You are on page 1of 1

SERVICE ENTRANCE CAP

SCHEDULE OF LOADS
GENERAL NOTES: CKT. #
LOAD
DESCRIPTION
QUANTITY OF LOADS
L.O. C.O. OTHERS S1
SWITCHES
S2
230 V 60HZ, SINGLE PHASE

S3 S3W
VOLT
LOAD IN
V.A. AMPERE
BRANCH
CIRCUIT
PROTECTION
WIRE SIZE CU. (MM²) UPVC
2 - 14 MM² THHN CU. WIRE
IN 32 MMØ UPVC CONDUIT
1.0 ALL ELECTRICAL WORKS INDICATED HEREIN SHALL BE 1 LO 8 @ 11 W 8 -- -- 1 2 O 2 230 88 0.38 15 AT 2 - 2.0 MM², THHN, CU. 20 MM Ø UPVC PIPE
PANEL BOARD

PANEL BOARD
DONE IN ACCORDANCE WITH LATEST EDITION OF THE LO 9 @ 11 W 9
-- -- 1 --
2 2 0 230 109 0.43 15 AT 2 - 2.0 MM², THHN, CU. 20 MM Ø UPVC PIPE
LO 2 @ 5 W WALL LIGHTING
PHILIPPINE ELECTRICAL CODE, THE RULES & REGULATION 2

LO 6 @ 11 W __ AT
OF THE MUNICIPALITY CONCERNED & THE LOCAL POWER 3
LO 2 @ 5 W WALL LIGHTING
11 -- -- 3 0 0 0 230 121 0.53 15 AT 2 - 2.0 MM², THHN, CU. 20 MM Ø UPVC PIPE
15AT 15AT
COMPANY (AKELCO). 4 LO 6 @ 11 W 6 -- -- 5 230 66 0.29 15 AT 2 - 2.0 MM², THHN, CU. 20 MM Ø UPVC PIPE 2 - 2.0 MM²,THHN CU, WIRE 2 - 2.0 MM²,THHN CU, WIRE
LO 1 15AT 15AT
2 LO

2.0 ALL ELECTRICAL INSTALLATION SHALL BE EMBEDDED IN 2 - 2.0 MM²,THHN CU, WIRE 2 - 2.0 MM²,THHN CU, WIRE
5 CONVENIENT OUTLET @ 180 V -- 12 -- -- -- -- -- 230 2160 9.39 20 AT 2 - 3.5 MM², THHN, CU. 20 MM Ø UPVC PIPE LO 3 4 LO
CONCRETE OR MASONRY AND CONCEALED IN CEILINGS & 20AT 30AT
2 - 3.5 MM²,THHN CU, WIRE 2 - 3.5 MM²,THHN CU, WIRE
PARTITIONS WITH APPROPRIATE ELECTRICAL ACCESSORIES. 6 2 HP ACU OUTLET -- 7 -- -- -- -- -- 230 1492 6.49 30 AT 2 - 3.5 MM², THHN, CU. 20 MM Ø UPVC PIPE CO 5 20AT 30AT
6 ACU

2 - 3.5 MM²,THHN CU, WIRE CONDUIT ONLY


3.0 ALL LIGHT SWITCHES SHALL BE THE APPROVED FLUSH 7 CONVENIENT OUTLET @ 180 V -- 12 -- -- -- -- -- 230 2160 9.39 20 AT 20 MM Ø UPVC PIPE
CO 7 SPARE
8 SPARE
2 - 3.5 MM², THHN, CU.
TYPE INSTALLED 1450 MM FROM THE FINISH FLOOR LINE, SPARE 9 CONDUIT ONLY
8 SPARE @ 500 VA -- -- -- -- -- -- -- 230 500 2.17 SPARE CONDUIT ONLY
& THE CONVENIENCE OUTLETS SHALL BE INSTALLED
300 MM FROM THE FINISH FLOOR LINE. 9 SPARE @ 500 VA -- -- -- -- -- -- -- 230 500 2.17 SPARE CONDUIT ONLY

4.0 THE MINIMUM BRANCH CIRCUIT SHALL BE 20 AMP., T O T A L 38 25 -- 4 11 2 4 230 8,464 36.80 70 AT 2 - 14 MM², THHN, CU. WIRE 32 MM Ø UPVC PIPE
1-8.0 MM² THW GROUND WIRE
230 VOLTS, UNLESS OTHERWISE SPECIFIED ON THE PLANS.
GROUND CONNECTION

5.0 WHENEVER NECESSARY, PULL BOXES SHALL BE INSTALLED


EVEN IF THEY ARE NOT ON THE PLANS.
WIRING DESIGN ANALYSIS
6.0 SPLICING OF WIRES INSIDE THE CONDUITS IS PROHIBITED.
MAIN CIRCUIT COMPUTATION: RISER DIAGRAM
NOT TO SCALE
7.0 ALL ELECTRICAL MATERIALS USED / TO BE INSTALLED MAIN: CONDUCTOR 2 - 14 MM², THHN CU. WIRE
MUST BE NEW, BEARING THE LABELS AND/OR THE BRAND NAMES. CONDUIT PIPE :32 MM I.D., UPVC PIPE
Ic = 8,464 = 36.80
_____ Amp MAIN CIRCUIT PROTECTION: 70 AT, 2P ACB MOLDED CASE CIRCUIT BREAKER
230
9.0 ALL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT
SUPERVISION OF THE DULY LICENSED ELECTRICAL ENGINEER. Itc = 36.80
_____ (1.25) = 46.00Amp
THIS SITE

LEGEND:
POWER SUPPLY LINE (C.O.)
6" DIAM RECESSED PINLIGHT;
11 W CFL BULB; WARM WHITE Sa ONE GANG SWITCH, FLUSH TYPE POWER SUPPLY LINE (L.O.)

SERVICE ENTRANCE CAP


WL WALL LAMP 5W S ab TWO GANG SWITCH, FLUSH TYPE

Sabc THREE GANG SWITCH, FLUSH TYPE M KILOWATTHOURMETER


WP WEATHER PROOF OUTLET
S3w THREE WAY SWITCH, FLUSH TYPE PANEL BOARD
CO
CONVENIENCE OUTLET, DUPLEX,
FLUSH TYPE MOLDED CASE CIRCUIT BREAKER
GROUND CONNECTION
ACU
AIR CONDITIONING OUTLET
G GENERATOR
CATV
CABLE OUTLET
VICINITY MAP
NOT TO SCALE

NOTE:
THIS DRAW ING, AS INSTRUMENT
OF SERV IC E ARE T H E IN T ELLEC TU AL
P R O P E RT Y O F T H E A R CHI TE CT ,W H E T H E R
T H E O BJ E C T F O R W H IC H T H E Y A RE M A D E
IS EXECUTED OR NOT. IT SHALL BE UNLAWFUL LICENSED ELECTRICAL ENGINEER
PROPOSED TWO (2) STOREY GILAMIE R. AREVALO E-2
F OR AN Y PERSON TO M AK E COPIES OF SAID AS COMMERCIAL-RESIDENTIAL BUILDING
FRED LESTER D. GERVACIO DOCUM ENTS FOR USE IN THE REPETITION OF
AN D F OR OT H ER P ROJ ECT S OR BU ILDIN GS, PRC NO. VALIDITY: SHOWED
W H ET H ER EX EC U T ED PART LY OR IN W H OLE,
W IT H O U T T H E W RIT T E N C O N S E N T O F T H E
A R

R.A. 9266
C H I T E C T . PTR. NO. DATE ISSUED: OWNER
7 9
TIN NO. PLACE ISSUED:

You might also like