Court Complex – Criminal Court Building - Mechanical Systems

 02 pcs fountain water filter pumps are not connected to BMS, fire pump room B2 zone D
 02 pcs fountain water booster pumps are not connected to BMS, fire pump room B2 zone D
 03 pcs fire Pumps and domestic water pumps are connected but only Monitoring, fire pump room B2 zone D, 02 pcs tanks are not
connected
 03 pcs Grey water Booster pumps are connected but only Monitoring, B2 Zone A
 02 pcs Grey water feed pumps are not connected to BMS, B2 Zone A ( Both Tanks are also not connected)
 02 pcs Blower fans are also not connected to BMS in Grey water pump room B2 Zone A
 02 pcs Submersible pumps in grey water pump room connected to BMS but only Monitoring, Grey water pump room B2 Zone A
 04 pcs Irrigation pumps are connected to BMS but only Monitoring, Also 02 tanks are not connected
 04 pcs TES Room B2 Zone B, Secondary pumps are not connected to BMS
 03 pcs TES Room B2 Zone B, 03 pcs Heat Exchanger pumps are not connected to BMS
 03 pcs TES Room B2 Zone B, Ice Tank pumps are not connected to BMS
 02 pcs TES Room B2 Zone B, Submersible pumps are not connected to BMS
 04 pcs Submersible pumps in B2 Car parking area zone A, not connected to BMS
 04 pcs Submersible pumps in B2 Car parking area zone D, not connected to BMS
 13 pcs Smoke Exhaust Fans in B1 & B2 Car Parking Area All zones, not connected to BMS
 04 pcs primary Pumps service floor zone D, Not connected to BMS
 06 Pcs Smoke Exhaust Fans service floor all zones, are not connected to BMS
 04 pcs Fresh Air Supply Fans for stair case are not connected to BMS
 04 pcs Toilet exhaust fans 04 pcs service floor are not connected to BMS
Rectification Rectification
System Location Notes Photos Remarks
status Date
Fountain B2 Fire  Not connected to Yes
filtration Pumps pump BMS
02 pcs Room No
Zone D

Fountain B2 Fire  Not connected to Yes


Booster Pumps pump BMS
02 pcs Room No
Zone D

Domestic water B2 Fire  Connected to BMS Yes


pumps pump just
Room MONITORING No
Zone D
Fire Pumps with B2 Fire  Connected to BMS Yes
Jockey Pump pump just
Room MONITORING No
ALSO ALL Zone D
WATER
TANKS ARE
CONNECTED
FOR ITS
LEVEL
MONITORING
B2 Gray  Connected to BMS Yes
Gray Water Water just
Booster pumps pumps MONITORING No
03 pcs Room
Zone A Both Tanks are
not connected to
BMS

Gray water feed B2 Gray  Not Connected to Yes


pumps 02 pcs Water BMS
pumps No
Room
Zone A

Blower Fan for B2 Gray  Not Connected to Yes


Raw water tank Water BMS
02 pcs pumps No
Room
Zone A
Submersible B2 Gray  Connected to BMS Yes
pumps for waste Water just
water pumps MONITORING No
Room
Zone A

Irrigation B2 irrigation  Connected to BMS Yes


pumps 04 pumps Room just
pcs Zone A MONITORING No

Secondary B2 TES Room  Not Connected to Yes


pumps 04 Zone B BMS
pcs No

Heat B2 TES Room  Not Connected to Yes


Exchange Zone B BMS
r pumps No
03 pcs
Ice Tank B2 TES Room  Not Connected to Yes
pumps 03 Zone B BMS
pcs No

Submersib B2 TES  Not Connected to Yes


le pumps Room Zone B BMS
02 pcs No

Primary Service Floor  Not Connected to Yes


Pumps Primary Pump BMS
Room Zone D No

Submersib B2 Room  Not Connected to Yes


le pumps Zone A BMS
04 pcs No
Submersib B2 Room  Not Connected to Yes
le pumps Zone D BMS
04 pcs No

Smoke Service Floor  Not Connected to Yes


Exhaust Zone D&B BMS
Fans 02 No
pcs

Smoke Service Floor  Not Connected to Yes


Exhaust Zone A&C BMS
Fans 02 No
pcs

Fresh Air Service Floor  Not Connected to Yes


Supply Zone D&B BMS
Fans to No
Stair Case
02 pcs
Fresh Air Service Floor  Not Connected to Yes
Supply Zone A&C BMS
Fans to No
Stair Case
02 pcs

