Professional Documents
Culture Documents
15) Generator-Protection-System
15) Generator-Protection-System
P. A. Amilkanthwar
Assistant Engineer (Gen)
Test - II
Topics for Discussion
◼ Basics of Electrical Protection system
◼ Synchronous machine
◼ Concept of reactive power and real power
sharing
◼ Different Protections used for generator
◼ Advanced Protection Relays(Microprocessor
based)
◼ Case studies (analysis of electrical faults)
◼ Synchronization
Different Protections used for Generator
◼ Generator Differential Protection.
◼ Generator Inter Turn Protection.
◼ Generator Negative Sequence Protection.
◼ Generator Loss of Excitation Protection.
◼ Generator Over Voltage Protection.
◼ Frequency Protection
◼ Generator Over Load/ Over Current Protection
◼ Generator Rotor Earth Fault Protection
◼ Generator Back Up Impedance protection
◼ Generator Low Forward power Interlock
◼ Generator reverse power protection.
◼ 95% stator Earth Fault Protection
Instrument Transformers
◼ Current Transformers ◼ Potential Transformers
• Turns ratio is • Turns ratio is directly
inversely proportional proportional to the ratio
to the ratio specified specified
• Secondary current is • Secondary current is
according to primary according to burden
current only connected
• Should not be short
• Should not be left
circuited
open circuited
Flow Diagram of Tripping Process
Protection Classes
◼ Class A Protection
• This master trip will operate when the fault
needs to isolate the generator immediately
• This gives command to open the generator
breaker and field breaker.
◼ Class B Protection
• This master trip will operate when the fault is not
serious in view of generator or it is not directly
harmful to generator
• This gives the command to trip turine
◼ Prime Mover Tripped
This indicates (gives feed back)prime mover is
tripped.
Basics of Electrical Protection system
Setting criteria
Xa1 = 0.5*Xd*CTR/PTR
Xd = 30.5% = 0.305 pu ……sub-
transient reactance of generator
Xd in ohms = Xd (pu)*kv2/MVA
= 0.305*15.752/247
=0.306311993
Xa1 = 2.139 ohm
Xb1 = Xd * CTR/PTR
Xd (ohmic) = Xd(pu)*kv2/MVA
Xb1 =
2.22(15.752/247)(10000/5)(110/15750)
= 31.14 ohm
Generator capability curve
Generator Over Voltage Protection.
1.1 3600
1.5 60 90
Generator Over Load/ Over Current
Protection2
Generator Capability Relay characristic
950
900
850
800
750
700
650
600
time in Sec.
550
500
450
400
350
300
250
200
150
100
50
0
1 1.05 1.1 1.15 1.2 1.25 1.3 1.35 1.4 1.45 1.5 1.55 1.6
% over current
Rotor E/F
Generator Back Up Impedance protection
Impedance protection to be covered up to 220 KV bus bar that is
Z = Z(G.T.) 12.5%
Ohmic value of Z (G.T.) = Z(pu)*KV2/MVA
= 0.125*15.752/250 = 0.124 ohm
Z at C.T.,P.T. secondary level = Z*(CTR/PTR)
= 0.124*(10000/5)*(110/15750)= 1.73 ohm
For 3 phase impedance 1.73*sqrt(3) = 2.996 ohm
Time setting = 2.5 sec (considering the line under Impedance time
setting that is to allow the line protections to clear the fault
before tripping of generator)
Z<1 setting (for P343 main only) Setting criteria: for long faults
and sustained overloading the setting of this stage should be
kept to operate at 30% overloading i.e. it should be set at 70%
impedance of the full load parameters of the generator.
Zfull load at C.T., P.T. level = rated volts (phase to phase)/ Ifull load
= 110/4.525 = 24.3 ohms
Z 70% = Zfull load*0.7 = 24.3*0.7 = 17.01 ohms delay = 5 sec
95% stator Earth Fault Protection
Salient Features of the relay P343:
• Following Protections of generator are covered in the relay
1.Generator Differential Protection: - High Impedance / Biased Differential
2. Phase fault over current protection: -
3.Neutral voltage displacement protection: -
4.100% Stator earth fault protection: -
5.Under/over voltage protection: - Two stage under and Over voltage
protection.
6.Under/over frequency protection: - Four stage under frequency and two
stage over frequency protection.
7.Reverse power: - Protection against loss of prime mover.
8.Low forward power: - Provides an interlock for non-urgent tripping.
9.Field failure: - Two stage element for protection against loss of excitation.
1 Negative phase sequence protection: - Provides protection against
unbalanced loading, which can cause overheating of the generator rotor.
1Over fluxing: - Provides protection for the generator/transformer against
unusual voltage or frequency conditions.
1 Unintentional energization at standstill (dead machine) protection: -
Protection against inadvertent closing of the generator circuit breaker when
machine is not running.
Other non-protective features of the relay:
1. Voltage transformer supervision: - To prevent mal-
operation of voltage dependent protection elements upon loss
of a VT input signal.
2. Measurements: - Various measurement of value for display
on the relay or accessed from the serial communications e.g.
Currents, voltages, Power etc.
3. Fault / event / disturbance records: - Available from the
serial communication or on the relay display (fault and event
records only on relay display.
4. Four setting groups: - Independent setting groups to cater
for alternative arrangements or user specific application.
5. Continuous self monitoring: - Power on diagnostics and
self checking routine to provide maximum relay reliability and
availability.
6. Circuit breaker state monitoring: - Provides indication of
discrepancy between circuit breaker auxiliary contacts.
P343
Case studies (analysis of electrical faults)