400
Page
PART 1 GENERAL 2
1.1 Related Documents 2
1.2 Summary 2
1.3 Submittals 2
1.4 Quality Assurance 2
1.5 Delivery, Storage And Handling 3
1.6 Coordination 3
1.7 Warranty 3
PART 2 PRODUCTS 3
2.1 Material 3
2.2 Wing Access Gate 3
2.3 Full Height Turnstiles 4
2.4 Fabrication 4
2.5 Stainless Steel Finishes 5
2.6 Steel And Iron 5
PART 3 EXECUTION 6
3.1 Installation, General 6
3.2 Field Quality Control 6
3.3 Protection 6
3.4 Demonstration 6
PART 1 GENERAL
1.2 SUMMARY
1.3 SUBMITTALS
B. Samples for Initial Selection: Manufacturer's color charts showing the full range of
colors available for products with factory-applied color finishes.
C. Samples for Verification: For each type of exposed finish required, prepared on
components indicated below and of same thickness and metal indicated for the
Work. If finishes involve normal color and texture variations, include sample sets
showing the full range of variations expected.
B. Source Limitations: Obtain each type of pedestrian control devices through one
source from a single manufacturer.
B. Store off ground, under cover, protected from weather and construction activities.
1.6 COORDINATION
1.7 WARRANTY
A. Special Warranty: Provide written warranty signed by the Manufacturer and the
Contractor in which manufacturer agrees to repair or replace products that fail in
materials or workmanship within specified warranty period. Failures include, but are
not limited to, the following:
PART 2 PRODUCTS
2.1 MATERIAL
A. General: Provide metal free from pitting, seam marks, roller marks, stains,
discolorations, and other imperfections where exposed to view on finished units.
B. Brackets, Flanges, and Anchors: Cast or formed metal of same type of material and
finish as supported rails, unless otherwise indicated.
C. Brackets, Flanges, and Anchors: Cast or formed metal of same type of material and
finish as supported rails, unless otherwise indicated.
2.4 FABRICATION
B. Assemble products in shop to greatest extent possible to minimize field splicing and
assembly. Disassemble units only as necessary for shipping and handling limitations.
C. Provide sleeves, inserts, and other anchorage devices to connect unit systems to
concrete, masonry, embedded steel plates, and structural steel work. Fabricate
anchorage devices capable of withstanding loads imposed by systems. Coordinate
anchorage devices with supporting structure.
D. Glazing Channels: Provide minimum clearances for thickness and type of glass
indicated according to GANA's "Glazing Manual."
A. Remove or blend tool and die marks and stretch lines into finish.
1. Install pedestrian control devices plumb and true on a level floor in alignment
with established lines and grades without warp or rack of framing members
and doors. Anchor securely in place.
2. Installation shall not begin until these unacceptable conditions are rectified.
C. Adjustment: Installer shall adjust door and hardware for smooth operation and
proper performance.
E. Activation Devices: Adjust devices to provide detection field and functions indicated.
F. Cleaning: Clean metal and glass surfaces carefully after installation to remove excess
caulk, dirt and labels.
A. Engage an inspector to test and inspect pedestrian control devices and prepare test
and inspection reports.
B. Repair or remove work where test results and inspections indicate that it does not
comply with specified requirements.
3.3 PROTECTION
A. Protect finishes from damage during construction period with temporary protective
coverings approved by the manufacturer. Remove protective coverings at the time
of Substantial Completion.
3.4 DEMONSTRATION
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. PARKING CONTROL EQUIPMENTS
CAIRO - EGYPT 111500 – 2839 0
Page
PART 1 GENERAL 2
1.1 Related Documents 2
1.2 Summary 2
1.3 Submittals 2
1.4 Quality Assurance 2
1.5 Project Conditions 3
1.6 Delivery, Storage And Handling 3
PART 3 EXECUTION 4
3.1 Examination 4
3.2 Installation 4
3.3 Field Quality Control 5
3.4 Adjusting 5
3.5 Cleaning 5
3.6 Demonstration, Testing And Acceptance 5
3.7 Protection 5
PART 1 GENERAL
1.2 SUMMARY
1.3 SUBMITTALS
C Wiring Diagrams: Detailing wiring for parking control equipment operator, signal, and
control systems differentiating clearly between manufacturer-installed wiring and
field-installed wiring.
