Professional Documents
Culture Documents
• Voltage stability
∆Te = TS ∆δ + TD ∆ω (1)
1
a) Small signal (or small disturbance) stability It is the ability of the
power system to maintain synchronism under small disturbances. Instability
can be of two forms: (i) steady increase in rotor angle due to lack of sufficient
synchronising torque, or (ii) rotor oscillations of increasing amplitude due to
lack of sufficient damping torque. In today’s practical power systems, all
generators are equipped with automatic voltage regulators. Hence small
signal stability is largely a problem of insufficient damping of oscillations.
We are interested in the stability of the following types of oscillations
• Local modes or machine system modes are associated with the swinging
of units at a generating station with respect to the rest of the power
system.
2
(a) Large-disturbance voltage stability is the ability of the system to
control voltages within acceptable steady state values following large distur-
bances such as system faults, loss of generation, or circuit contingencies.
2 Frequency Stability
The frequency of a system depends on the active power balance. In an in-
terconnected system, change in power demand at any part of the system
will be reflected as a frequency change throughout the system. Primary
speed(frequency) control is provided by the speed governor the respective
machines while supplementary control is done by a central control that con-
trols generation.
3
Load response to frequency deviation In power system there are fre-
quency dependent and independent loads. Motor loads are frequency depen-
dent. Overall frequency-dependent characteristics of composite load may be
expressed as
∆Pe = ∆PL + D∆ω (7)
where,
∆PL = non-frequency-sensitive load change
D∆ωr = frequency-sensitive load change
D = load-damping constant(expressed as a percentage change in load
for one percentage change in frequency)
where
ωN L = steady state speed at no load
ωF L = steady state speed at full load
ω0 = nominal or rated speed
4
3 Concept of Load Sharing
When a no. of generators with drooping characteristics are connected in
parallel to share load, they will be operating at a unique frequency. We
consider two generators with droops R1 and R2 , and with outputs P1 and
P2 respectively operating at a nominal frequency f0 . If the total load on
the generators increase by ∆PL , governors increase output until they reach a
0
new common operating frequency f . The additional loads taken up by each
generator is
∆f
∆P1 = P10 − P1 =
R1
∆f
∆P2 = P20 − P2 =
R2
Hence,
∆P1 R2
=
∆P2 R1
where
1
Req = 1 1 1 (9)
R1
+ R2
+ ··· + Rn
5
Factors influencing frequency decay
t
∆f = −∆L 1 − e− T K (11)
where, K= D1 and T= M
D
PL + j(QL − VL Bc2 )
vqL + jvdL = (18)
(iq − jid )
where
q
2 2
VL = vdL + vqL (19)
mp
VL
PL = PL0 (20)
VL0
mp
VL
QL = QL0 (21)
VL0
6
Linearising equations (13) t0 (21) and simplifying, we get
0
∆id = Yd ∆Eq (22)
0
∆iq = Yq ∆Eq (23)
0
and ∆Te = K2 ∆Eq (24)
(25)
In case of single machine infinite bus system, the torque deviation ∆Te is
given as
0
∆Te = K1 ∆δ + K2 ∆Eq (26)
Thus from Eqn. (24) it is observed that a SMLB system does not exhibit
angular instability and the only dynamics is that corresponding to field flux
decay and excitation system(??). In the block diagram of Fig.(??) , K3 and
K6 are analogous to Heffron-Phillips constant.
The characteristic equation shown in Fig.(??) is
2 1 1 1 + K3 K6 KE
s + 0 + s+ 0 =0
Tdo K3 TE Tdo K3 TE
If we assume a lossless network with unity power factor load, the received
active power and voltage are given by
Eg2 sin 2δ
P = = PL (27)
2X(1 − Bc X)
Eg cos δ
V = (28)
(1 − Bc X)
where X = xg + xe
7
where P0 is the nominal power to be maintained at all voltages. The stability
of the equilibrium point is determined as
dP
<0 (30)
dV
At the load bus, using Jacobian
J1 J2 ∆δ ∆P
= (31)
J3 J4 ∆V 0
where
∂P ∂P ∂Q ∂Q
J1 = , J2 = , J3 = , J4 =
∂δ ∂V ∂δ ∂V
If J3 is non-singular, then
dP
= J2 − J1 J3−1 J4 (32)
dV
dP
If Jacobian is singular, dV = 0. The determinant of Jacobian indicates
proximity to voltage collapse. Eqn. (29) can be written as
dV ∂W
Tp =− (33)
dt ∂V
RV
where W = V1 (P0 − P )dV is the potential energy. The energy margin given
by Eqn. (34) can be used as an index for voltage security.
Z V2
∆W = (P0 − P )dV (34)
V1
If the active power is assumed constant, Q–V curve can be used for evaluating
the stability margin. Eqn.(29) can be written as
dV 1
= [Q(V ) − Q0 ] (35)
dt Tq
Eqn.(34 is replaced as
Z V2
0
∆W = (Q0 − Q)dV (36)
V1
8
where Q is the received reactive power, QL is the reactive power requirement
of load, and QC is the reactive power supplied by the reactive compensator
at the load bus. The reactive compensator is described as
1 dQC
= = V0 − V (38)
Tc dt
The criterion for stability is
dV
>0 (39)
dQC
References
[1] P. Kundur, N. J. Balu, and M. G. Lauby, Power System Stability and
Control. McGraw-hill New York, 1994, vol. 7.
[3] P. W. Sauer and M. A. Pai, Power System Dynamics and Stability. Pear-
son Education(Singapore) Pte Ltd., Delhi, India, 2002.