You are on page 1of 1

CALCULATION PULLING FORCE STRINGING

Data:
Total weight of ACSR (W) 1.584 kg/m (TPG/spec.)
Total span 14400 m (Tower sch.)
Total tower 32 set (Tower sch.)
Avarage span tower to tower (L) 450 m (Tower sch.)
Total support/pulley block (N) 32 pcs (Actual condition)
Sag for stringing (S) 25 m (Stringing procedure)
Total conductor per phase 4 pcs (TPG/spec.)

Tensioning Force (T)


𝐓_𝟏=(𝐖×𝐋^𝟐)/(𝟖×𝐒)
T1 = 1603.8 kg = 15.73 kN

Pulling Force (Tmax)


𝐓_𝐦𝐚𝐱=𝐓_𝟏/ 〖𝟎 .𝟗𝟖 〗 ^𝐍 Tmax = 3061.37 kg/conductor = 30.03 kN

T = 12245.48 kg = 120.13 kN

Reference IEEE Std 524-2003 Overhead Transmission Line Conductors