You are on page 1of 2

Ref.

:
FIELD CONSTRUCTION MANUAL Number: A-A110Ev1
MANUAL LEARNING MODE USING TEST TOOL
OTIS ANNEX 11
STARING UP PAX DOOR OPERATOR WITH TEST TOOL
Page:
Date:
Supersedes:
1/2
JANUARY 2008

1 2
Press “1”
CONNECT THE POWER SUPPLY Learning:
Init Run = 1 1 With default parameters
TO DOOR OPERATOR CONTROL Door Para Run = 2 2 With the customized paramete
DISCONNECT AND RECONNECT THE
TEST TOOL THE RESTART THE
SELF TEST IN OPERATION. WAIT 20 SECONDS Door is running
PROGRESS BEFORE CONNECTING Stop Door run = 3

SELF TEST SELF TEST


OK-MECS-MODE OK-MP2/3-MODE
THE DOOR OPENS AND CLOSES IN STEPS OF 10 cm AT LOW
SPEED.
Press “Module” THE DOOR CLOSES AT LOW SPEED.

Welcome to Atxx
Atxx = 3

Press “3” Para run finish


Learning finished.
Monitor = 1 Test = 2 Press “ Funtkey” Press "FUNCTION"
Tools = 4
Press “blue”+”7”
Monitor = 1 Test = 2 THE DOOR IS CLOSED
Setup = 3 Tools = 4

Press “3”
Install = 1 Para run failed
Learning interrupted on
Field = 3 ENG = 4 Run again : “SET” account of a Daule.
Press “3” Press “1” Press “SET”
IF THE LEARNING HAS ALREADY
BEEN DONE, MODIFY THE TO PERFORM THE LEARNING IF THERE HAS BEEN A MISTAKE DURING THE
PARANETERS DIRECTLY. Press 1 LEARNING, OPEN THE DOOR MANUALLY
Press 3

"Press 1"
Install = 1
Field = 3 ENG = 4
START THE LEARNING OPERATION AGAIN
Press “1”
Config = 1
SetDef = 9

"Press Blue + ENTER" AFTER THE LEARNING RUN, THE PARAMETERS CAN BE
MODIFIED IF IT DOES NOT WORK CORRECTLY.
Start learn run
Press “ENTER”

"Press 3"
OPEN THE DOOR MANUALLY FRM THE
TOP OF THE CAR AND LEAVE IT IN OPEN Install = 1
POSITION. Field =3 ENG = 4

Press “ Blue” “ENTER”


