You are on page 1of 51

Assuming source MVA = 500 MVA ……( from MSEDCL)

Let Base MVA = 50 MVA


hence, Base current = KVA = 50000
KV * 1.732 11* 1.732
Adobe Acrobat
= 2624.3 A. p.u PDFXML Document
Source impedance = Base MVA = 50
Source MVA 500
= 0.1 ohm. p.u

Fault Current at HT breaker at F1

Ifault = Ib = Ib = 2624.31 Z = 0.0149


%Z % Z at F1 + %Z cable 0.1+0.0.00616
= 2624.310 %Z cable = Z * 50000
0.10616 1000*11*11
= 0.00616 ohm p.u
= 24720.328 A

= 24.720 KA

MVAfault = MVA Base = 50 = 470.9872 MVA


%Z 0.10616

Fault Current Transformer's primary

Ifault = Ib = Ib = 2624.31 Z = 0.0022


%Z % Z at F1 + %Z cable 0.10616+0.00090
= 2624.310 %Z cable = Z * 50000
0.10706 1000*11*11
= 0.0009 ohm p.u
= 24512.516 A

= 24.5125 KA

MVAfault = MVA Base = 50 = 467.0278 MVA


%Z 0.10706

Fault Current Transformer's Secondary

%Z at Primary Side = 0.10706 ohm .p.u Ib = Base KVA


Isc at Primary Side = 24.514 KA KV*1.732
Fault Level at Primary = 467.02 MVA = 50000
0.415*1.732
New Ztrans = Base MVA * % Z old = 50*5 = 69560.27 A p.u
Rated MVA 1*100
= 2.5 Ohm p.u

Ifault = Ib = Ib = 69560.27
%Z % Z at sec + %Z cable 2.50+0.10706
= 26681.4995 A
= 26.681 KA

MVAfault = MVA Base = 50 = 19.179 MVA


%Z 2.60706

Fault Current at Point F2


(i.e at main incomer of PCC-1)

Ifault = Ib = Ib = 69560.27 Z = 0.00029 ohm


%Z % Z at sec + %Z cable 2.60+0.084
= 69560.270 %Z cable = Z * 50000
2.684 1000*0.415*0.415
= 0.084 ohm p.u
= 25916.643 A

= 25.9166 KA

MVAfault = MVA Base = 50 = 18.6289 MVA


%Z 2.684

Fault Current at Point F3


(i.e at main incomer of Hybrid Panel)

Ifault = Ib = Ib = 69560.27 Z = 0.0281


%Z % Z at PCC-1 + %Z cable 2.684+
= 69560.270 %Z cable = Z * 50000
11.782 1000*0.415*0.415
= 8.158 ohm p.u
= 5903.944 A

= 5.9039 KA

MVAfault = MVA Base = 50 = 4.2438 MVA


%Z 11.782

Fault Current at Point F4


(i.e at main incomer of PCC -2)

Ifault = Ib = Ib = 69560.27 Z = 0.00324


%Z % Z at PCC-1 + %Z cable 2.684+0.941
= 69560.270 %Z cable = Z * 50000
3.625 1000*0.415*0.415
= 0.941 ohm p.u
= 19189.040 A

= 19.1890 KA

MVAfault = MVA Base = 50 = 13.7931 MVA


%Z 3.625

Fault Current at DG output Terminals


(i.e Fault contribution from DG set)

Sg = 1010 KVA
%Xd'' = 14%

Ib= Sbase = 1010 = 1405


1.732*0.415 1.732*0.415

Ifault P.U = 1 = 1 = 1
%Z %Xd'' 0.14

= 7.143 A p.u

Ifault = Ib * Ifault P.U = 7.143*1405 = 10035.714 A


= 10.036 KA

MVAfault = MVA Base = 1.01 = 7.214 MVA


%Z 0.14

Fault Current at Point F5


(i.e at main incomer from DG at PCC-2)

Ifault = Ib = Ib = 1405 Z = 0.0044


%Z %Xd''+ %Z cable 0.14+0.026
= 1405.000 %Z cable = Z * 1010
0.166 1000*0.415*0.415
= 0.026 ohm p.u
= 8463.855 A

= 8.4639 KA
MVAfault = MVA Base = 1.01 = 6.0843 MVA
%Z 0.166

Fault Current at Point F6


(i.e at main incomer of Scrubber MCC)

Ifault = Ib = Ib = 69560.27 Z = 0.04


%Z % Z at F4 + %Z cable 3.625+11.613
= 69560.270 %Z cable = Z * 50000
15.238 1000*0.415*0.415
= 11.613 ohm p.u
= 4564.921 A

= 4.5649 KA

MVAfault = MVA Base = 50 = 3.2813 MVA


%Z 15.238

Fault Current at Point F7


(i.e at main incomer of AAD MCC)

Ifault = Ib = Ib = 69560.27 Z = 0.0081


%Z % Z at F4 + %Z cable 3.632+2.352
= 69560.270 %Z cable = Z * 50000
5.984 1000*0.415*0.415
= 2.352 ohm p.u
= 11624.377 A

= 11.6244 KA

MVAfault = MVA Base = 50 = 8.3556 MVA


%Z 5.984

Fault Current at Point F8


(i.e at main incomer of HPS CT)

Ifault = Ib = Ib = 69560.27 Z = 0.0077


%Z % Z at F4 + %Z cable 3.632+2.235
= 69560.270 %Z cable = Z * 50000
5.867 1000*0.415*0.415
= 2.235 ohm p.u
= 11856.191 A
= 11.8562 KA

MVAfault = MVA Base = 50 = 8.5222 MVA


%Z 5.867

Fault Current at Point F9


(i.e at main incomer of Utility MCC 8)

Ifault = Ib = Ib = 69560.27 Z = 0.0062


%Z % Z at F4 + %Z cable 3.632+1.8
= 69560.270 %Z cable = Z * 50000
5.432 1000*0.415*0.415
= 1.800 ohm p.u
= 12805.646 A

= 12.8056 KA

MVAfault = MVA Base = 50 = 9.2047 MVA


%Z 5.432

Fault Current at Point F10


(i.e at main incomer of Powe DB)

Ifault = Ib = Ib = 69560.27 Z = 0.059


%Z % Z at F4 + %Z cable 3.632+17.129
= 69560.270 %Z cable = Z * 50000
20.761 1000*0.415*0.415
= 17.129 ohm p.u
= 3350.526 A

= 3.3505 KA

MVAfault = MVA Base = 50 = 2.4084 MVA


%Z 20.761

Fault Current at Point F11


(i.e at main incomer of ETP Panel)

Ifault = Ib = Ib = 69560.27 Z = 0.0281


%Z % Z at F4 + %Z cable 3.632+8.15
= 69560.270 %Z cable = Z * 50000
11.782 1000*0.415*0.415
= 8.158 ohm p.u
= 5903.944 A

= 5.9039 KA

MVAfault = MVA Base = 50 = 4.2438 MVA


%Z 11.782

Fault Current at Point F12


(i.e at main incomer of Fire Hydrant panel)

Ifault = Ib = Ib = 69560.27 Z = 0.0156


%Z % Z at F4 + %Z cable 3.632+4.529
= 69560.270 %Z cable = Z * 50000
8.161 1000*0.415*0.415
= 4.529 ohm p.u
= 8523.498 A

= 8.5235 KA

MVAfault = MVA Base = 50 = 6.1267 MVA


%Z 8.161

Fault Current at Point F13


(i.e at main incomer of Utilty 20KVA UPS)

Ifault = Ib = Ib = 69560.27 Z = 0.022


%Z % Z at F4 + %Z cable 3.632+6.387
= 69560.270 %Z cable = Z * 50000
10.019 1000*0.415*0.415
= 6.387 ohm p.u
= 6942.836 A

= 6.9428 KA

MVAfault = MVA Base = 50 = 4.9905 MVA


%Z 10.019

Fault Current at Point F14


(i.e at main incomer of DM Plant)

