: 461116-100127-43636-0005
Doc No:
GFDP-107-52-ELE-DS-GE-005
PETRONAS
Date:
07-Jul-2014
TypicalDatasheet
Data Sheet for Well Pad Distribution Rev: Page
for Distribution Transformer for Transformers
GIFT Offsite Facilities Substation
3 1 of 7
FOR
Class 1
Internal Ctrl. No.: 461116-100127-43636-0005
REVISION HISTORY
Typical Data
Datasheet forSheet for Well
Distribution Pad Distribution
Transformer for GIFT Transformers
Offsite Facilities Substation
16 C AREA CLASSIFICATION
17 1 SAFE / HAZARDOUS SAFE
18 2 INDOOR / OUTDOOR OUTDOOR, UNDER SUN SHADE
19
20 D SYSTEM CHARACTERISTICS
21 1 PRIMARY SYSTEM:
22 1.1 VOLTAGE 33kV ±10%
23 1.2 NO. OF PHASES / WIRE 3 PHASE / 3 WIRE
24 1.3 SYSTEM GROUNDING SOLID GROUNDING
25 1.4 SYMMETRICAL FAULT LEVEL (R.M.S) 25 kA
26 2 SECONDARY SYSTEM:
27 2.1 VOLTAGE (FULL LOAD) 400V
28 2.2 NO. OF PHASES / WIRE 3 PHASE / 4 WIRE
29 2.3 SYSTEM GROUNDING SOLID GROUNDING
30
31 E TECHNICAL PARTICULARS
32 1 RATING 300kVA
300 kVA (To be confirmed during detailed design)
33 2 NO. OF PHASES THREE
34 3 VOLTAGE RATIO : PRIMARY / SECONDARY 6.6/0.42kV
33 / 0.42kV
35 4 VECTOR GROUP Dyn 11
36 5 FREQUENCY 50Hz ±2%
37 6 % IMPEDANCE VOLTAGE 4%
38 7 TYPE OF COOLING ONAN
KNAN
39 8 INSTALLATION OUTDOOR UNDER SUN SHADE
40 9 INSULATION LEVEL
41 10 a) FOR IMPULSE TEST PRY-170kV, SRY-Not applicable AS PER IEC 60076
42 b) FOR POWER FREQUENCY PRY-70kV, SRY-3kV rms AS PER IEC 60076
43 11 TEMPERATURE RISE:
44 a) WINDING 50°C OVER 55°C AMBIENT (HOT SPOT)
45 b) OIL 45°C OVER 55°C AMBIENT
46 12 TYPE OF TRANSFORMER (CONSERVATOR / SEALED) HERMETICALLY SEALED TYPE
47 13 ADDITIONAL BUSHING FOR NEUTRAL EARTHING :
48 a) FOR PRIMARY NOT REQUIRED
49 b) FOR SECONDARY REQUIRED
50 c) EARTH CONDUCTOR SIZE (SEE NOTE-6)
51 14 TAP CHANGER : HV SIDE OFF CIRCUIT
52 RANGE OF TAPS / STEPS ±5% IN STEPS OF 2.5% (+5%, +2.5%, 0, -2.5%, -5%)
53 ON LOAD TAP CHANGER : AUTO & MANUAL NOT APPLICABLE
54 15 PROTECTIVE CT's
55 HV SIDE : (PRIMARY) NOT APPLICABLE
56 LV SIDE : (SECONDARY) NOT APPLICABLE
57
Internal Ctrl. No.: 461116-100127-43636-0005
Typical Data
Datasheet Sheet forTransformer
for Distribution Well Pad Distribution Transformers
for GIFT Offsite Facilities Substation
3 INFORMATION BY BUYER
4 LV SIDE : (NEUTRAL) APPLICABLE
5 CT-3 RATIO 500/1A
6 ACCURACY CLASS, BURDEN 5P20, 10VA
7 16 MOUNTING OF CT's (LOCATION) :
12
13 F CONSTRUCTION
19 6 RADIATOR (*)
21 8 FITTINGS & ACCESSORIES (MINIMUM) PROTECTION RELAY (DGPT2) WITH ALARM & TRIP CONTACTS
24 BREATHER
25 DRAIN/SAMPLING VALVE
26 FILTER VALVE
34
40
41
44
45
46
47
48
49
50
51
52
53
54
55
56
Internal Ctrl. No.: 461116-100127-43636-0005
Typicalfor
Datasheet Data Sheet for
Distribution Well Pad Distribution
Transformer Transformers
for GIFT Offsite Facilities Substation
30
Datasheet forData
Typical Distribution Transformer
Sheet for Well Padfor GIFT OffsiteTransformers
Distribution Facilities Substation
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
Internal Ctrl. No.: 461116-100127-43636-0005
GARRAF FINAL DEVELOPMENT PLAN (GFDP)
4 NOTES:
6 1. (*) TO BE PROVIDED AND GUARANTEED BY VENDOR. VENDOR TO PROVIDE ALL OTHER REQUIREMENTS AS PER SPECIFICATION.
7 2. PERFORMANCE DATA SHALL BE FURNISHED FOR MAXIMUM RATING.
8 3. LOSSES SHALL BE INCLUSIVE OF POSITIVE TOLERANCE AND SHALL BE IN NOMINAL TAP.
9 4. LANGUAGE OF DOCUMENTS AND LANGUAGE ON EQUIPMENTS SHALL BE ENGLISH
10 5. DRAWING, DATAS AND TEST CERTIFICATES SHALL BE AS PER GFDP-COM-52-ELE-SP-GE-005
11 6. CABLE, GLAND SIZES FOR TERMINAL BOXES ARE ON HOLD AND SHALL BE UPDATED BY EPC CONTRACTOR DURING DETAILED ENGINEERING.
12 7. RATINGS SHALL BE UPDATED BY THE EPC CONTRACTOR BASED ON FINAL VENDOR DATA DURING DETAILED ENGINEERING.