D Maintenance Data.
B Single-Source Responsibility: Obtain parking control equipment from one source and
from a single manufacturer.
B Store materials in weather tight and dry storage facility. Protect from damage due to
handling, weather, and construction operations before, during and after installation.
2.1 MATERIALS
B Structural tubing in rounds and shapes: A500; Cold-Formed Welded and Seamless
Carbon Steel Structural Tubing in Rounds and Shapes.
A General: Heavy duty automatic rising barrier, especially designed for lanes of width
indicated on Drawings. Comply from the following features:
1. Housing: Made of folded and welded 10-gauge galvanized steel sheet, seam
welded, reinforced internally with welded steel angles and angle framing, tamp
proof hardware, and weather tight gaskets.
a. Four mounting holes shall be provided for securing the cabinet to the
mounting pad. Mounting holes shall be readily accessible through the
cabinet door.
b. Lateral door side mounted for easy access to mechanism. The door will
be secured to the cabinet by a lock only accessible with a specific key.
c. Finish: Manufacture standard, polyester powder coating
PART 3 EXECUTION
3.1 EXAMINATION
2. Verify that anchor bolts, and are ready to receive work and dimensions are as
indicated on shop drawings and as instructed by manufacturer.
3. Verify that electric power is available and of correct characteristics.
3.2 INSTALLATION
B Perform the following field tests and inspections and prepare test reports:
1. Controls and safeties shall be tested and adjusted. Report any damaged and
malfunctioning controls and equipment.
C Remove and replace parking control equipment where test results indicate that it
does not comply with specified requirements.
3.4 ADJUSTING
A Prior to final acceptance of project, adjust system components for smooth operation.
3.5 CLEANING
A Clean metal surfaces promptly after installation, exercising care to avoid damage to
coatings. Touch up damaged shop-applied finishes as required to restore damaged
areas.
3.7 PROTECTION
A Protect parking control equipment finished surfaces from damage during erection,
and after completion of work until final inspection and acceptance.
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. EARTHWORK
CAIRO - EGYPT 312000 - 2839 0
SECTION 312000
EARTHWORK
Page
PART 1 GENERAL 2
1.1 Related Documents 2
1.2 Summary 2
1.3 Reference Standards 2
1.4 Related Sections 3
1.5 Submittals 3
1.6 Definitions 4
1.7 Project Conditions 5
1.8 Use Of Explosives 6
1.9 Contractor's Responsibility 6
PART 2 PRODUCTS 7
2.1 Soil Materials 7
2.2 Warning Tape 9
2.3 Water 10
2.4 Equipment 10
PART 3 EXECUTION 10
3.1 Open-Cut Excavation, General 10
3.2 Excavation For Structures 12
3.3 Approval Of Subgrade Bottom 13
3.4 Footing Subgrade 14
3.5 Backfilling Around Foundations 14
3.6 Soil Replacement Under Foundations And Above Water Level 15
3.7 Field Quality Control: 15
3.8 Auxiliary Works 16
3.9 Tolerance Limits 16
3.10 Surface Finish 16
3.11 Disposal 17
PART 1 GENERAL
A. Drawings and general provisions of the Contract, including Contract Conditions and
Division 1 Specification Sections, apply to work of this section.
1.2 SUMMARY
A. Earth works including cut, fill and backfilling and grading works shall be performed in
compliance with Drawings, tests and the requirements of the project, and the
specifications of the American Society of Testing and Materials (ASTM) as noted
below:
ASTM No.