Start “ENTER” THE ADJUSTMENT PARAMETERS APPEAR ON SCREEN;
CHECK THAT THE VALUES ARE AS SHOWN IN THE TABLE
(See following page)
1 2
Ref.:
Table of parameters FIELD CONSTRUCTION MANUAL Number: A-A110Ev1
% PARAM ETERS TLD
700
TLD
750
TLD
800
TLD
850
TLD
900
CLD
800
CLD
900
OTIS ANNEX 11
STARING UP PAX DOOR OPERATOR WITH TEST TOOL
Page:
Date:
2/2
MAY 2009
Supersedes: JANUARY 2008
START O PN DIST 50 50 50 50 50 50 50
10 10 10 10 20 20
O PEN CRP DIST 10
VERIFICATIONS AND CHECKS IN ORDER TO SOLVE POSSIBLE PROBLEMS
CLOSE CRP DIST 70 70 70 70 70 50 50
- Verify the parameter DOOR=12 in the LCB_II board (M-1-3-1-5) or parameters DOOR and REAR=13
START CLS DIST 20 20 20 20 20 20 20
ACCEL O PEN 40 40 40 40 40 40 40
in the GECB board (M-M-1-1-3-1-5).
DECEL O PEN 40 40 40 40 40 40 40
- Verify the addresses of the remote stations (Inputs and Outputs) which control the door operator,
ACCEL CLOSE 40 40 40 40 40 40 40 (LCB_II: M-1-3-2 or in GECB: M-M-1-1-3-2).
DECEL CLOSE 40 40 40 40 40 40 40 - Verify the addresses of each I/O in the programming list for the unit as there might be variations
REVERSAL O PEN 40 40 40 40 40 40 40 in the address.
REVERSAL CLOSE 40 40 40 40 40 40 40
69 69 69 69 69 69 ADDRESS ADDRESS
START O PEN SPEED 69 I/O FRONT I/O REAR
LCBII GECB LCBII GECB
O PEN CRP SPEED 46 46 46 46 46 46 46
CLOSE CRP SP EED 20 20 20 20 20 20 20 991 ST1 17.3 16.2 994 ST1 19.3 19.2
START CLOS E SP EED 30 30 30 30 30 30 30 992 ST2 17.4 16.3 995 ST2 19.4 19.3
M AX O PEN S PEED 62 62 62 62 62 54 54 993 ST3 16.3 16.4 996 ST3 00.0 19.4
M AX CLO SE SPEED 38 38 38 38 38 41 41
0 DOL 17.1 16.3 544 DOL 19.1 19.3
NUDG ING SPEED 47 47 47 47 47 47 47
605 DOS 17.4 16.2 606 DOS 19.4 19.2
O PEN TORQ UE 100 100 100 100 100 100 100
CLOSE TORQUE 50 50 50 50 50 50 50 607 LRD 17.3 16.4 608 LRD 19.3 19.4
CLOSE CRE EP 50 50 50 50 50 50 50 NOTE: Ignore the message «Double Adr/Pin» in the Test Tool and press «ENTER».
TORQ UE
- Check that all the inputs that are not used in the LCB_II board (M-1-1-2) or the GECB board
CLOSE IDLE TO RQUE 50 50 50 50 50 50 50
(M-M-1-1-1-2) are in small letters (deactivated).
O PEN LDLE TORQUE 50 50 50 50 50 50 50
CLOSE PUSH 100 100 100 100 100 100 100 CHECKING COMMUNICATION OF CONTROL SIGNALS ST1, ST2, ST3 WITH LCB_II
TORQ UE
NUDG ING TO RQUE 50 50 50 50 50 50 50
CONTROLLER.
STOP TO RQUE 255 255 255 255 255 255 255 - With the lift on INSPECTION and the stop not pressed, connect the Test Tool in the door operator
control and carry out a check of the interface M-3-2-4-1.
The main parameters in the above table are in dark grey. - It should show “Finish No Error” if the communication is correct. If not, consult the table of
To modify the parameters the door must be closed. test errors.
To check the door after each modification, follow the SVT Inte rfa c e OK Test completed successfully. Communication correct.
sequence below.
Press “ SET” ST1 shortcirc, ST1+2 shortcirc,
ST2 shortcirc, ST1+3 shortcirc,
Short-circuit with HL2 of one or more lines of command. Check the wiring.
Install = 1 ST3 shortcirc, ST2+3 shortcirc,
Field = 3 ENG = 4
ST1-3 shortcirc

ST1 broken, ST1+2 broken,


Press “ 4”
ST2 broken, ST1+3 broken,
Short-circuit at 24 V DC or broken wire in one or more lines of command.
Monitor = 1 Test = 2 ST3 broken, ST2+3 broken,
Setup = 3 Tools = 4
ST1-3 broken

Press “1” ST1 wrong connect,


Single Run = 1
ST2 wrong connect, Wiring sequence incorrect. Check the wiring between the junction box and DCSS.
Cont Run = 2 ST3 wrong connect,

The checking sequence is not detected in a period of 400 ms after request. Check the input
No response pin of the remote station and the voltage levels. In the checking sequence DOL and DOS are
Press “1” to open Open = 1 Close = 2 required in high logic status.
Stop = 3 Revels = 4
Press “2” to close
The DCSS was unable to interpret the commands received. The checking sequence was
Unknown error
possibly interrupted. Repeat the operation.

You might also like