You are on page 1of 61

MICOM C264

HARDWARE

Imagination at work.
Summary

1) Generalities Page 3

2) Hardware Page 9

3) Board address and rules of slot positioning Page 50

4) C264 – Process bus Page 54

© 2015 General Electric Company. Proprietary. All Rights Reserved.


1.1) Modular Racks

MiCOM C264C - 4U / 40 TE MiCOM C264 - 4U / 80 TE


with 6 slots for optional boards with 15 slots for optional boards

© 2015 General Electric Company. Proprietary. All Rights Reserved.


1.2) Connections – 40TE example
5 available slots for board (project 1 slot for Ethernet switch board
dependants) (project dependants)
H G F E D C B A

Mandatory boards
(CPU / Power supply)

Connector Screwing Power supply connector


(2 RS232/485 links)

Removable wiring connectors


(maintain by 2 screws) IRIG B

© 2015 General Electric Company. Proprietary. All Rights Reserved.


1.3) Connections – 80TE example

14 available slots for board (project 1 slot for DSP board


dependants) (project dependants)

Q P O N M L K J I H G F E D C B A Mandatory boards
(CPU / Power
supply)

Connector
Screwing
Power supply
connector
(2 RS232/485 links)

Connector for CT VT
acquisition
(project dependants) Optional : IRIG B
Removable wiring connectors
(maintain by 2 screws)

© 2015 General Electric Company. Proprietary. All Rights Reserved.


1.4) Overview

© 2015 General Electric Company. Proprietary. All Rights Reserved.


1.5) Rack / Boards Overview

BIU2xx
TMU2x0

CPU264
DIU20x
AIU20x
DOU20x

CT/VT inputs
NEXT board
Redundant CPU board +
Power Optical Ethernet
Supply Link
2 serialRS232

Binary Input
boards
Digital Output Boards
Analog Input Boards

© 2015 General Electric Company. Proprietary. All Rights Reserved.


Summary

1) Generalities Page 3

2) Hardware Page 9

3) Board address and rules of slot positioning Page 50

4) C264 – Process bus Page 54

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.1) Content
● C264 cards list - Name

• CPU: Central Processor Unit Mandatory


• GHU: Graphical Human Unit
• BIU: Basic Interface Unit (power supply)
• DIU: Digital Input Unit
• DOU: Digital Output Unit
• CCU: Circuit breaker Control Unit
• HBU: High Breaker Unit
• AIU: Analogue Input Unit
• AOU: Analogue Output Unit
• SWx : Switch Units

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.1) Different kind of boards

● Mandatory cards – CPU & BIU

Central Processing Unit (CPU)


– Calculator brain
– 1 board for each C264 (Max.)

Basic Interface Unit (BIU)


– C264 power supply
– C264 default communication ports (x2)
– 1 board for each C264 (Max.)

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.1) Different kind of boards

• High break high speed Outputs Unit


(HBU)
– Digital output : 10 output relays per board (10 NO)
which are suitable for high breaking loads
– 1 slot per board
– Only one board allowed in the C264

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.1) Different kind of boards

• High break high speed Outputs Unit


(HBU)
– Digital output : 10 output relays per board (10 NO)
which are suitable for high breaking loads
– 1 slot per board
– Only one board allowed in the C264

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.2) Boards management
● Board operating state
• Each board status is represented by a multiple point status
This MPS status is displayed in MAIN C264 Fault panel in case of fault
• 4 possible states (MAIN C264 Fault panel )
 Faulty = physically present but faulty
 Missing = Board configured but physically missing
 Too many = Board not configured but physically present
 OK = Present and healthy (Not display in Fault panel !!!)

FAULT *12:45:12

HARDWARE

DISCONN
“Faulty” board list

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.2) Boards management
● Board operating state
• Each board status is represented by a multiple point status
This MPS status is displayed in MAIN C264 Fault panel in case of fault
• 4 possible states (MAIN C264 Fault panel )
 Faulty = physically present but faulty
 Missing = Board configured but physically missing
 Too many = Board not configured but physically present
 OK = Present and healthy (Not display in Fault panel !!!)