ASTM C131 Standard Test Method for Resistance to Degradation of Small Size
Coarse Aggregate by Abrasion and impact in the Los Angeles
Machine.
ASTM C136 Sieve Analysis of Fine and Coarse Aggregates
ASTM C142 Clay Lumps and Friable Particles in Aggregates
ASTM D421 Practice for Dry Preparation of Soil Samples for Particle Size Analysis
and Determination of Soil Constants
ASTM D422 Particle Size Analysis of Soils
ASTM D427 Shrinkage Factors of Soils
ASTM D512 Chloride Ion in Water
ASTM D516 Sulfate Ion in Water
ASTM D638 Tensile Properties of Plastics
ASTM D698 Moisture Density Relation of Soils and Soil Aggregate Mixtures
ASTM D854 Specific Gravity of Soils
ASTM D1293 pH of Water
1.5 SUBMITTALS
A. Submit the following in accordance with Conditions of the Contract and Division-1
Specification Sections:
1. 2 kg samples sealed in airtight containers, of each proposed fill and backfill soil
material from on-site or borrow sources
2. 300 mm long of each type of plastic warning tape
3. 300 x 300 mm samples of drainage fabric
G. Detailed design of temporary side slopes and side support system (if any) for
approval.
1.6 DEFINITIONS
A. Borrow soil: Satisfactory soil imported from off-site for use as fill or backfill.
D. Rock Fill: Material composed of hard, sound, durable rock with only a small amount
of fine particles used for filling or back filling
E. Sub-base Course: Course placed between the subgrade and base course for hot-mix
asphalt pavement, or course placed between the subgrade and a cement concrete
pavement or a cement concrete or hot-mix asphalt walk.
F. Retain definitions that remain after this Section has been edited. Revise to suit office
or local earthwork practices.
G. Base Course: Course placed between the sub-base course and hot-mix asphalt
paving.
H. Bedding Course: Course placed over the excavated subgrade in a trench before
laying pipe.
I. Revise heading in first paragraph below to read "Capillary Water Barrier" or a similar
title if required.
J. Drainage Course: Course supporting the slab-on-grade that also minimizes upward
capillary flow of pore water.
B. A geotechnical report has been prepared for this project and is available. The
opinions expressed in this report, the design and drawings are those of the
geotechnical engineer and represent interpretations of the subsoil conditions, tests,
and results of analyses conducted by the geotechnical engineer.
C. The Contractor shall carry out his own site investigations and shall inform and satisfy
himself as to the character, quality and distribution of all material to be excavated,
filled, spoiled and borrowed. The Contractor shall be fully responsible for asserting
necessary information concerning permanent water-table, period of rainfall and all
matters affecting the excavation and foundation work.
D. The contractor is responsible to verify the required different levels before starting
construction works.
E. Before starting any construction works compacting the top surface is required to
assure the quality of compaction.
F. Topographic Survey: Do not assume accuracy of the existing benchmark, and run a
closing survey of the existing project area and take cross-sectional elevations and
levels of the works on the Site and submit the result to the Engineer for approval, as
quantities of excavation, earthwork etc., shall be measured from these levels as
agreed and signed by the Engineer.
A. Blasting and use of explosives is prohibited. Do not bring explosives onto Site or use
in work.
A. The methods of excavation which the Contractor desires to use shall be at the sole
discretion of the Contractor.
B. The Contractor shall perform all excavation and backfilling as required for all works
under this Contract. Excavations shall be carried out in all materials, by whatever
means necessary and shall be performed accurately to the lines, levels and grades
shown on Drawings.
C. Except where indicated on the Drawings to remain undisturbed, the Contractor shall
remove all unaccepted topsoil, plants, roots, vegetation, rubbish, rock, etc., from
areas lying within limits of structures and from area to receive fill, embankment,
surfacing, road construction, concrete or other constructions.