Ifault = Ib = Ib = 69560.27 Z = 0.069


%Z % Z at F4 + %Z cable 3.632+20.032
= 69560.270 %Z cable = Z * 50000
23.664 1000*0.415*0.415
= 20.032 ohm p.u
= 2939.498 A

= 2.9395 KA

MVAfault = MVA Base = 50 = 2.1129 MVA


%Z 23.664

Fault Current at Point F15


(i.e at main incomer of Utility 5KVA UPS)

Ifault = Ib = Ib = 120481 Z =
%Z % Z at F4 + %Z cable 3.632+
= 120481.000 %Z cable = Z * 50000
= 1000*0.415*0.415
= 0.000 ohm p.u
= #VALUE! A

= #VALUE! KA

MVAfault = MVA Base = 50 = #VALUE! MVA


%Z =

Fault Current at Point F16


(i.e at main incomer of Active MCC Panel)

Ifault = Ib = Ib = 69560.27 Z = 0.0059


%Z % Z at F4 + %Z cable 3.632+1.713
= 69560.270 %Z cable = Z * 50000
5.345 1000*0.415*0.415
= 1.713 ohm p.u
= 13014.082 A

= 13.0141 KA

MVAfault = MVA Base = 50 = 9.3545 MVA


%Z 5.345

Fault Current at Point F17


(i.e at main incomer of Utility 9 - OMC RVPD Panel)

Ifault = Ib = Ib = 69560.27 Z = 0.00312


%Z % Z at F4 + %Z cable 3.632+0.906
= 69560.270 %Z cable = Z * 50000
4.538 1000*0.415*0.415
= 0.906 ohm p.u
= 15328.398 A

= 15.3284 KA

MVAfault = MVA Base = 50 = 11.0181 MVA


%Z 4.538

Fault Current at Point F18


(i.e at main incomer of WareHouse MCC)

Ifault = Ib = Ib = 69560.27 Z = 0.058


%Z % Z at F4 + %Z cable 3.632+16.838
= 69560.270 %Z cable = Z * 50000
20.47 1000*0.415*0.415
= 16.838 ohm p.u
= 3398.157 A

= 3.3982 KA

MVAfault = MVA Base = 50 = 2.4426 MVA


%Z 20.47

Fault Current at Point F19


(i.e at main incomer of OMC MCC PANEL/ MCC-5)

Ifault = Ib = Ib = 69560.27 Z = 0.0062


%Z % Z at F4 + %Z cable 3.632+1.800
= 69560.270 %Z cable = Z * 50000
5.432 1000*0.415*0.415
= 1.800 ohm p.u
= 12805.646 A

= 12.8056 KA

MVAfault = MVA Base = 50 = 9.2047 MVA


%Z 5.432

SPARE
Fault Current at Point F20
(i.e at main incomer of OMC LIFT 1&2)
Ifault = Ib = Ib = 69560.27 Z = 0
%Z % Z at F4 + %Z cable
= 69560.270 %Z cable = Z * 50000
= 1000*0.415*0.415
= 0.000 ohm p.u
= #VALUE! A

= #VALUE! KA

MVAfault = MVA Base = 50 = #VALUE! MVA


%Z =

Fault Current at Point F21


(i.e at main incomer of Chilling 129Tr panel)

Ifault = Ib = Ib = 69560.27 Z = 0.0078


%Z % Z at F4 + %Z cable 3.632+2.264
= 69560.270 %Z cable = Z * 50000
5.896 1000*0.415*0.415
= 2.264 ohm p.u
= 11797.875 A

= 11.7979 KA

MVAfault = MVA Base = 50 = 8.4803 MVA


%Z 5.896

Fault Current at Point F22


(i.e at main incomer of OMC MCC 6-SCIT)

Ifault = Ib = Ib = 69560.27 Z = 0.0062


%Z % Z at F4 + %Z cable 3.632+1.8
= 69560.270 %Z cable = Z * 50000
5.432 1000*0.415*0.415
= 1.800 ohm p.u
= 12805.646 A

= 12.8056 KA

MVAfault = MVA Base = 50 = 9.2047 MVA


%Z 5.432
Fault Current at Point F23
(i.e at main incomer of Thermopac Panel)

Ifault = Ib = Ib = 69560.27 Z = 0.0086


%Z % Z at F4 + %Z cable 3.632+2.497
= 69560.270 %Z cable = Z * 50000
6.129 1000*0.415*0.415
= 2.497 ohm p.u
= 11349.367 A

= 11.3494 KA

MVAfault = MVA Base = 50 = 8.1579 MVA


%Z 6.129

Fault Current at Point F24


(i.e at main incomer of Utility Lighting Panel)

Ifault = Ib = Ib = 69560.27 Z = 0.001


%Z % Z at F4 + %Z cable 3.632+0.290
= 69560.270 %Z cable = Z * 50000
3.922 1000*0.415*0.415
= 0.290 ohm p.u
= 17735.918 A

= 17.7359 KA

MVAfault = MVA Base = 50 = 12.7486 MVA


%Z 3.922

Fault Current at Point F25


(i.e at main incomer of admin office)

Ifault = Ib = Ib = 69560.27 Z = 0.011


%Z % Z at F4 + %Z cable 3.632+3.193
= 69560.270 %Z cable = Z * 50000
6.825 1000*0.415*0.415
= 3.193 ohm p.u
= 10191.981 A

= 10.1920 KA

MVAfault = MVA Base = 50 = 7.3260 MVA


%Z 6.825
Fault Current at Point F26
(i.e at main incomer of QA Lab MCC)

Ifault = Ib = Ib = 69560.27 Z = 0.077 ohms


%Z % Z at F4 + %Z cable 3.632+22.354
= 69560.270 %Z cable = Z * 50000
25.986 1000*0.415*0.415
= 22.354 ohm p.u
= 2676.836 A

= 2.6768 KA

MVAfault = MVA Base = 50 = 1.9241 MVA


%Z 25.986

Fault Current at Point F27


(i.e at main incomer of Chilling 15Tr)

Ifault = Ib = Ib = 69560.27 Z = 0.0195 ohms


%Z % Z at F4 + %Z cable 3.632+5.661
= 69560.270 %Z cable = Z * 50000
9.293 1000*0.415*0.415
= 5.661 ohm p.u
= 7485.233 A

= 7.4852 KA

MVAfault = MVA Base = 50 = 5.3804 MVA


%Z 9.293

Fault Current at Point F28


(i.e at main incomer of 3Tph Boiler CP)

Ifault = Ib = Ib = 69560.27 Z = 0.275 ohms


%Z % Z at F4 + %Z cable 3.632+79.837
= 69560.270 %Z cable = Z * 50000
83.469 1000*0.415*0.415
= 79.837 ohm p.u
= 833.367 A

= 0.8334 KA

MVAfault = MVA Base = 50 = 0.5990 MVA


%Z 83.469

Fault Current at Point F29


(i.e at main incomer of lift 1 )

Ifault = Ib = Ib = 69560.27 Z = 0.826 ohms


%Z % Z at F4 + %Z cable 3.632+239.803
= 69560.270 %Z cable = Z * 50000
243.435 1000*0.415*0.415
= 239.803 ohm p.u
= 285.745 A

= 0.2857 KA

MVAfault = MVA Base = 50 = 0.2054 MVA


%Z 243.435

Fault Current at Point F30


(i.e at main incomer of SSR-9 AGT VFD panel)

Ifault = Ib = Ib = 69560.27 Z = 0 ohms


%Z % Z at F4 + %Z cable 3.632+79.837
= 69560.270 %Z cable = Z * 50000
0 1000*0.415*0.415
= 0.000 ohm p.u
= #DIV/0! A

= #DIV/0! KA

MVAfault = MVA Base = 50 = #DIV/0! MVA


%Z 0

SPASPARERE
Fault Current at Point F31
(i.e at main incomer )