Toilet Service Floor  Not Connected to Yes


Exhaust Zone D&B BMS
Fans 02 No
pcs

Toilet Service Floor  Not Connected to Yes


Exhaust Zone A&C BMS
Fans 02 No
pcs

Smoke B1 & B2 Car  Not Connected to Yes


Exhaust Parking Area BMS
Fans 13 in Criminal No
Pcs Court
Court Complex – Mix Use Building - Mechanical Systems
 02 pcs Service floor toilet exhaust fans are connected but 01 pc is not connected to BMS, also without alarm switched off,
may have command problem

Rectification
System Location Notes Photos Rectification status Remarks
Date
Toilet Exhaust Service  Connected to Yes
Fans 03 PCS Floor BMS
MIX USE Zone  Command
BUILDING C&D issue No
 Off without
Alarm
 All Exhaust
fans off
 3rd one is not
connected
Court Complex – General Court Building - Mechanical Systems
 04 pcs Irrigation Pumps in General Court, Jockey Pump is not connected to BMS, also have sequence problem, where we need jockey start
first and then simultaneously pumps 1st to 3rd.
 03 pcs TES room Chilled water pumps General Court, it have no strainer, no non-return valve and have no stand by pump.
 03 pcs Fire pump room basement west side General court, all equipment are connected, remarks are just Monitoring.
 04 pcs Smoke Exhaust Fans in car parking area, connected to BMS but not working at different level of Co2, currently it is on 25% of Co2.
 01 pc Pressurized air fan to stair case east side AHU 09, connected to BMS but not working.
 03 pcs Ventilation fans east side car parking area not working, including TES room also
 02 pcs Ventilation fans west side car parking area not working, including fire pump room also

Rectification Rectification
System Location Notes Photos Remarks
status Date
Irrigation Basement  Not connected to Yes
Jockey Car BMS
Pump Parking  Should be first No
Area Jockey Start and
irrigation then other
Pump simultaneously
Room  Tank Level is not
West side connected
 Pump No.03 is not
working

Chilled Basement  Not connected to Yes


Water TES BMS
Pumps Room,  No Strainer in line No
East Side  No Non Return
Valve
 No Stand By
Pump
Rectification Rectification
System Location Notes Photos Remarks
status Date
Lower Basement  Connected to Yes
Zone Fire BMS just for
Pumps Pump Monitoring No
Room
West
Side

Lower Basement  Connected to


Yes
Zone Fire BMS just for
Pumps Pump Monitoring
Room No
West
Side

Fire Basement  Connected to


Pumps Fire BMS just for Yes
with Pump Monitoring
Jockey Room No
Pump West
Side
Rectification Rectification
System Location Notes Photos Remarks
status Date
Pressurized Service  Connected to
Air Fan to Floor BMS Yes
Stair case East Side  Not working by
AHU 09 Command No

Smoke Basement  Connected to


Exhaust Car BMS Yes
Fans 04 Parking  Not working on
pcs Area East any level of Co2 No
and West
Sides

Ventilation Basement  Connected to


Fans Car Parking BMS Yes
Basement Area East  Not Working
Side and No
03 pcs TES Room

Ventilation Basement  Connected to


West Side Yes
Fans BMS
Basement Car Parking  Not Working
Area and No
02 pcs Fire Pump
Room
Court Complex – Masjid Building - Mechanical Systems

 03 pcs Masjid Transfer Pumps are not connected to BMS


 03 pcs Masjid Booster Pumps are not connected to BMS
 02 pcs Masjid Public toilets/Ladies toilets & Gents Toilets exhaust fans are connected to BMS

Rectification Rectification
System Location Notes Photos Remarks
status Date
Transfer Masjid  Not Connected
Pumps Transfer to BMS Yes
03 Pcs Pump No
room
east side

Booster Masjid  Not Connected Yes


Pumps Booster to BMS
03 Pcs Pump No
room
North
side

Toilet Masjid  Not Connected


Exhaust Service to BMS Yes
Fans floor
No
02 Pcs North &
East
sides