FAULT *12:45:12

HARDWARE

DISCONN
“Faulty” board list

© 2015 General Electric Company. Proprietary. All Rights Reserved.


MiCOM C264C 4/6 slots MiCOM C264 14/15
2.3) Capabilities slots
BIU 241 (power + 2RS) 1 1

CPU260 (2RS + RJ45) / CPU270 options :Optic Fx, IRIG-B, DSP 1 1

GHU 2xx : 20x=LCD, 21x=no LCD, 22x=remote 1 1

DIU200 (16 DI) / DIU211 (16DI) 6 (96 DI) 15 (240 DI)

DIU210 (16 DI) / DIU220 (16DI) cf. C264/TD cf. C264/TD

DOU200 / DOU201 (10DO) 6 (60 DO) 15 (150 DO)

CCU200 (8 DI + 4 DO) 6 (48 DI + 24 DO) 15 (120 DI + 60 DO)

AIU201 (4 AI, mA or V) 6 (24 AI) 6 (24 AI)

AIU210 (8 AI, mA) 6 (48 AI) 6 (48 AI)

AIU211 (8 AI, mA) 6 (48 AI) 6 (48 AI)

TMU200 1 (4 CT, 4 VT) 1 (4 CT, 4 VT)

TMU220 1 (4 CT, 5 VT) 1 (4 CT, 5 VT)

TMU210 C264-P C264-P

AOU200 (4AO + 4DO) 4 (24AO + 24DO) 4 (24AO + 24DO)

15
© 2015 General Electric Company. Proprietary. All Rights Reserved.
2.4) Graphical Human machine interface Unit

The GHU20x is the front panel with LCD and LEDs used for the MiCOM C264:

• 17 LEDs (13 free configurable)

• 7 pushbuttons (L/R, Open, Close, etc)

• a keypad at the front plate for local MMI management with 5 pushbuttons

• a LCD (resolution of 128 x 128 pixels /16 lines of 21 characters each)

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.4) Graphical Human machine interface Unit

The GHU21x is the front panel with LEDs used for the MiCOM C264:

• 17 LEDs (12 free configurable)

• 1 pushbutton (L/R)

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.4) Graphical Human machine interface Unit

The GHU22x is the front panel used for the MiCOM C264. This includes only a RJ11
coupler
in order to connect a remote GHU20x or GHU21x.

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.5) Basic Interface Unit - BIU24x

1°- Main characteristics :


Power Supply
1 Watchdog contact
2 DI & 2 DO used for redundancy
RS1 (232/485)
Depending of the Jumper
RS2 (232/422/485)

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.5) Basic Interface Unit - BIU24x

2°- Technical features - BIU 241


• Watchdog relays - Closed if C264 is healthy
• Auxiliary voltage converter - Supply range
– VA01 : 24 VDC
– VA02 : 48/60 VDC
– VA03 : 110/125 VDC
– VA04 : 220 VDC /230 VAC

© 2015 General Electric Company. Proprietary. All Rights Reserved.


3.2°- C264 – New BIU 261

• Main characteristics
– 60W auxiliary power supply converter
• 48VDC to 250VDC +/-20% one part number
• 48VRMS to 250VRMS +/-20%
• 44Hz to 66Hz

– Double sources redundancy AC/DC (Optional)

– Protection against polarity reversal

– The operating temperature range of the unit is


• -40C to 85C (maximum load = 40W)
• -40C to 70C (full load)

– 2 optically insulated DI with 1 common for 2 inputs

– Watchdog relay (NO/NC)

– 2 command output relays (NO)

– 2 insulated RS485/RS422/RS232 interface


– Can be use to replace the old BIU

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.6) Central Program Unit - Structure

FLASH (R/W) non volatile DRAM (R/W) volatile

Current boot parameters + If format Real time data :


MAC address flash only current states + …

C264-R internal software files EEPROM (R) non volatile


(OS VxWorks + Application C264)
Bootprom files
(equivalent to BIOS for a PC)