Ifault = Ib = Ib = 69560.27 Z = 0 ohms


%Z % Z at F4 + %Z cable 3.632+79.837
= 69560.270 %Z cable = Z * 50000
0 1000*0.415*0.415
= 0.000 ohm p.u
= #DIV/0! A

= #DIV/0! KA
MVAfault = MVA Base = 50 = #DIV/0! MVA
%Z 0

Fault Current at Point F32


(i.e at main incomer of Airavat VFD Panel)

Ifault = Ib = Ib = 69560.27 Z = 0.024 ohms


%Z % Z at F4 + %Z cable 3.632+6.968
= 69560.270 %Z cable = Z * 50000
10.6 1000*0.415*0.415
= 6.968 ohm p.u
= 6562.290 A

= 6.5623 KA

MVAfault = MVA Base = 50 = 4.7170 MVA


%Z 10.6

Fault Current at Point F33


(i.e at main incomer of microlab MCC)

Ifault = Ib = Ib = 69560.27 Z = 0.0591 ohms


%Z % Z at F4 + %Z cable 3.632+17.158
= 69560.270 %Z cable = Z * 50000
20.79 1000*0.415*0.415
= 17.158 ohm p.u
= 3345.852 A

= 3.3459 KA

MVAfault = MVA Base = 50 = 2.4050 MVA


%Z 20.79

Fault Current at Point F34


(i.e at main incomer of cooling tower VFD mains)

Ifault = Ib = Ib = 69560.27 Z = 0.134 ohms


%Z % Z at F4 + %Z cable 3.632+38.903
= 69560.270 %Z cable = Z * 50000
42.535 1000*0.415*0.415
= 38.903 ohm p.u
= 1635.365 A
= 1.6354 KA

MVAfault = MVA Base = 50 = 1.1755 MVA


%Z 42.535

Fault Current at Point F35


(i.e at main incomer of Workshop mains)

Ifault = Ib = Ib = 69560.27 Z = 0.0624 ohms


%Z % Z at F4 + %Z cable 3.632+18.116
= 69560.270 %Z cable = Z * 50000
21.748 1000*0.415*0.415
= 18.116 ohm p.u
= 3198.467 A

= 3.1985 KA

MVAfault = MVA Base = 50 = 2.2991 MVA


%Z 21.748

Fault Current at Point F36


(i.e at main incomer of lift 2&3)

Ifault = Ib = Ib = 69560.27 Z = 0.1 ohms


%Z % Z at F4 + %Z cable 3.632+29.032
= 69560.270 %Z cable = Z * 50000
32.664 1000*0.415*0.415
= 29.032 ohm p.u
= 2129.570 A

= 2.1296 KA

MVAfault = MVA Base = 50 = 1.5307 MVA


%Z 32.664

SPASPARERE
Fault Current at Point F37
(i.e at main incomer of )

Ifault = Ib = Ib = 69560.27 Z = 0 ohms


%Z % Z at F4 + %Z cable 3.632+29.032
= 69560.270 %Z cable = Z * 50000
0 1000*0.415*0.415
= 0.000 ohm p.u
= #DIV/0! A

= #DIV/0! KA

MVAfault = MVA Base = 50 = #DIV/0! MVA


%Z 0

Fault Current at Point F38


(i.e at main incomer of )

Ifault = Ib = Ib = 69560.27 Z = 0.0117 ohms


%Z % Z at F4 + %Z cable 3.632+3.397
= 69560.270 %Z cable = Z * 50000
7.029 1000*0.415*0.415
= 3.397 ohm p.u
= 9896.183 A

= 9.8962 KA

MVAfault = MVA Base = 50 = 7.1134 MVA


%Z 7.029

Fault Current at Point F39


(i.e at main incomer of Heat tracing Panel)

Ifault = Ib = Ib = 69560.27 Z = 0.0188 ohms


%Z % Z at F4 + %Z cable 3.632+5.458
= 69560.270 %Z cable = Z * 50000
9.09 1000*0.415*0.415
= 5.458 ohm p.u
= 7652.395 A

= 7.6524 KA

MVAfault = MVA Base = 50 = 5.5006 MVA


%Z 9.09

Fault Level For AAD MCC PANEL

At Incomer Side …..( At F7)


%Z= 5.984 ohm p.u
Fault Current = 11.62 KA
fault level = 8.3556 MVA

Fault current for 0.75 KW Motor

2R2-1 0.75KW NTR-1 CAUSTIC DOSING FLC = 0.75


2R2-2 0.75KW NTR-1 CC DOSING 0.415*0.8*0.8
= 2.82 A
These are Single Phase Motors, hence
Ib = KVA = 50000 = 120481.928 A p.u
KV 0.415
Nominal Fault current,
Inf = Ib = Ib = 120481.928 2c,2.5sq mm, Cu Unarmed wire = 30m
%Z % Z at incomer+ %Z cable 5.984+79.083 Z = 0.2724 ohms
= 1416.31 A
motor contribution, %Z cable = Z * 50000
Imc 4*FLC = 4*2.82 = 11.28 A 1000*0.415*0.415
= 79.083 ohm p.u
Ifault = Inf + Imc = 1416.31+11.28
= 1427.59 A

Fault current for 2.2KW Motor

FLC = 2.2 = 4.782 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.984+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
111.427
= 624.268 A
motor contribution,
Imc 4*FLC = 4*4.78 = 19.12963633 A

Ifault = Inf + Imc = 624.26+19.12


= 643.3972734 A

Fault current for 3.7KW Motor

FLC = 3.7 = 8.043 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.984+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
111.427
= 624.268 A
motor contribution,
Imc 4*FLC = 4*4.78 = 32.17257019 A
Ifault = Inf + Imc = 624.26+32.17
= 656.440 A

Fault current for 3.7KW Motor

FLC = 5.5 = 11.956 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.984+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
111.427
= 624.268 A
motor contribution,
Imc 4*FLC = 4*4.78 = 47.82409082 A

Ifault = Inf + Imc = 624.26+47.824


= 672.092 A

Fault current for 7.5KW Motor

FLC = 7.5 = 16.304 A 3c, 6.0sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.1512 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.984+43.896 1000*0.415*0.415
= 69560.27 A = 43.896 ohm p.u
49.88
= 1394.552 A
motor contribution,
Imc 4*FLC = 4*4.78 = 65.2146693 A

Ifault = Inf + Imc = 1394.55+65.21


= 1459.767 A

Fault current for worker room mains

Ifault = Ib = Ib = 69560.27 3c, 2R, 6.0sq mm, Cu Unarmed wire = 40m


%Z % Z at incomer+ %Z cable 5.984+21.948 Z = 0.0756 ohms
= 69560.27 A
27.932 %Z cable = Z * 50000
= 2490.343 A 1000*0.415*0.415
= 21.948 ohm p.u

Fault current for Air Compressor Mains

Ifault = Ib = Ib = 69560.27 3c, 2R, 4.0sq mm, Cu Unarmed wire = 40m


%Z % Z at incomer+ %Z cable 5.984+32.980 Z = 0.1136 ohms
= 69560.27 A
38.964 %Z cable = Z * 50000
= 1785.245 A 1000*0.415*0.415
= 32.980 ohm p.u

Fault current for Power DB & Maint Office

Ifault = Ib = Ib = 69560.27 3c, 2R, 4.0sq mm, Cu Unarmed wire = 40m


%Z % Z at incomer+ %Z cable 5.984+43.54 Z = 0.15 ohms
= 69560.27 A
49.524 %Z cable = Z * 50000
= 1404.577 A 1000*0.415*0.415
= 43.548 ohm p.u

Fault current for AAD VFD Panel Mains

Ifault = Ib = Ib = 69560.27 3.5c, 2R, 120sq mm, AL XLPE Cable = 15m


%Z % Z at incomer+ %Z cable 5.984+0.679 Z = 0.00234 ohms
= 69560.27 A
6.663 %Z cable = Z * 50000
= 10439.782 A 1000*0.415*0.415
= 0.679 ohm p.u

