and Triplex for MCTC‐MCB‐C‐SJ
Lifts can be connected in Duplex and Triplex.
Both of Duplex and Triplex are based on CANBUS communication by
different wiring connection and setting including parameter and
jumpers.
Different of connection
Duplex
Two lifts can be connected to each other by one cable to make them in
duplex.
Triplex
Triplex connection is based on one GCB board (Group Control Board). 3
lifts should be connected to GCB board.
Different of Parameters setting
Duplex:
Main lift: F6‐07=2, F6‐08=1, F6‐09 bit3=1
Vice lift: F6‐07=2, F6‐08=2, F6‐09 bit3=1
Triplex:
1. F6‐07 should set 3 at all 3 lifts.
2. F6‐08=1 at lift 1 which connect with CN7; F6‐08=2 at lift 2 which
connect with CN9; F6‐08=3 at lift 3 which connect with CN8.
3. F6‐09 bit3=1 at all 3 lifts.
Jumper setting
Duplex and Triplex
MCB jumper J5 and CTB jumper J2 setting are same on both lift, as
below.