02 pcs fountain water filter pumps are not connected to BMS, fire pump room B2 zone D
02 pcs fountain water booster pumps are not connected to BMS, fire pump room B2 zone D
03 pcs fire Pumps and domestic water pumps are connected but only Monitoring, fire pump room B2 zone D, 02 pcs tanks are not
connected
03 pcs Grey water Booster pumps are connected but only Monitoring, B2 Zone A
02 pcs Grey water feed pumps are not connected to BMS, B2 Zone A ( Both Tanks are also not connected)
02 pcs Blower fans are also not connected to BMS in Grey water pump room B2 Zone A
02 pcs Submersible pumps in grey water pump room connected to BMS but only Monitoring, Grey water pump room B2 Zone A
04 pcs Irrigation pumps are connected to BMS but only Monitoring, Also 02 tanks are not connected
04 pcs TES Room B2 Zone B, Secondary pumps are not connected to BMS
03 pcs TES Room B2 Zone B, 03 pcs Heat Exchanger pumps are not connected to BMS
03 pcs TES Room B2 Zone B, Ice Tank pumps are not connected to BMS
02 pcs TES Room B2 Zone B, Submersible pumps are not connected to BMS
04 pcs Submersible pumps in B2 Car parking area zone A, not connected to BMS
04 pcs Submersible pumps in B2 Car parking area zone D, not connected to BMS
13 pcs Smoke Exhaust Fans in B1 & B2 Car Parking Area All zones, not connected to BMS
04 pcs primary Pumps service floor zone D, Not connected to BMS
06 Pcs Smoke Exhaust Fans service floor all zones, are not connected to BMS
04 pcs Fresh Air Supply Fans for stair case are not connected to BMS
04 pcs Toilet exhaust fans 04 pcs service floor are not connected to BMS
Rectification Rectification
System Location Notes Photos Remarks
status Date
Fountain B2 Fire Not connected to Yes
filtration Pumps pump BMS
02 pcs Room No
Zone D
Rectification
System Location Notes Photos Rectification status Remarks
Date
Toilet Exhaust Service Connected to Yes
Fans 03 PCS Floor BMS
MIX USE Zone Command
BUILDING C&D issue No
Off without
Alarm
All Exhaust
fans off
3rd one is not
connected
Court Complex – General Court Building - Mechanical Systems
04 pcs Irrigation Pumps in General Court, Jockey Pump is not connected to BMS, also have sequence problem, where we need jockey start
first and then simultaneously pumps 1st to 3rd.
03 pcs TES room Chilled water pumps General Court, it have no strainer, no non-return valve and have no stand by pump.
03 pcs Fire pump room basement west side General court, all equipment are connected, remarks are just Monitoring.
04 pcs Smoke Exhaust Fans in car parking area, connected to BMS but not working at different level of Co2, currently it is on 25% of Co2.
01 pc Pressurized air fan to stair case east side AHU 09, connected to BMS but not working.
03 pcs Ventilation fans east side car parking area not working, including TES room also
02 pcs Ventilation fans west side car parking area not working, including fire pump room also
Rectification Rectification
System Location Notes Photos Remarks
status Date
Irrigation Basement Not connected to Yes
Jockey Car BMS
Pump Parking Should be first No
Area Jockey Start and
irrigation then other
Pump simultaneously
Room Tank Level is not
West side connected
Pump No.03 is not
working
Rectification Rectification
System Location Notes Photos Remarks
status Date
Transfer Masjid Not Connected
Pumps Transfer to BMS Yes
03 Pcs Pump No
room
east side