MVAfault = MVA Base = 50 = 7.5041 MVA


%Z 6.663

Fault Level For AAD VFD PANEL

At Incomer Side
%Z= 6.663 ohm p.u
Fault Current = 10.439 A
fault level = 7.50 MVA

Fault current for 10HP Motor with VFD

FLC = 7.5 = 16.304 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 6.663+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
112.106
= 620.487 A
motor contribution,
Imc 4*FLC = 4*16.304 = 65.2147 A

Ifault = Inf + Imc = 620.48+19.12


= 685.701 A

Fault current for 5HP Motor with VFD

FLC = 3.7 = 8.043 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 6.663+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
112.106
= 620.487 A
motor contribution,
Imc 4*FLC = 4*4.78 = 32.17257019 A

Ifault = Inf + Imc = 620.487+32.17


= 652.659 A

Fault Level For SCRUBBER MCC PANEL

At Incomer Side …..( At F6)


%Z= 15.238 ohm p.u
Fault Current = 4.564 kA
fault level = 3.2813 MVA

Fault current for 2.2KW Motor

FLC = 2.2 = 4.782 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 15.238+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
120.681
= 576.398 A
motor contribution,
Imc 4*FLC = 4*4.78 = 19.12963633 A

Ifault = Inf + Imc = 576.398+19.12


= 595.5274951 A

Fault current for 3.7KW Motor

FLC = 3.7 = 8.043 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 15.238+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
120.681
= 576.398 A
motor contribution,
Imc 4*FLC = 4*8.043 = 32.17257019 A

Ifault = Inf + Imc = 624.26+32.17


= 608.570 A

Fault current for Tank-1 VFD Mains

Ifault = Ib = Ib = 69560.27 3c,4.0sq mm, Cu Unarmed wire = 20m


%Z % Z at incomer+ %Z cable 15.238+32.980 Z = 0.1136 ohms
= 69560.27 A
48.218 %Z cable = Z * 50000
= 1442.620 A 1000*0.415*0.415
= 32.980 ohm p.u

Fault current for 15KW Motor

FLC = 15 = 32.607 A 3c,4sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.04544 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 48.218+13.192 1000*0.415*0.415
= 69560.27 A = 13.192 ohm p.u
61.41
= 1132.719 A
motor contribution,
Imc 4*FLC = 4*32.607 = 130.4293386 A

Ifault = Inf + Imc = 1132.719+130.42


= 1263.148 A

Fault Level For ACTIVE MCC PANEL

At Incomer Side …..( At F16)


%Z= 5.354 ohm p.u
Fault Current = 13.014 KA
fault level = 9.354 MVA

Fault current for 2.2KW Motor

FLC = 2.2 = 4.782 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.354+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
110.797
= 627.817 A
motor contribution,
Imc 4*FLC = 4*4.78 = 19.12963633 A

Ifault = Inf + Imc = 627.817+19.12


= 646.9469057 A

Fault current for 3.7KW Motor

FLC = 3.7 = 8.043 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.354+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
110.797
= 627.817 A
motor contribution,
Imc 4*FLC = 4*8.043 = 32.17257019 A

Ifault = Inf + Imc = 627.817+32.17


= 659.990 A

Fault current for 5.5KW Motor

FLC = 5.5 = 11.956 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.354+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
110.797
= 627.817 A
motor contribution,
Imc 4*FLC = 4*11.956 = 47.8241 A

Ifault = Inf + Imc = 627.817+47.824


= 675.641 A

Fault current for ACTIVE VFD Panel Mains

Ifault = Ib = Ib = 69560.27 3.5c, 2R, 120sq mm, AL XLPE Cable = 40m


%Z % Z at incomer+ %Z cable 5.354+1.812 Z = 0.00624 ohms
= 69560.27 A
7.166 %Z cable = Z * 50000
= 9706.987 A 1000*0.415*0.415
= 1.812 ohm p.u

MVAfault = MVA Base = 50 = 6.9774 MVA


%Z 7.166

Fault current for FLP-1 MCC Panel Mains

Ifault = Ib = Ib = 69560.27 3.5c, 2R, 300sq mm, AL XLPE Cable = 20m


%Z % Z at incomer+ %Z cable 5.354+0.427 Z = 0.00147 ohms
= 69560.27 A
5.781 %Z cable = Z * 50000
= 12032.567 A 1000*0.415*0.415
= 0.427 ohm p.u

MVAfault = MVA Base = 50 = 8.6490 MVA


%Z 5.781

Fault current for FLP-2 MCC Panel Mains

Ifault = Ib = Ib = 69560.27 3.5c, 2R,300sq mm, AL XLPE Cable = 25m


%Z % Z at incomer+ %Z cable 5.354+0.534 Z = 0.00184 ohms
= 69560.27 A
5.888 %Z cable = Z * 50000
= 11813.905 A 1000*0.415*0.415
= 0.534 ohm p.u

MVAfault = MVA Base = 50 = 8.4918 MVA


%Z 5.888

Fault Level For ACTIVE VFD PANEL

At Incomer Side
%Z= 7.166 ohm
Fault Current = 9.706 KA
fault level = 6.97 MVA

Fault current for 25HP Motor with VFD

FLC = 18.625 = 40.487 A 3c,6sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.151 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 7.166+43.838 1000*0.415*0.415
= 69560.27 A = 43.838 ohm p.u
51.004
= 1363.820 A
motor contribution,
Imc 4*FLC = 4*40.487 = 161.9498 A

Ifault = Inf + Imc = 1363.82+161.94


= 1525.770 A

Fault current for 15HP Motor with VFD

FLC = 11.175 = 24.292 A 3c,6sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.151 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 7.166+43.838 1000*0.415*0.415
= 69560.27 A = 43.838 ohm p.u
51.004
= 1363.820 A
motor contribution,
Imc 4*FLC = 4*24.29 = 97.1699 A

Ifault = Inf + Imc = 1363.82+97.16


= 1460.990 A

Fault current for 10HP Motor with VFD

FLC = 7.5 = 16.304 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 7.166+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
112.609
= 617.715 A
motor contribution,
Imc 4*FLC = 4*16.304 = 65.2147 A

Ifault = Inf + Imc = 617.715+65.214


= 682.930 A

Fault current for 6HP Motor with VFD

FLC = 4.5 = 9.782 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 7.166+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
112.609
= 617.715 A
motor contribution,
Imc 4*FLC = 4*9.782 = 39.1288 A

Ifault = Inf + Imc = 617.715+39.128


= 656.844 A

Fault current for 5HP Motor with VFD

FLC = 3.75 = 8.152 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 7.166+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
112.609
= 617.715 A
motor contribution,
Imc 4*FLC = 4*8.152 = 32.6073 A

Ifault = Inf + Imc = 617.715+32.6073


= 650.322 A

Fault current for 3HP Motor with VFD

FLC = 2.25 = 4.891 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 7.166+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
112.609
= 617.715 A
motor contribution,
Imc 4*FLC = 4*4.891 = 19.5644 A

Ifault = Inf + Imc = 617.715+19.5644


= 637.279 A

Fault Level For AIRAVAT VFD PANEL

At Incomer Side …..( At F32)


%Z= 10.6 ohm p.u
Fault Current = 6.562 KA
fault level = 4.7170 MVA

Fault current for 3HP Motor …(SSR23 seal cooling pump)

FLC = 2.2 = 4.782 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 10.6+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
116.043
= 599.435 A
motor contribution,
Imc 4*FLC = 4*4.782 = 19.12963633 A

Ifault = Inf + Imc = 599.43+19.12


= 618.5649319 A

Fault current for 75HP Motor …(SSR23 Agitator)