DB1 DB2
Default boot parameters

Storage : Errors + SRAM (R/W) non


disturbance files volatile (2 days)
Archives (events log) +
Volatile : it requires a steady flow of electricity to CT + RS States
maintain its contents. As soon as the power is turned
off, datas are lost

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.6) Central Program Unit - CPU260
Main characteristics :
32-bit Power PC-base processor (clock 80 MHz) BUS
DRAM (64Mo) & Flash (16Mo)
VxWorks for RT OS
Powerful DSP TMS320C6713 for CT/VT
Ethernet-Based 10/100Base-FX or Base-TX
2 Serial links up to 64 Kbit/s RS232
IRIG-B port

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.7) Central Program Unit - CPU270
Main characteristics :
32-bit Power PC-base processor (clock 260 MHz)
More memory on DRAM (128Mb) and Flash (64Mb)
VxWorks for RT OS
Powerful DSP TMS320C6713 for CT/VT
2 Ethernet ports 10/100Base-TX (1 activated today)
2 Serial links up to 64 Kbit/s RS232
IRIG-B port

New bus
A new bus is designed for the CPU3 : this bus is compatible with existing I/O boards.
A new rack has also been designed : it is compatible with all existing I/O boards but
not with the CPU2 (See PS02 Page 17)

! Good Practice : in “Boot Parameters” from CMT, make


sure IP address 1 and IP address 2 are belonging to
different domains. Indeed, if the 2 addresses are in the
same domain, C264 application is not properly
starting.
© 2015 General Electric Company. Proprietary. All Rights Reserved.
2.8) Digital Input Board - DIU200

Main characteristics (different cortec numbers for DigitalInputU nit DIU20x

different Nominal Voltages) : board

VA, nom : 24-30 Vdc PIN Signal inputs

1
VA, nom : 40 Vdc (range 20 to 60 Vdc)
VIN VIN
+ DI1 + DI2
- -
2 - -
3
VA, nom : 100 Vdc (range 40 to 150 Vdc) 4
+
VIN
DI3 +
VIN
DI4
- -
- -
VA, nom : 220 Vdc (range 180 to 264 Vdc) 5
6
7 VIN VIN
+ DI5 + DI6
- -
8 - -
9
1 ms Time-tag 10
+
VIN
DI7 +
VIN
DI8
- -

Opto Isolated (2kV) 11


12
- -

Filtering possibilitiy 13 VIN VIN


+ DI9 + DI10
- -
14 - -
15
16 VIN VIN
+ DI11 + DI12
- -

16 DI usable for : 17
18
- -

19 VIN VIN
+ DI13 + DI14

- single or double status


- -
20 - -
21

- pulse 22
23
+
-
VIN

-
DI15 +
-
VIN

-
DI16

- digital measurement input 24

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.9) Digital Input Board - DIU210

Main characteristics :
Accept all Nominal Voltages
1 ms Time-tag
Opto Isolated (2kV during 1mn)
If 24VDC => I > 25mA always
If 48 to 220VDC => peak for 2ms :

16 DI usable for :
- single or double status
- pulse
- digital measurement input

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.10) Digital Input Board - DIU211

Similar to DIU200/DIU210 by jumpers


Main characteristics :
Accept all Nominal Voltages according on
jumpers definition :

Board address
1 ms Time-tag
Opto Isolated (2kV during 1mn)
27mA peak for 2ms

16 DI usable for :
- single or double status
- pulse
- digital measurement input

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.11) Digital Input Board - DIU220

Main characteristics :

Accept 2 different Nominal Voltages depending the


version :
- A02 : VA, nom : 48 Vdc (range 20 to 60 Vdc)
- A03 : VA, nom : 110 Vdc (range 40 to 125 Vdc)

1 ms Time-tag
Opto Isolated (2kV)

16 DI usable for :

- single or double status


- pulse
- digital measurement input

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.14) High break high speed Board - HBU200

High Break Unit: BCU board used in applications


requiring high rupture capacity.

