Professional Documents
Culture Documents
N6166 - E05 - F514 - MV - SBEF - Relay - 7SJ61 Site Test Report
N6166 - E05 - F514 - MV - SBEF - Relay - 7SJ61 Site Test Report
Built-in rated auxiliary voltage (DC): 110 -250 VDC Feeder : =E05 - Transformer T202
Functions
Enabled Disabled
IEC No. Description
Description
50N/51N Earth fault Protection Enabled
F - LED function
Inject current in the relay as per the table below. Observe the reading on the relay display, in secondary values and in
Primary values. Inject Current through the test switch -X510
CT RATIO: 2500/1 A
2.3 Earth Fault function (IDMT- Normal inverse curve ): 51N 0.14
T= .TP [s]
0.02
[(I/IP) - 1]
Instruments Used
Remark :
- Omicron print outs will be attached along with the test report for Pickup/Drop off & Characteristics
Company: Siemens
Test Person: Josip Spolador
Testmodules Checked: 9
Testmodules Passed: 9
Substation/Bay:
Substation: 132/11 kV SS ADNEC Substation address:
Bay: 40MVA Transformer 2 Bay address: =E05-T202
Device:
Name/description: MV SBEF 7SJ61 Manufacturer: SIEMENS
Device type: 7SJ6111-5EB90-1FA0 Device address: =E05+R1-F514
Serial/model number: BF1108116125
Additional info 1: MV Winding SBEF Relay
Additional info 2:
Hardware Configuration
Test Equipment
Type Serial Number
CMC256-6 JG655S
Hardware Check
Performed At Result Details
23/08/2012 10:48:48 Passed
IE:
Current output 1 ---> -X514: 26,28
Instruction Text:
Disable IDMT , and enable 50N-1 DMT
Instruction Text:
Disable DMT , and enable 51N IDMT
10000.0
1000.0
100.0
t/s
10.0
1.0
51N SBEF
Mode selection:
Information or instruction
Instruction Text:
Settings: IEp>=0.2A; T-IEp=0.5; IEC Normal Inverse
IE>=0.5A; T-IE>=1.0; DT
IE>>=1A; T-IE>>=0.5; DT
End of Test