E. In the event of a fall occurring in any excavation the Contractor shall carry out at his
own expense and to the satisfaction of the Engineer any re-excavation reinstatement
or repairs which may become necessary as the result of such fall. Any voids caused
by a fall shall be filled and consolidated as directed by the Engineer.
F. Protection of Persons and Properties: The Contractor shall erect temporary fencing
or barricade open excavations occurring as part of this work and post with warning
lamps and take all necessary steps to prevent any entry of public to the vicinity of
open excavation. He shall protect structures and utilities from damage caused by
settlement, lateral movement, undermining, washout and other hazards created by
earthwork operations.
G. The Contractor shall restore and repair any damage or defects caused to adjacent
structures, utilities or properties without responsibilities or extra charge to the
Employer.
PART 2 PRODUCTS
A. General: Provide borrow soil materials when sufficient satisfactory soil materials are
not available from excavations.
B. Topsoil: Natural and cultivated surface-soil layer containing organic matter and sand,
silt and clay particles, friable, pervious, and black or darker shade of brown, gray or
red than underlying subsoil, reasonably free of subsoil, clay lumps, gravel, and other
objects more than (50mm) in diameter, and free of subsoil and weeds, roots, toxic
materials, or other non-soil materials.
D. Structural fill shall be used underneath the structures and under slab on grade.
E. The source of the Engineering fill shall be provided by the Contractor and approved
by the Engineer. The Contractor shall provide samples at specified intervals to
monitor the material, and to the Engineer satisfaction.
F. Engineering fill shall be used underneath the structures, roads, shoulders and paved
areas and under slab on grade as specified in the geotechnical report.
Table 1
Table 2
Selected Fill
1. For depth from 3.0 m to 10.0 m (under buildings area) with max. Fines
percentage 20% and min. compaction percentage 85% (as stated in table 3).
2. For depth from 2.0 m to 10.0 m (under roads and parking area) with max. Fines
percentage 25% and min. compaction percentage 85%.
3. Landscape area and non-loaded area (non-structural fill) with max. Fines
percentage 25%, min. compaction percentage 85% and the maximum
thickness for each layer is 700 mm.
I. Maximum dry density and optimum moisture content shall be determined based on
Modified Proctor Test according to ASTM D 1557.
J. Backfilling material uses under buildings specifications and criteria are stated in the
following table:
Table 3
Table 4
L. Backfilling material uses under roads and parking areas specifications and criteria are
stated in the following table:
M. Bedding for Underground Utility Installation: Bedding shall be granular, well graded,
with all material passing 12.5 mm (1/2 inch) mesh screen and at least 90 percent
retained on 75 µm (No. 200) sieve as determined in accordance with ASTM D 422.
N. Trench Backfill (Within the Pipe Zone): Trench backfill shall contain no rocks or
stones larger than 25 mm in the greatest dimension and shall be free of vegetation,
trash, chunks of highly plastic clay, or other unsatisfactory- material. Trench backfill
placed under roadways or structures shall meet the requirements of engineering fill.
A. Acid- and alkali-resistant polyethylene film warning tape for marking and identifying
underground utilities 150 mm wide and 4 mils thick, continuously inscribed with a
description of the utility; colored as follows:
1. Red: Electric
A. Water used for soil compaction shall be clean and free from unusual proportions of
dissolved salt, organic matters and industrial contamination oils, acids or other
deleterious matter.
B. Water shall not contain chemical salts including sulfates (SO3) and chlorides (Cl) in a
percentage that shall increase the overall salts percentage for filling materials more
than 0.35%.
C. For the water used in compaction process, water sample from wells and/or any
source shall be tested to satisfy the previous limits.
2.4 EQUIPMENT
A. Use types of equipment that are most suitable for the work and of numbers, sizes
and capacities that can perform earthwork as specified within the time schedule.
