Submit Deration calculation.

01/12/2022
Approved with Comments:-
1.DG set shall be heat exchanger type prime duty diesel generating set.
2. Submit GA drawing of DG sets and all associated system as per BOQ and Specification.DG set and
accessories shall comply the BOQ, Specification and shall meet the Site requirement.
3. Submit Calculation for DG self motor selection with selected Ah of Batteries and required cranking current.
4. Submit Test certificate of Alternator and DG set with required insulation class.
5 Submit QAP for DG sets.
Submit Data sheet
with control wiring.

Submit GA drawing Day oil fuel tank including glass type level
indicator and level controllers with BMS integration, float valves
etc. (Tank shall be painted with 2 coats of red oxide primer & 1
coat enamle paint outside) as per BOQ.

5mm Thick