FLC = 56.25 = 122.278 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.0098 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 10.6+2.845 1000*0.415*0.415
= 69560.27 A = 2.845 ohm p.u
8.199
= 8483.994 A
motor contribution,
Imc 4*FLC = 4*122.278 = 489.1100198 A

Ifault = Inf + Imc = 8483.994+489.11


= 8973.104 A

Fault Level For FLP-1 MCC PANEL

At Incomer Side
%Z= 5.781 ohm p.u
Fault Current = 12.032 KA
fault level = 8.64 MVA

Fault current for 2.2KW Motor

FLC = 2.2 = 4.782 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.781+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
111.224
= 625.407 A
motor contribution,
Imc 4*FLC = 4*4.78 = 19.12963633 A

Ifault = Inf + Imc = 625.407+19.12


= 644.5366528 A

Fault current for 3.7KW Motor

FLC = 3.7 = 8.043 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.781+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
111.224
= 625.407 A
motor contribution,
Imc 4*FLC = 4*8.043 = 32.17257019 A

Ifault = Inf + Imc = 625.407+32.17


= 657.580 A

Fault current for 5.5KW Motor

FLC = 5.5 = 11.956 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.781+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
111.224
= 625.407 A
motor contribution,
Imc 4*FLC = 4*11.956 = 47.8241 A

Ifault = Inf + Imc = 625.407+47.824


= 673.231 A

Fault current for 7.5KW Motor

FLC = 7.5 = 16.304 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.781+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
111.224
= 625.407 A
motor contribution,
Imc 4*FLC = 4*16.304 = 65.2147 A

Ifault = Inf + Imc = 625.407+65.214


= 690.622 A

Fault current for 11KW Motor

FLC = 11 = 23.912 A 3c,4sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.2272 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.781+65.960 1000*0.415*0.415
= 69560.27 A = 65.960 ohm p.u
71.741
= 969.603 A
motor contribution,
Imc 4*FLC = 4*23.912 = 95.6482 A

Ifault = Inf + Imc = 969.603+95.648


= 1065.251 A

Fault current for Flaker-2 AHU

Ifault = Ib = Ib = 69560.27 3.5c, 6sq mm,unarmed CU wire = 40m


%Z % Z at incomer+ %Z cable 5.781+43.896 Z = 0.1512 ohms
= 69560.27 A
49.677 %Z cable = Z * 50000
= 1400.251 A 1000*0.415*0.415
= 43.896 ohm p.u

Fault current for Fristom pump

Ifault = Ib = Ib = 69560.27 3.5c, 2R, 120sq mm, AL XLPE Cable = 40m


%Z % Z at incomer+ %Z cable 5.781+0.427 Z = 0.00147 ohms
= 69560.27 A
6.208 %Z cable = Z * 50000
= 11204.940 A 1000*0.415*0.415
= 0.427 ohm p.u

MVAfault = MVA Base = 50 = 8.0541 MVA


%Z 6.208

Fault current for FLP-1 VFD Panel Mains

Ifault = Ib = Ib = 69560.27 3.5c, 2R, 120sq mm, AL XLPE Cable = 40m


%Z % Z at incomer+ %Z cable 5.781+1.812 Z = 0.00624 ohms
= 69560.27 A
7.593 %Z cable = Z * 50000
= 9161.105 A 1000*0.415*0.415
= 1.812 ohm p.u

MVAfault = MVA Base = 50 = 6.5850 MVA


%Z 7.593

Fault Level For FLP-1 VFD PANEL

At Incomer Side
%Z= 7.593 ohm
Fault Current = 9.16 KA
fault level = 6.58 MVA

Fault current for 15HP Motor with VFD

FLC = 11.25 = 24.456 A 3c,4sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.2272 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 7.593+65.960 1000*0.415*0.415
= 69560.27 A = 65.960 ohm p.u
73.553
= 945.716 A
motor contribution,
Imc 4*FLC = 4*24.456 = 97.8220 A

Ifault = Inf + Imc = 945.716+97.8220


= 1043.538 A

Fault current for 10HP Motor with VFD

FLC = 7.5 = 16.304 A 3c,6sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 7.593+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
113.036
= 615.382 A
motor contribution,
Imc 4*FLC = 4*16.304 = 65.2147 A

Ifault = Inf + Imc = 615.38+65.21


= 680.596 A

Fault current for 5HP Motor with VFD

FLC = 3.75 = 8.152 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 7.593+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
113.036
= 615.382 A
motor contribution,
Imc 4*FLC = 4*8.152 = 32.6073 A

Ifault = Inf + Imc = 615.382+32.6073


= 647.989 A

Fault Level For FLP-2 MCC PANEL

At Incomer Side
%Z= 5.888 ohm p.u
Fault Current = 11.813 KA
fault level = 8.49 MVA

Fault current for 1.5KW Motor

FLC = 1.5 = 3.261 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.888+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
111.331
= 624.806 A
motor contribution,
Imc 4*FLC = 4*3.261 = 13.04293386 A

Ifault = Inf + Imc = 624.806+13.04


= 637.849 A

Fault current for 2.2KW Motor

FLC = 2.2 = 4.782 A 3c,1.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.6 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.888+174.19 1000*0.415*0.415
= 69560.27 A = 174.191 ohm p.u
180.078
= 386.279 A
motor contribution,
Imc 4*FLC = 4*4.782 = 19.12963633 A

Ifault = Inf + Imc = 386.279+19.12


= 405.408 A

Fault current for 2.2KW Motor

FLC = 2.2 = 4.782 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.888+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
111.331
= 624.806 A
motor contribution,
Imc 4*FLC = 4*4.782 = 19.12963633 A

Ifault = Inf + Imc = 624.806+19.12


= 643.936 A

Fault current for 3.7KW Motor

FLC = 3.7 = 8.043 A 3c,1.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.6 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.888+174.191 1000*0.415*0.415
= 69560.27 A = 174.191 ohm p.u
180.079
= 386.276 A
motor contribution,
Imc 4*FLC = 4*8.043 = 32.17257019 A

Ifault = Inf + Imc = 386.27+32.17


= 418.449 A

Fault current for 3.7KW Motor

FLC = 3.7 = 8.043 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.888+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
111.331
= 624.806 A
motor contribution,
Imc 4*FLC = 4*8.043 = 32.17257019 A

Ifault = Inf + Imc = 624.806+32.17


= 656.979 A

Fault current for 7.5KW Motor

FLC = 7.5 = 16.304 A 3c,4sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.2272 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.888+65.960 1000*0.415*0.415
= 69560.27 A = 65.960 ohm p.u
71.848
= 968.159 A
motor contribution,
Imc 4*FLC = 4*16.304 = 65.2147 A

Ifault = Inf + Imc = 968.159+65.214


= 1033.373 A

Fault current for FLP-2 VFD Panel Mains

Ifault = Ib = Ib = 69560.27 3.5c, 2R, 120sq mm, AL XLPE Cable = 45m


%Z % Z at incomer+ %Z cable 5.888+2.038 Z = 0.00702 ohms
= 69560.27 A
7.926 %Z cable = Z * 50000
= 8776.214 A 1000*0.415*0.415
= 2.038 ohm p.u

MVAfault = MVA Base = 50 = 6.3084 MVA


%Z 7.926

Fault Level For FLP-1 VFD PANEL

At Incomer Side
%Z= 7.926 ohm
Fault Current = 8.776 KA
fault level = 6.3 MVA

Fault current for 20HP Motor with VFD

FLC = 15 = 32.607 A 3c,6sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.1512 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 7.926+43.8960 1000*0.415*0.415
= 69560.27 A = 43.896 ohm p.u
51.822
= 1342.292 A
motor contribution,
Imc 4*FLC = 4*32.607 = 130.4293 A

Ifault = Inf + Imc = 1342.292+130.429


= 1472.722 A

Fault current for 10HP Motor with VFD

FLC = 7.5 = 16.304 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 7.926+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
113.369
= 613.574 A
motor contribution,
Imc 4*FLC = 4*16.304 = 65.2147 A