Maximum Number : 2 Boards with 10 DO / C264

Main characteristics :

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.17) Analogue Input Board - AIU211

Main characteristics :
8 independent opto-isolated AI (Current only)
20 ms time tagging (acquisition)
16 bits A/D converter 0.1% accuracy
SMRR : 98dB
CMRR : 150dB
Input impedance : 75ohms
! This board will replace the actual AIU210

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.18) Analogue Output Board - AOU200

− 4 analogic outputs - External power


source is mandatory
− AI value available during 100ms (DO
closed)

− 4 simple relays with 1 common per


output - normally open (NO)
− Watchdog relay –
close if AO are correct

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.14) High break high speed Board - HBU200

High Break Unit: BCU board used in applications


requiring high rupture capacity.

Maximum Number : 2 Boards with 10 DO / C264

Main characteristics :

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.19) TMU200 - TMU220 - CT/VT Board

Transducerless Measurement Unit


4 CT
2 ranges each (1-5A) Range 0.2 In to 4 In accuracy 0.2%
4 VT for TMU200 and 5 VT for TMU220
Input Nom: 57 to 500V Range 4V to 500V(800V) acc. 0.2%
(possibility to use TMU220 instead of TMU200 on old
substations without changing configuration)
Direct measurement
RMS values of line/phase voltage (Van, Vab, ...)
RMS values of line current (Ia, Ib, Ic)
RMS values of residual current and voltage (Ir and Vr)²
Frequency
Active power (Pa, Pb, Pc and Ptotal)
Reactive power (Qa, Qb, Qc and Qtotal)
Derived Measurements
Fundamental magnitudes and phase angles
Apparent Power (Sa, Sb , Sc and Stotal)
Import/Export active and reactive energy
Power factor (displacement, distortion and true factor)
Fundamental Sequence components (Id, Ii, I0, Vd, Vi, V0)
Rolling, Peak, Dip demand values
Phase and amplitude difference + Daughter Board DSP on CPU260
15th Harmonic 64 samples/period

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.16) Analogue Input Board - AIU210

Main characteristics :
8 opto-isolated AI (Current only)
20 ms time tagging (acquisition)
16 bits A/D converter 0.1% accuracy
SMRR : 98dB
CMRR : 150dB
1 negative common for 2 inputs :

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.17) Analogue Input Board - AIU211

Main characteristics :
8 independent opto-isolated AI (Current only)
20 ms time tagging (acquisition)
16 bits A/D converter 0.1% accuracy
SMRR : 98dB
CMRR : 150dB
Input impedance : 75ohms
! This board will replace the actual AIU210

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.18) Analogue Output Board - AOU200

− 4 analogic outputs - External power


source is mandatory
− AI value available during 100ms (DO
closed)

− 4 simple relays with 1 common per


output - normally open (NO)
− Watchdog relay –
close if AO are correct

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.19) TMU200 - TMU220 - CT/VT Board

Transducerless Measurement Unit


4 CT
2 ranges each (1-5A) Range 0.2 In to 4 In accuracy 0.2%
4 VT for TMU200 and 5 VT for TMU220
Input Nom: 57 to 500V Range 4V to 500V(800V) acc. 0.2%
(possibility to use TMU220 instead of TMU200 on old
substations without changing configuration)
Direct measurement
RMS values of line/phase voltage (Van, Vab, ...)
RMS values of line current (Ia, Ib, Ic)
RMS values of residual current and voltage (Ir and Vr)²
Frequency
Active power (Pa, Pb, Pc and Ptotal)
Reactive power (Qa, Qb, Qc and Qtotal)
Derived Measurements
Fundamental magnitudes and phase angles
Apparent Power (Sa, Sb , Sc and Stotal)
Import/Export active and reactive energy
Power factor (displacement, distortion and true factor)
Fundamental Sequence components (Id, Ii, I0, Vd, Vi, V0)
Rolling, Peak, Dip demand values
Phase and amplitude difference + Daughter Board DSP on CPU260
15th Harmonic 64 samples/period

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.22) SWU20x Switch Board

SWU200 : 4 TX SWU202 : Multimode -2FX - 4 TX

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.20) TMU210 - CT/VT Board

The TMU210, used in the C264 equipment, is a current / voltage analogue board. This is
an evolution of the TMU200 in order to manage the 1A / 5A cases using jumpers. Often
use for protection in C264P.

