[Meaning] When current in the electric motor exceeds limit value(If over current [Countermeasures]
occurs,stop switching in order to prevent damages on motor and 1. Check VB connector on DPC-140 PCB.
inverter devices).
2. Verify that HCT cable is properly connected to U and V of HCT.
3. Check a proper connection HCT direction (Normal if HCT ‘arrow’
[Explanation] points downwards).
4. Verify that voltage of HCT connectors are +15V and -15V.
INV U-V-W stack
5. Check J5H jumper on DPC-140 and number of HCT turns, on the
basis of the below table.
HCT
U HCT Position of J5H
V IPM Capacity Motor Name plate
W
+15V TURNS jumper pin
R10 R9 R11 R12
J5H 75A ↓ 4 1-2 4.5~7.5kW
1 2
3 4 R78
100A 4 3-4 9.5~11kW
+5V
150A 4 1-2 13~15kW
R18
10
- 13 OCT
VB - 03
11 + U6HD U4GA
VB - 07
R44 C88
6. Check the earth condition and connection at building
DPC-140 7. Check if ground conditions of building & E&I panel are good.
8. Check followings:
- Resistance R9, 10, 11, 12 and 78 (marked on the left diagram) are properly
To DPC-1XX VB connector
fitted.(R9: 10K, R10: 1.5K, R11: 5K, R12: 12K, R78: 1M)
HCT
HCT 커넥터
- When a short pin is inserted into 3-4 on J5H, the potential of pin 10 on U6H
1 2 3 4 5 6
connector
+15V -15V IAS GND IBS GND is 8.89 ±0.44V.
1 6
HCT 9. Check the R_ENCODER wiring (Refer to TCD 92)
A B
10. Replace HCT & its cable.
HCT
HCT의 ‘arrow’
방향이 should
아래로
11. Replace DPC-140 PCB.
U-phase point 향해야 정상임
downwards
U상 V상
V-phase
Part : TCD Code
MUSE ED / Trouble Shooting Ctrl No. : MUSE ED-TS-03-0
Page: 21/127
○ Operation CPU
TCD 31 DC Link Over voltage Detection Application Si220
○ Speed CPU
[Meaning] [Countermeasures]
When DC link voltage is 770V or more is detected (Stop switching to prevent condenser, IPM
1. Check if the voltage of DC link is 770V±60V.
and IGBT from damages).
2. Check if reference voltage is within 7.9 ±0.5V
Check point (DPP-140,150 : TE40, TE100)
[Diagram]
The gap of regenerative voltage and over voltage must be within
Over voltage
과전압 detection
검출회로 circuit 0.25~0.36V in case of DPP 150 or 140)
3. If item 2, 3 are OK, check the connection between INV STACK
VDC(+)
GW - 03 DPP-150 & DPP-150, replace DPP-150.
15V (GDC) 정상시 LOW(0V)
Normal if Low(0V)
VDC(-)
이상시 HIGH(15V)
Abnormal if High(15V)
4. Check if regenerative IGBT operates normally. (Refer to TCD35:
GP - 09 D23
OV
In case of regenerative IGBT trouble, this error may be occurred.
R101 R36
R31
R102 R37
15V
C10D29 PC7 D30
6. Check if input power of E&I panel is correct.
VG - 13
R103 R38 -9V R47 7. If TCD 31 is detected while the car is not running, check followings:
R30 DPC-140
4
R104 R39
- 2 R21 C5 (INV) - VG connector on DPC-140.
5 VG - 14
+
LED1 R98 C4 IC1 - VA, GA connector on DPP-150.
8. After power off, check regenerative resistors is OK.
-9V
(Before this job, the voltage of DC link is 0V)
[Countermeasures]
[Meaning] Motor capacity 15kW below : In case that U phase of upper or lower 1. In case of DPP-150, check if the condition of GU, GV, GW & GX pin
IGBT in IPM are switching on together or regenerative IGBT in IPM connector are OK, and the connection between IPM and INV. Stack.
is short failure, the trouble occurs. 2. In case of DPP-150, check if the condition of GU, GV, GW & GX pin
connector are OK, and the connection between IPM and INV. Stack.
3. After separating of DPP-150 PCB and IPM, check output of gate
SMPS
(GU-01,02: 15V, GV-01,02: 15V, GW-01,02: 15V, GX-01,02: 15V,
GX-03,02: -9V)
4. Check if the condition of HCT cable and HCT is OK.
5. Check the direction of HCT
[Explanation]
Motor 15kW below: - Normal if HCT ‘arrow’ points to the bottom of CP
S-IPM is used that R IGBT is
mounted at inside. - Check wiring directions and refer to INV. over current.
6. Check for proper connections of the followings:
CONVERTER - VB connector to DPC-140 PCB
DIODE Reactor is applied
S-IPM in case of 15kW
and above
- U-phase HCT signal wire to VB-03
- V-phase HCT signal wire to VB-07.