Ifault = Inf + Imc = 613.57+65.21


= 678.789 A

Fault Level For OMC MCC PANEL/MCC3

At Incomer Side
%Z= 5.432ohm p.u …(at F19)
Fault Current = 12.80 KA
fault level = 9.20 MVA

Fault current for 2.2KW Motor

FLC = 2.2 = 4.782 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.432+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
110.875
= 627.376 A
motor contribution,
Imc 4*FLC = 4*4.78 = 19.12963633 A

Ifault = Inf + Imc = 627.376+19.12


= 646.5052395 A
Fault current for 3.7KW Motor

FLC = 3.7 = 8.043 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.432+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
110.875
= 627.376 A
motor contribution,
Imc 4*FLC = 4*8.043 = 32.17257019 A

Ifault = Inf + Imc = 627.376+32.17


= 659.548 A

Fault current for 5.5KW Motor

FLC = 5.5 = 11.956 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.432+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
110.875
= 627.376 A
motor contribution,
Imc 4*FLC = 4*11.956 = 47.8241 A

Ifault = Inf + Imc = 627.376+47.824


= 675.200 A

Fault current for 7.5KW Motor

FLC = 7.5 = 16.304 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.432+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
110.875
= 627.376 A
motor contribution,
Imc 4*FLC = 4*16.304 = 65.2147 A

Ifault = Inf + Imc = 627.376+65.214


= 692.590 A
Fault Level For OMC SCIT PANEL/MCC4

At Incomer Side
%Z= 5.432ohm p.u …(at F22)
Fault Current = 12.80 KA
fault level = 9.20 MVA

Fault current for 1.5KW Motor

FLC = 1.5 = 3.261 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.432+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
110.875
= 627.376 A
motor contribution,
Imc 4*FLC = 4*3.261 = 13.04293386 A

Ifault = Inf + Imc = 627.376+13.04


= 640.418537 A

Fault current for 2.2KW Motor

FLC = 2.2 = 4.782 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.432+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
110.875
= 627.376 A
motor contribution,
Imc 4*FLC = 4*4.78 = 19.12963633 A

Ifault = Inf + Imc = 627.376+19.12


= 646.5052395 A

Fault current for 3.7KW Motor

FLC = 3.7 = 8.043 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.432+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
110.875
= 627.376 A
motor contribution,
Imc 4*FLC = 4*8.043 = 32.17257019 A

Ifault = Inf + Imc = 627.376+32.17


= 659.548 A

Fault current for 5.5KW Motor

FLC = 5.5 = 11.956 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.432+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
110.875
= 627.376 A
motor contribution,
Imc 4*FLC = 4*11.956 = 47.8241 A

Ifault = Inf + Imc = 627.376+47.824


= 675.200 A

Fault current for 7.5KW Motor

FLC = 7.5 = 16.304 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.432+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
110.875
= 627.376 A
motor contribution,
Imc 4*FLC = 4*16.304 = 65.2147 A

Ifault = Inf + Imc = 627.376+65.214


= 692.590 A

Fault Level For OMC RVPD/MCC6

At Incomer Side
%Z= 4.538 ohm p.u …(at F17)
Fault Current = 15.320 KA
fault level = 11.01 MVA
Fault current for 2.2KW Motor

FLC = 2.2 = 4.782 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 4.538+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
109.981
= 632.475 A
motor contribution,
Imc 4*FLC = 4*4.78 = 19.12963633 A

Ifault = Inf + Imc = 632.475+19.12


= 651.604973 A

Fault current for 3.7KW Motor

FLC = 3.7 = 8.043 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 4.538+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
109.981
= 632.475 A
motor contribution,
Imc 4*FLC = 4*8.043 = 32.17257019 A

Ifault = Inf + Imc = 632.475+32.17


= 664.648 A

Fault Level For HPS CT Panel

At Incomer Side
%Z= 5.86 ohm p.u …(at F8)
Fault Current = 11.856 KA
fault level = 8.522 MVA

Fault current for 20HP Motor

FLC = 11.25 = 24.456 A 3c,4sq mm, Cu Unarmed wire = 30m


0.415*0.8*0.8*1.732 Z = 0.17 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.86+49.354 1000*0.415*0.415
= 69560.27 A = 49.354 ohm p.u
55.214
= 1259.830 A
motor contribution,
Imc 4*FLC = 4*24.456 = 97.822 A

Ifault = Inf + Imc = 1259.83+97.82


= 1357.652 A

Fault Level For Cooling Tower VFD Mains

At Incomer Side
%Z= 42.5 ohm p.u …(at F34)
Fault Current = 1.63 KA
fault level = 1.175 MVA

Fault current for 20HP Motor

FLC = 11.25 = 24.456 A 3c,4sq mm, Cu Unarmed wire = 30m


0.415*0.8*0.8*1.732 Z = 0.17 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.86+49.354 1000*0.415*0.415
= 69560.27 A = 49.354 ohm p.u
55.214
= 1259.830 A
motor contribution,
Imc 4*FLC = 4*24.456 = 97.822 A

Ifault = Inf + Imc = 1259.83+97.82


= 1357.652 A

Fault Level For ETP Panel

At Incomer Side
%Z= 11.78ohm p.u
Fault Current = 5.90 KA
fault level = 4.24 MVA

Fault current for 1HP Motor

FLC = 0.75 = 1.630 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 11.78+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
117.223
= 593.401 A
motor contribution,
Imc 4*FLC = 4*1.63 = 6.52146693 A

Ifault = Inf + Imc = 593.401+6.521


= 599.9226766 A

Fault current for 1.5HP Motor

FLC = 1.1 = 2.391 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 11.78+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
117.223
= 593.401 A
motor contribution,
Imc 4*FLC = 4*2.391 = 9.564818164 A

Ifault = Inf + Imc = 593.401+9.56


= 602.966 A

Fault current for 3HP Motor

FLC = 2.25 = 4.891 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 11.78+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
117.223
= 593.401 A
motor contribution,
Imc 4*FLC = 4*4.891 = 19.56440079 A

Ifault = Inf + Imc = 593.401+19.56


= 612.966 A

Fault current for 5HP Motor

FLC = 3.75 = 8.152 A 3c,1.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.6 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 11.78+174.19 1000*0.415*0.415
= 69560.27 A = 174.191 ohm p.u
185.97
= 374.040 A
motor contribution,
Imc 4*FLC = 4*8.152 = 32.60733465 A

Ifault = Inf + Imc = 374.04+32.60


= 406.648 A

Fault current for 5HP Motor

FLC = 3.75 = 8.152 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 11.78+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
117.223
= 593.401 A
motor contribution,
Imc 4*FLC = 4*8.152 = 32.60733465 A

Ifault = Inf + Imc = 593.401+32.60


= 626.009 A

Fault current for 7.5HP Motor

FLC = 5.625 = 12.228 A 3c,2.5sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.3632 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 11.78+105.443 1000*0.415*0.415
= 69560.27 A = 105.443 ohm p.u
117.223
= 593.401 A
motor contribution,
Imc 4*FLC = 4*12.228 = 48.91100198 A

Ifault = Inf + Imc = 593.401+48.911


= 642.312 A

Fault current for 7.5HP Motor

FLC = 5.625 = 12.228 A 3c,4sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.2272 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 11.78+65.960 1000*0.415*0.415
= 69560.27 A = 65.960 ohm p.u
77.74
= 894.781 A
motor contribution,
Imc 4*FLC = 4*12.228 = 48.91100198 A

Ifault = Inf + Imc = 894.78+48.911


= 943.692 A

Fault current for 30HP Motor

FLC = 22.5 = 48.911 A 3c,6sq mm, Cu Unarmed wire = 40m


0.415*0.8*0.8*1.732 Z = 0.1512 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 11.78+43.89 1000*0.415*0.415
= 69560.27 A = 43.896 ohm p.u
55.67
= 1249.511 A
motor contribution,
Imc 4*FLC = 4*48.911 = 195.6440079 A

