Duplex 

and Triplex for MCTC‐MCB‐C‐SJ   
Lifts can be connected in Duplex and Triplex. 
Both of Duplex and Triplex are based on CANBUS communication by 
different wiring connection and setting including parameter and 
jumpers. 
 Different of connection 
 Duplex   
Two lifts can be connected to each other by one cable to make them in 
duplex. 

 
 Triplex   
Triplex connection is based on one GCB board (Group Control Board). 3 
lifts should be connected to GCB board. 

 
 Different of Parameters setting 
 Duplex: 
Main lift: F6‐07=2, F6‐08=1, F6‐09 bit3=1 
Vice lift: F6‐07=2, F6‐08=2, F6‐09 bit3=1 
 Triplex: 
1. F6‐07 should set 3 at all 3 lifts. 
2.  F6‐08=1  at  lift  1  which  connect  with  CN7;  F6‐08=2  at  lift  2  which 
connect with CN9; F6‐08=3 at lift 3 which connect with CN8. 
3. F6‐09 bit3=1 at all 3 lifts. 
 Jumper setting 
 Duplex and Triplex 
MCB jumper J5 and CTB jumper J2 setting are same on both lift, as 
below. 