3Φ 380V
HCT 7. Turn the power ON and check the followings:
U
V - Power condition of DPP-150 PCB
W
IM
- Voltage of GATE terminal
8. If TCD 32 is detected while the car is not running, check followings:
- VG connector on DPC-140.
- GA connector on DPP-150.
9. If the voltage of pin 6 of RA1(coordinates: 8I) on DPC-140 is +15V,
examine the connection between pin 21 on DPC-140 VG connector,
GP - 01
GP - 03
1Φ 110V
GU - 01
GU - 02 and pin 21 on DPP-150 GA connector.
VB - 07
VB - 03
GV - 01
GATE GV - 02
It is normal if they are connected.
GW - 01
SMPS GW - 02 DPP-150 DPC-140
10. Replace DPP-150 PCB.
GX - 01 (GDC) VA VG (INV)
GX - 02
GX - 03 11. Replace DPC-140 PCB.
(In case of IPM 150A ↓, 12. Replace S-IPM
DPP-150 is used.)
In case of S-IPM,
Use GATE SMPS
Part : TCD Code
MUSE ED / Trouble Shooting Ctrl No. : MUSE ED-TS-03-0
Page: 23/127
[Countermeasures]
[Meaning] Motor capacity 15kW below : In case that V phase of upper or lower 1. In case of DPP-150, check if the condition of GU, GV, GW & GX pin
IGBT in IPM are switching on together or regenerative IGBT in IPM connector are OK, and the connection between IPM and INV. Stack.
is short failure, the trouble occurs. 2. In case of DPP-150, check if the condition of GU, GV, GW & GX pin
connector are OK, and the connection between IPM and INV. Stack.
3. After separating of DPP-150 PCB and IPM, check output of gate
SMPS
(GU-01,02: 15V, GV-01,02: 15V, GW-01,02: 15V, GX-01,02: 15V,
GX-03,02: -9V)
[Explanation] 4. Check if the condition of HCT cable and HCT is OK.
5. Check the direction of HCT
Motor 15kW below: - Normal if HCT ‘arrow’ points to the bottom of CP
S-IPM is used that R IGBT is
mounted at inside. - Check wiring directions and refer to INV. over current.
6. Check for proper connections of the followings:
CONVERTER - VB connector to DPC-140 PCB
DIODE Reactor is applied
S-IPM in case of 15kW
and above
- U-phase HCT signal wire to VB-03
- V-phase HCT signal wire to VB-07.
3Φ 380V
HCT 7. Turn the power ON and check the followings:
U
V - Power condition of DPP-150 PCB
W
IM
- Voltage of GATE terminal
8. If TCD 33 is detected while the car is not running, check followings:
- VG connector on DPC-140.
- GA connector on DPP-150.
9. If the voltage of pin 6 of RA1(coordinates: 8I) on DPC-140 is +15V,
examine the connection between pin 21 on DPC-140 VG connector,
GP - 01
GP - 03
1Φ 110V
GU - 01
GU - 02 and pin 21 on DPP-150 GA connector.
VB - 07
VB - 03
GV - 01
GATE GV - 02
It is normal if they are connected.
GW - 01
SMPS GW - 02 DPP-150 DPC-140
10. Replace DPP-150 PCB.
GX - 01 (GDC) VA VG (INV)
GX - 02
GX - 03 11. Replace DPC-140 PCB.
(In case of IPM 150A ↓, 12. Replace IPM
DPP-150 is used.)
In case of S-IPM,
Use GATE SMPS
Part : TCD Code
MUSE ED / Trouble Shooting Ctrl No. : MUSE ED-TS-03-0
Page: 24/127
[Countermeasures]
[Meaning] Motor capacity 15kW below : In case that W phase of upper or lower 1. In case of DPP-150, check if the condition of GU, GV, GW & GX pin
IGBT in IPM are switching on together or regenerative IGBT in IPM connector are OK, and the connection between IPM and INV. Stack.
is short failure, the trouble occurs. 2. In case of DPP-150, check if the condition of GU, GV, GW & GX pin
connector are OK, and the connection between IPM and INV. Stack.
3. After separating of DPP-150 PCB and IPM, check output of gate
SMPS
(GU-01,02: 15V, GV-01,02: 15V, GW-01,02: 15V, GX-01,02: 15V,
GX-03,02: -9V)
[Explanation] 4. Check if the condition of HCT cable and HCT is OK.
5. Check the direction of HCT
Motor 15kW below: - Normal if HCT ‘arrow’ points to the bottom of CP
S-IPM is used that R IGBT is
mounted at inside. - Check wiring directions and refer to INV. over current.