Ifault = Inf + Imc = 1249.511+195.64


= 1445.155 A

Fault current for ultrafilteration Mains

Ifault = Ib = Ib = 69560.27 4c, 2.5sqmm, Cu unarmed wire=30m


%Z % Z at incomer+ %Z cable 11.78+79.083 Z = 0.2724 ohms
= 69560.27 A
90.863 %Z cable = Z * 50000
= 765.551 A 1000*0.415*0.415
= 79.083 ohm p.u

Fault current for HPRO Mains/ ATFD Mains/ RO Mains

Ifault = Ib = Ib = 69560.27 4c, 6sqmm, Cu unarmed wire=30m


%Z % Z at incomer+ %Z cable 11.78+32.922 Z = 0.1134 ohms
= 69560.27 A
44.702 %Z cable = Z * 50000
= 1556.089 A 1000*0.415*0.415
= 32.922 ohm p.u

Fault current for MEE Mains

Ifault = Ib = Ib = 69560.27 3.5c 95sqmm, AL XLPE Cable = 80m


%Z % Z at incomer+ %Z cable 11.78+9.058 Z = 0.0312 ohms
= 69560.27 A
20.838 %Z cable = Z * 50000
= 3338.145 A 1000*0.415*0.415
= 9.058 ohm p.u

Fault Level For MEE Panel

At Incomer Side
%Z= 20.838 ohm p.u
Fault Current = 3.338 KA
fault level = 2.399 MVA

Fault current for 1.5kw Motor

FLC = 1.5 = 3.261 A 3c,2.5sq mm, Cu Unarmed wire = 20m


0.415*0.8*0.8*1.732 Z = 0.18 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 20.838+52.25 1000*0.415*0.415
= 69560.27 A = 52.257 ohm p.u
73.088
= 951.733 A
motor contribution,
Imc 4*FLC = 4*3.261 = 13.043 A

Ifault = Inf + Imc = 951.733+13.043


= 964.776 A

Fault current for 2.2kw Motor

FLC = 2.2 = 4.782 A 3c,2.5sq mm, Cu Unarmed wire = 20m


0.415*0.8*0.8*1.732 Z = 0.18 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 20.838+52.25 1000*0.415*0.415
= 69560.27 A = 52.257 ohm p.u
73.088
= 951.733 A
motor contribution,
Imc 4*FLC = 4*4.782 = 19.130 A

Ifault = Inf + Imc = 951.733+19.130


= 970.863 A

Fault current for 3.7kw Motor


FLC = 3.7 = 8.043 A 3c,2.5sq mm, Cu Unarmed wire = 20m
0.415*0.8*0.8*1.732 Z = 0.18 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 20.838+52.25 1000*0.415*0.415
= 69560.27 A = 52.257 ohm p.u
73.088
= 951.733 A
motor contribution,
Imc 4*FLC = 4*8.043 = 32.173 A

Ifault = Inf + Imc = 951.733+32.173


= 983.906 A

Fault current for 7.5kw Motor

FLC = 7.5 = 16.304 A 3c,2.5sq mm, Cu Unarmed wire = 20m


0.415*0.8*0.8*1.732 Z = 0.18 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 20.838+52.25 1000*0.415*0.415
= 69560.27 A = 52.257 ohm p.u
73.088
= 951.733 A
motor contribution,
Imc 4*FLC = 4*16.304 = 65.215 A

Ifault = Inf + Imc = 951.733+65.215


= 1016.948 A

Fault Level For ATFD Panel

At Incomer Side
%Z= 44.702 ohm p.u
Fault Current = 1.556 KA
fault level = 1.119 MVA

Fault current for 0.5HP Motor

FLC = 0.375 = 0.815 A 3c,2.5sq mm, Cu Unarmed wire = 15m


0.415*0.8*0.8*1.732 Z = 0.136 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 44.702+39.483 1000*0.415*0.415
= 69560.27 A = 39.483 ohm p.u
84.185
= 826.279 A
motor contribution,
Imc 4*FLC = 4*0.815 = 3.261 A

Ifault = Inf + Imc = 826.27+3.261


= 829.539 A

Fault current for 1HP Motor

FLC = 0.75 = 1.630 A 3c,2.5sq mm, Cu Unarmed wire = 15m


0.415*0.8*0.8*1.732 Z = 0.136 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 44.702+39.483 1000*0.415*0.415
= 69560.27 A = 39.483 ohm p.u
84.185
= 826.279 A
motor contribution,
Imc 4*FLC = 4*1.63 = 6.521 A

Ifault = Inf + Imc = 826.27+6.521


= 832.800 A

Fault current for 15HP Motor

FLC = 11.1 = 24.129 A 3c,4sq mm, Cu Unarmed wire = 15m


0.415*0.8*0.8*1.732 Z = 0.08521 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 44.702+24.738 1000*0.415*0.415
= 69560.27 A = 24.738 ohm p.u
69.44
= 1001.732 A
motor contribution,
Imc 4*FLC = 4*24.129 = 96.518 A

Ifault = Inf + Imc = 1001.732+96.518


= 1098.250 A

Fault Level For Fire Hydrant Panel

At Incomer Side
%Z= 8.161 ohm p.u
Fault Current = 8.523 KA
fault level = 6.127 MVA

Fault current for 7.5HP Motor


FLC = 5.5 = 11.956 A 3c,2.5sq mm, Cu Unarmed wire = 10m
0.415*0.8*0.8*1.732 Z = 0.09 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 8.161+26.129 1000*0.415*0.415
= 69560.27 A = 26.129 ohm p.u
34.29
= 2028.588 A
motor contribution,
Imc 4*FLC = 4*11.956 = 47.824 A

Ifault = Inf + Imc = 2028.588+47.82


= 2076.412 A

Fault current for 75HP Motor

FLC = 55 = 119.560 A 3c, 35


0.415*0.8*0.8*1.732 Z = 0 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 8.161+0 1000*0.415*0.415
= 69560.27 A = 0.000 ohm p.u
17.161
= 4053.393 A
motor contribution,
Imc 4*FLC = 4*11.956 = 478.241 A

Ifault = Inf + Imc = 2028.588+47.82


= 4531.633 A

Fault Level For Fire Sprinkler Panel

At Incomer Side of Fire Hydrant


%Z= 8.161 ohm p.u
Fault Current = 8.523 KA
fault level = 6.127 MVA

Fault current for Fire Sprinkler Main

Ifault = Ib = Ib = 69560.27 3.5c 95sqmm, AL XLPE Cable = 80m


%Z % Z at incomer+ %Z cable 11.78+9.058 Z = 0.0312 ohms
= 69560.27 A
20.838 %Z cable = Z * 50000
= 3338.145 A 1000*0.415*0.415
= 9.058 ohm p.u
Fault current for 7.5kw Motor

FLC = 7.5 = 16.304 A 3c,2.5sq mm, Cu Unarmed wire = 10m


0.415*0.8*0.8*1.732 Z = 0.09 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 8.161+26.129 1000*0.415*0.415
= 69560.27 A = 26.129 ohm p.u
34.29
= 2028.588 A
motor contribution,
Imc 4*FLC = 4*20.217 = 65.215 A

Ifault = Inf + Imc = 2028.588+47.82


= 2093.802 A

Fault current for 9.3kw Motor

FLC = 9.3 = 20.217 A 3c,2.5sq mm, Cu Unarmed wire = 10m


0.415*0.8*0.8*1.732 Z = 0.09 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 8.161+26.129 1000*0.415*0.415
= 69560.27 A = 26.129 ohm p.u
34.29
= 2028.588 A
motor contribution,
Imc 4*FLC = 4*20.217 = 80.866 A