Equipment for earthwork shall be operated in strict accordance to manufacturer's
instructions and recommendations and shall be always maintained by the Contractor
in such condition that they shall deliver manufacturer's rated capacities.
PART 3 EXECUTION
A. Should the Contractor through negligence or other fault excavate or fill beyond the
designated lines, he shall replace/remove such excavation/fill in an approved manner
and condition at his own expense with satisfactory soil materials and thoroughly
compact to a density equal to adjacent original ground.
B. Do not neglect to check for underground services, which may not initially appear to
be of interest. Protect utilities, structures, improvements, pavement from damage
caused by settlement due to lateral movement created by earthwork operations.
B. Survey points, benchmarks, boundary stones and the like shall be removed only with
the engineer’s written consent.
C. Removed boundary stones and marking shall be stored according to the engineer
instructions.
E. For all fill and cut over 1 m in height, sturdy stakes shall be placed at any changes of
direction of the ground but in all cases at intervals not greater than 30 m as directed
by the engineer.
F. Permanent slope (if any) to be kept in the sand it shall be stabilized by one of the
following means:
G. The quantity, type and capacity of the equipment provided, the work method
envisaged transportation and distribution of the excavated materials, location of
stock-piles, main storage areas as well as the approximate number of laborers, etc.
and the working schedule and any amendment to it during the construction period
shall require the engineer’s period approved.
L. The Contractor shall make his own estimate of the kind and extent of the various
materials and presence or absence of water which shall be encountered in the
excavation.
M. The final 150 mm depth of all excavations shall be taken out manually or otherwise if
accepted by the Engineer and the bottom levelled and rammed immediately prior to
placing structures.
O. Stockpile soil materials suitable for backfill at sufficient distance away from edge of
excavation and neatly pile in stock piles in a manner that shall not overload or cause
collapse of excavation sides. All unsuitable and surplus excavated materials shall be
immediately removed from site, loaded and transported to dumps approved by local
authorities.
P. Extend excavations a sufficient distance from structures for placing and removing
concrete formwork, for installing services and other construction, for inspection.
R. No back-throwing whatever shall be allowed and all materials shall be brought to the
surface and formed in heaps clear of excavation.
T. Over Excavation: If somewhere and for any reason excavations are executed beyond
the established lines and without the engineer’s previous approval, the Contractor
shall backfill with lean concrete or other approved materials, the volume
corresponding to the over excavation.
W. The excavation shall at all times be well drained, kept free from storm water,
percolating water or subsoil water.
X. The Contractor shall make good at his own expense any damage that may result from
his failure to keep the excavation free from water.
A. Excavation Limits for Structures: Banks shall be either shored or sloped at a safe
angle according to conditions and to the approval of the Engineer. If necessary
extend a reasonable sufficient distance from footing and foundations to permit
placing and removal of concrete form work, shoring, installation of services and other
constructions, for performing all works in the excavation and for inspection. No
compensation shall be paid to the Contractor in respect to excavation or backfilling of
extended distances.
B. If any part of an excavated area is in error or excavated wider than required, the
excess excavated distance shall be backfilled as directed by the Engineer and
compacted at the Contractor's charge.
A. When excavation has reached required subgrade elevations, the Engineer shall
inspect soil materials at these elevations for suitability as a foundation level for the
related construction, and he may instruct the Contractor to test the bearing capacity
of the soil at this level. Should the bottoms of excavation be found to be unsuitable
as bearing surfaces as a result of such tests, the Engineer may decide to continue
excavation until suitable bearing materials are encountered and replace with
compacted backfill. Additional excavation and replacement material shall be paid for,
according to Contract.
B. Excavated materials shall not be piled up along sides of excavations in a manner that
will overload or cause collapse of excavation sides.
C. Sub-soil from the excavation shall be selected for suitability for backfilling and
compaction, shall be free from any organic materials and shall not have big lumps. It
shall be placed directly in its final position or stacked on site as directed by the
Engineer in the vicinity of the work and those unsuitable for fill shall be removed
from site to a tip provided by the Contractor. All other filling materials shall be
imported.