6. Check for proper connections of the followings:
CONVERTER - VB connector to DPC-140 PCB
DIODE Reactor is applied
S-IPM in case of 15kW
and above
- U-phase HCT signal wire to VB-03
- V-phase HCT signal wire to VB-07.
3Φ 380V
HCT 7. Turn the power ON and check the followings:
U
V - Power condition of DPP-150 PCB
W
IM
- Voltage of GATE terminal
8. If TCD 34 is detected while the car is not running, check followings:
- VG connector on DPC-140.
- GA connector on DPP-150.
9. If the voltage of pin 6 of RA1(coordinates: 8I) on DPC-140 is +15V,
examine the connection between pin 21 on DPC-140 VG connector,
GP - 01
GP - 03
1Φ 110V
GU - 01
GU - 02 and pin 21 on DPP-150 GA connector.
VB - 07
VB - 03
GV - 01
GATE GV - 02
It is normal if they are connected.
GW - 01
SMPS GW - 02 DPP-150 DPC-140
10. Replace DPP-150 PCB.
GX - 01 (GDC) VA VG (INV)
GX - 02
GX - 03 11. Replace DPC-140 PCB.
(In case of IPM 150A ↓, 12. Replace IPM
DPP-150 is used.)
In case of S-IPM,
Use GATE SMPS
Part : TCD Code
MUSE ED / Trouble Shooting Ctrl No. : MUSE ED-TS-03-0
Page: 25/127
○ Operation CPU
TCD 35 Regenerative IGBT trouble Detection Application Si220
○ Speed CPU
VB - 07
VB - 03
단상
AC 110V
110V
GATE
DPP-150 VA VG
TRANS DPC-140
(GDC)
GXL - 09 (In case of IPM 100A) (INV)
GXL - 17
Part : TCD Code
MUSE ED / Trouble Shooting Ctrl No. : MUSE ED-TS-03-0
Page: 26/127
○ Operation CPU
TCD 36 Inverter Hall CT trouble Detection Application Si220
○ Speed CPU
[Meaning] When current controlling HCT and VB connector on DPC-140 PCB [Countermeasures]
are not connected.
1. Examine VB connector and cable on DPC-140 PCB
(Connector checking jumper should be connected as in the left diagram)
[Diagram] 2. Examine connector and cable of HCT.
2. If TCD 36 is detected, while the connector is tightly inserted,
replace VB connector cable.
[Meaning] When the thermal switch on radiating plate activates in order to prevent [Countermeasures]
IPM from being damaged by overheating. ( 85 ℃ or more, b contact)
1. Examine the followings:
- GP and GX connectors on DPP-150
[Diagram] - SC, GA connector on DPP-150 and VG connector on DPC-140
- 6,7 of GP connector
INV. STACK
Detect circuit for Overheating - Check for a proper connection between TH Pin 1, Pin 2 on DPP-13X
Normal LOW(0V)
THERMAL GUARD DIODE Abnormal HIGH(15V)
CONV. and terminal ends of thermal guard.
THERMAL1
[Meaning] Stop the lift under unfavorable condition of LRT operation [Countermeasures]
1. TCD will be detected when the motor turning is detected. 4. Check the BS1 and BS2 input line
[Meaning] When a current command, which is over the rated motor [Countermeasures]
current, is detected due to failure in the motor, unstable input power
supply & drop of voltage.
1. Examine the number of turns of HCT
This is detected when the current command value is over 150% of the rated motor current,
while the motor are running at the rated speed, going through starting and acceleration zone.
Part : TCD Code
MUSE ED / Trouble Shooting Ctrl No. : MUSE ED-TS-03-0
Page: 30/127
○ Operation CPU
TCD 48 DC Link Under Voltage Detection Application Si220
○ Speed CPU
GP - 09
VDC(-)
D23
(1: +15V, 2: -9V, 4: GND)
R62
R101 R36
4. If the voltage of pin 3 of RA1(Coordinates 8I) on DPC-140 is +15V,
R63
R102 R37
15V
C13 D36 PC9 D37
then, examine the connection between pin 15 on DPC-140 VG
VG - 15
-9V R49
connector and pin 15 or DPP-150 GA connector.
R103 R38
R35 DPC-140
9 (Normal if they are connected)
R104 R39 + 14 R23 C9 (INV)
8 VG - 16
- 5. This indicates that the voltage has not charged.
LED1 R98 C4 IC1
Check regenerative IGBT ON failure and MAIN IGBT ON failure.
-9V 6. Check the condenser and replace it, if necessary.
7. Replace DPP-150 PCB and DPC-140 PCB.
8. Check RCR resistor and wiring.
9. Check input power.
VDC(+) VDC(-)
PCB
Connector Connector 10. In case that the trouble occurs in the beginning of acceleration,
DPP-150 GP-01 GP-02 check if the door switches is off.