Ifault = Inf + Imc = 2028.588+47.82


= 2109.454 A

Fault current for 75HP Motor

FLC = 55 = 119.560 A 3c, 35


0.415*0.8*0.8*1.732 Z = 0 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 8.161+0 1000*0.415*0.415
= 69560.27 A = 0.000 ohm p.u
17.161
= 4053.393 A
motor contribution,
Imc 4*FLC = 4*11.956 = 478.241 A

Ifault = Inf + Imc = 2028.588+47.82


= 4531.633 A
Fault Level For DM Plant MCC Panel

At Incomer Side
%Z= 23.664 ohm p.u …(at F14)
Fault Current = 2.29 KA
fault level = 2.110 MVA

Fault current for 1.1KW Motor

FLC = 1.1 = 2.391 A 3c,2.5sq mm, Cu Unarmed wire = 20m


0.415*0.8*0.8*1.732 Z = 0.181 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 23.66+52.54 1000*0.415*0.415
= 69560.27 A = 52.548 ohm p.u
76.2
= 912.864 A
motor contribution,
Imc 4*FLC = 4*2.391 = 9.565 A

Ifault = Inf + Imc = 912.86+9.565


= 922.429 A

Fault current for 2.2KW Motor

FLC = 2.2 = 4.782 A 3c,2.5sq mm, Cu Unarmed wire = 20m


0.415*0.8*0.8*1.732 Z = 0.181 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 23.66+52.54 1000*0.415*0.415
= 69560.27 A = 52.548 ohm p.u
76.2
= 912.864 A
motor contribution,
Imc 4*FLC = 4*4.782 = 19.130 A

Ifault = Inf + Imc = 912.86+19.130


= 931.994 A

Fault current for 3.7KW Motor

FLC = 3.7 = 8.043 A 3c,2.5sq mm, Cu Unarmed wire = 20m


0.415*0.8*0.8*1.732 Z = 0.181 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 23.66+52.54 1000*0.415*0.415
= 69560.27 A = 52.548 ohm p.u
76.2
= 912.864 A
motor contribution,
Imc 4*FLC = 4*8.043 = 32.173 A

Ifault = Inf + Imc = 912.86+32.173


= 945.037 A

Fault Level For WareHouse Panel

At Incomer Side
%Z= 20.47 ohm p.u …(at F)
Fault Current = 3.39 KA
fault level = 2.440 MVA

Fault current for 3.7KW Motor

FLC = 3.7 = 8.043 A 3c,2.5sq mm, Cu Unarmed wire = 20m


0.415*0.8*0.8*1.732 Z = 0.181 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 20.47+52.54 1000*0.415*0.415
= 69560.27 A = 52.548 ohm p.u
73.01
= 952.750 A
motor contribution,
Imc 4*FLC = 4*8.043 = 32.173 A

Ifault = Inf + Imc = 912.86+9.565


= 984.922 A

Fault Level For CHILLING Panel -1

At Incomer Side
%Z= 5.896 ohm p.u …(at F21)
Fault Current = 11.79 KA
fault level = 8.480 MVA

Fault current for HPS-1/HPS-2 mains

Ifault = Ib = Ib = 69560.27 4c, 6sqmm, CU unarmed wire = 10m


%Z % Z at incomer+ %Z cable 5.896+10.97 Z = 0.0378 ohms
= 69560.27 A
16.866 %Z cable = Z * 50000
= 4124.290 A 1000*0.415*0.415
= 10.974 ohm p.u

Fault current for 4KW Motor

FLC = 4 = 8.695 A 3c,2.5sq mm, Cu Unarmed wire = 10m


0.415*0.8*0.8*1.732 Z = 0.0908 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 16.866+26.361 1000*0.415*0.415
= 69560.27 A = 26.361 ohm p.u
43.227
= 1609.186 A
motor contribution,
Imc 4*FLC = 4*8.695 = 34.781 A

Ifault = Inf + Imc = 1609.186+34.781


= 1643.967 A

Fault current for 11KW Motor

FLC = 11 = 23.912 A 3c,2.5*2 sq mm, Cu Unarmed wire = 15m


0.415*0.8*0.8*1.732 Z = 0.0681 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.896+19.771 1000*0.415*0.415
= 69560.27 A = 19.771 ohm p.u
25.667
= 2710.105 A
motor contribution,
Imc 4*FLC = 4*23.912 = 95.648 A

Ifault = Inf + Imc = 2710.105+95.648


= 2805.753 A

Fault current for 11KW Motor

FLC = 11 = 23.912 A 3c,2.5*2 sq mm, Cu Unarmed wire = 15m


0.415*0.8*0.8*1.732 Z = 0.0681 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 5.896+19.771 1000*0.415*0.415
= 69560.27 A = 19.771 ohm p.u
25.667
= 2710.105 A
motor contribution,
Imc 4*FLC = 4*23.912 = 95.648 A

Ifault = Inf + Imc = 2710.105+95.648


= 2805.753 A
Fault Level For CHILLING Panel -2

At Incomer Side
%Z= 9.293 ohm p.u …(at F27)
Fault Current = 7.48 KA
fault level = 5.380 MVA

Fault current for 2.2KW Motor

FLC = 2.2 = 4.782 A 3c,2.5sq mm, Cu Unarmed wire = 15m


0.415*0.8*0.8*1.732 Z = 0.136 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 9.293+39.483 1000*0.415*0.415
= 69560.27 A = 39.483 ohm p.u
48.776
= 1426.117 A
motor contribution,
Imc 4*FLC = 4*4.782 = 19.130 A

Ifault = Inf + Imc = 1426.117+19.130


= 1445.246 A

Fault current for 5.5KW Motor

FLC = 5.5 = 11.956 A 3c,2.5sq mm, Cu Unarmed wire = 15m


0.415*0.8*0.8*1.732 Z = 0.136 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 9.293+39.483 1000*0.415*0.415
= 69560.27 A = 39.483 ohm p.u
48.776
= 1426.117 A
motor contribution,
Imc 4*FLC = 4*11.956 = 47.824 A

Ifault = Inf + Imc = 1426.117+47.824


= 1473.941 A

Fault Level For Thermopac Panel

At Incomer Side
%Z= 6.12 ohm p.u …(at F23)
Fault Current = 11.34 KA
fault level = 8.150 MVA

Fault current for 22KW Motor

FLC = 22 = 47.824 A 3c,6sq mm, Cu Unarmed wire = 20m


0.415*0.8*0.8*1.732 Z = 0.0756 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 6.12+21.948 1000*0.415*0.415
= 69560.27 A = 21.948 ohm p.u
28.068
= 2478.277 A
motor contribution,
Imc 4*FLC = 4*47.824 = 191.296 A

Ifault = Inf + Imc = 2478.277+191.296


= 2669.573 A

Fault current for Thermopac Control Panel Mains

Ifault = Ib = Ib = 69560.27 4c, 4sqmm, CU unarmed wire = 20m


%Z % Z at incomer+ %Z cable 6.12+32.980 Z = 0.1136 ohms
= 69560.27 A
39.1 %Z cable = Z * 50000
= 1779.035 A 1000*0.415*0.415
= 32.980 ohm p.u

Fault Level For Microlab MCC Panel

At Incomer Side
%Z= 20.79 ohm p.u …(at F33)
Fault Current = 3.345 KA
fault level = 2.405 MVA

Fault current for 3.7KW Motor

FLC = 3.7 = 8.043 A 3c,2.5sq mm, Cu Unarmed wire = 15m


0.415*0.8*0.8*1.732 Z = 0.136 ohms
Nominal Fault current,
Inf = Ib = Ib = 69560.27 %Z cable = Z * 50000
%Z % Z at incomer+ %Z cable 20.79+39.483 1000*0.415*0.415
= 69560.27 A = 39.483 ohm p.u
60.273
= 1154.087 A
motor contribution,
Imc 4*FLC = 4*8.043 = 32.173 A

Ifault = Inf + Imc = 1154.087+32.173


= 1186.259 A