D. Cleaning, grubling and removal of trash and debris from excavation shall be done
before backfilling works.
F. Compaction areas shall be kept separate and no layer shall be covered by another
until the proper density is obtained.
I. The soil used in backfilling shall be mixed with sufficient water to provide a moisture
content within a range of 2% from the optimum value. The mixing process shall be
completed out of backfill area then soil shall be spread in loose lifts and compacted
at designated locations. The moisture content shall be uniform throughout the
compacted layer. If the field quality testing as specified in Clause 3.9 revealed
moisture content out of the previously specified range, the soil shall be removed,
remixed and compacted again.
J. The Engineer, at his own discretion, may allow greater lift thickness not exceeding
350 mm thick if proper density and uniformity is obtained. Effective spreading
equipment shall be used on each lift to obtain uniform thickness prior to compacting.
As the compaction of each layer progresses, continuous levelling and manipulating
shall be required to assure uniform density. Water shall be added in order to obtain
the correct water content and the required density on stocked soil outside the
excavation. Construction equipment shall be routed uniformly over the entire
surface both in width and longitudinal extent of each layer before the next lift is
started. At the start of the work a field test shall be performed in the Site over an
adequate area not less than 100 m2 to determine the allowable thickness of layers
K. Pipes and reinforced concrete foundation members such as tie-beams laid on natural
ground shall be protected with a minimum of 1000 mm of tamped fill over the top
surface or according to Drawings before heavy equipment is allowed to pass over.
L. Backfill excavations shall start as promptly as work permits, but not until completion
of the following:
M. Pipes and reinforced concrete foundation members such as tie beams laid on natural
ground shall be protected with a minimum of 1000 mm of tamped fill over the top
surface or according to Drawings before heavy equipment are allowed to pass over.
R. After installation of pipes and cables according to specifications and all related tests
are performed and approved by Engineer.
A. Unless otherwise indicated on Drawings, the subgrade under footings and tie-beams
shall be prepared in the following sequence:
1. Excavate under footing and tie-beams down to the required depth from
existing ground surface.
2. Clean bottom of excavation from the loose surface soil skin and compact the
soil using suitable compaction equipment.
3.5 BACKFILLING AROUND FOUNDATIONS
A. Use selected fill materials as specified in Clause 2.1 and compact mechanically or by
manual tamping to 90% of maximum dry density according to ASTM D 1556 at
optimum moisture content during excavation.
A. Allow testing agency to inspect and test each subgrade and each fill layer.
B. Compaction and field density tests of in-place soil or the fill shall be made at each
location directed by the Engineer at the rate of one (1) test every 250 m2 for each
compacted layer according to ASTM D1556.
C. One plate loading test/1500 m2, with minimum of two tests for each plot, shall be
carried out at foundation level of natural granular soil or the top of the replacement
layer (if existing), or as directed by the Engineer.
In case of the existence of replacement soil with thickness equal to or bigger than
1.50 m, then the same number of tests shall be carried out at the middle of the layer
The test shall be carried out dry and soaked to check the soil collapsibility as per the
Egyptian code and shall satisfy the following:
1. The steel plate diameter at least 450 mm.
2. The stress of the test should be not less than three times the net allowable
bearing capacity at the foundation level.
3. The submergence is to occur at stress equals the net allowable bearing
capacity at the foundation level.
4. The value of deformation modulus, Es should be not less than 500 Kg/cm2
D. Field density tests shall be performed in accordance with AASHTO T-191 (sand cone
method). The Contractor shall perform the following tests at locations as directed by
the Engineer:
1. Laboratory test for Maximum Dry Density (MDD), Optimum moisture content,
for each layer.
2. Field density and California Bearing Ratio (CBR), for each layer as required by
the Engineer.
3. The areas shall be rejected if the resulting test results do not satisfy specified
requirements.
4. The Contractor shall be responsible for making good all settlement of filling
that may occur at/to the end of the Defect Liability Period.
A. Unless otherwise specified, all and any kind of works, materials, services, safety
measures, etc. as well as, and if so requested by the Engineer, all tests and samples
required for the completion of the work shall be for the responsibility of the
Contractor. The auxiliary works comprises, but not limited to the following:
A. The tolerance limits for the permanent finished earthworks will be as follows:
A. The top surface area shall be of dense and level without any protruding rock
fragments in excess of 50 mm, recesses of soft spots to the satisfaction of the
engineer.
A. Remove, only by night, surplus satisfactory soil and waste material including
unsatisfactory soil, trash, debris, and legally dispose of it off to the public disposal
areas.
SPECIFICATION REV.
ECG ENGINEERING CONSULTANTS GROUP S.A. DECORATIVE METAL FENCES AND
CAIRO - EGYPT GATES 323119 – 2839 0
SECTION 323119
Page
PART 1 GENERAL 2
1.1 Summary 2
1.2 Performance Requirements 2
1.3 Submittals 2
1.4 Quality Assurance 2
PART 2 PRODUCTS 2
2.1 Materials 2
2.2 Ornamental Steel Fence and Swinging Gate 3
2.3 Cast-In-Place Concrete 3
2.4 Steel Finishes 4
PART 3 EXECUTION 4
3.1 Gate Installation 4
3.2 Gate Operator Installation 4
3.3 Adjusting 4
PART 1 GENERAL
1.1 SUMMARY
1. Minimum Post Size and Maximum Spacing for Wind Velocity Pressure,
determine based on mesh size and pattern specified:
2. Wind Speed.
1.3 SUBMITTALS
B. Mockups: Build mockups to set quality standards for fabrication and installation.
PART 2 PRODUCTS
2.1 MATERIALS
C. Steel Rails and Bars: Hot-rolled, carbon steel complying with ASTM A 29M,
Grade 1010.
1. Gray Iron: ASTM A 48/A 48M, Class 30, unless another class is indicated or
required by structural loads.
2. Malleable Iron: ASTM A 47/A 47M.
E. Brackets, Flanges, and Anchors: Cast or formed metal of same type of material and
finish as supported rails, unless otherwise indicated.
A. General: Fabricate ornamental steel fence to designs indicated from steel bars and
shapes of sizes and profiles indicated. Form steel bars by bending, forging, coping,
mitering, and welding.
D. Point steel ends in precast concrete with non-shrink grout as specified. Finish
pointing grout neat and flush with adjoining concrete surface.
A. Materials: Portland cement complying with ASTM C 150, Type I aggregates complying
with ASTM C 33, and potable water.
1. Concrete Mixes: Normal-weight concrete with not less than 20.7- MPa
compressive strength 28 days, 75-mm slump, and 25-mm maximum size
aggregate.
A. Galvanized Coating: Steel sections and other accessories shall be hot dip galvanized
after fabrication to ASTM A123. Zinc coating intensity shall be 600 g/m2, minimum.
B. Field Applied Finish: Polyurethane paint over epoxy primer system as as specified in
Division 9 Section “Painting”.
PART 3 EXECUTION
A. Install gates plumb, level, and secure for full opening without interference. Install
ground-set items in concrete for anchorage. Adjust hardware for smooth operation
and lubricate where necessary. Install gates according to the manufacturer's
instructions, plumb, level, and secure.
B. Advise and consult with the Engineer to obtain the Employer's requirements for
standard available programmable features or adjustable controls (such as time
delays, interlocks, or safety devices), and make necessary adjustments.
3.3 ADJUSTING
A. Gate: Adjust gate to operate smoothly, easily, and quietly, free from binding, warp,
excessive deflection, distortion, nonalignment, misplacement, disruption, or
malfunction, throughout entire operational range..