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.25) HSR Switch Board

© 2015 General Electric Company. Proprietary. All Rights Reserved.


1.2.1) Hardware – Reference / DIN Rack / PCI Board

Reference Description Ethernet Device


Tx Fx
MICOM H 340 Switch “ simple” Copper 6 0 DIN Rack
MICOM H 341 Switch “ simple” (multi mode) 6 1 DIN Rack
MICOM H 342 Switch “ simple” (multi mode) 6 2 DIN Rack
MICOM H 343 Switch “ simple” (mono mode) 6 1 DIN Rack
MICOM H 344 Switch “ simple” (mono mode) 6 2 DIN Rack
MICOM H 352 Switch “ Redundant” (multi mode) 6 2 DIN Rack
MICOM H 354 Switch “ Redundant” (mono mode) 6 2 DIN Rack
MICOM H 362 Switch “ Dual Homing” (multi mode) 6 2 DIN Rack
MICOM H 364 Switch“ Dual Homing” (mono mode) 6 2 DIN Rack
MICOM H38 Box Switch “ PRP” 3 2 DIN Rack
MICOM H49 RedBox HSR/ PRP (coming soon)

H15x Redundant Ring 4 2 PCI Board


H16x Dual Homing 4 2 PCI Board
H18x PRP 0 2 PCI Board
H19x HSR 0 2 PCI Board

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.26) ECU20x : Communication module

ECU200 / ECU201 Extended Communication Unit for CPU

ECU200 : converts RS232 -> Fx


ST connector
Wavelength : 820nm
Jumper set : Light On
Jumper reset : Light Off

ECU201 : converts RS232 -> RS4xx


Jumper set : RS422 (4 wires)
Jumper reset : RS485 (2 wires)

© 2015 General Electric Company. Proprietary. All Rights Reserved.


3.2) Rules of slot positioning

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.22) SWR20x Switch Board

! SWR21x is new version able to communicate with Switch Manager software

SWR200 A03 - multimode 2FX -> 4 TX


SWR200 A05 - monomode 2FX -> 4 TX

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.23) SWD20x Switch Board

SWD200 A03 - multimode 2FX -> 4 TX


SWD200 A05 - monomode 2FX -> 4 TX

© 2015 General Electric Company. Proprietary. All Rights Reserved.


Summary

1) Generalities Page 3

2) Hardware Page 9

3) Board address and rules of slot positioning Page 50

4) C264 – Process bus Page 54

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.25) HSR Switch Board

© 2015 General Electric Company. Proprietary. All Rights Reserved.


2.26) ECU20x : Communication module

ECU200 / ECU201 Extended Communication Unit for CPU

ECU200 : converts RS232 -> Fx


ST connector
Wavelength : 820nm
Jumper set : Light On
Jumper reset : Light Off

ECU201 : converts RS232 -> RS4xx


Jumper set : RS422 (4 wires)
Jumper reset : RS485 (2 wires)

© 2015 General Electric Company. Proprietary. All Rights Reserved.


Summary

1) Generalities Page 3

2) Hardware Page 9

3) Board address and rules of slot positioning Page 50

4) C264 – Process bus Page 54

© 2015 General Electric Company. Proprietary. All Rights Reserved.


3.1) Set the Board address
Each board has an address, unique per type, starting from 0
by jumpers

CLOSED = 0 OPEN (see below)

Rules : If Open : address = address + 1


If Open : address = address + 2
If Open : address = address + 4
If Open : address = address + 8

Example :
=> + 2
=> 2 + 8 = 10
=> + 8

L1 - 03- MICOM C264 Hardware Presentation - Rev H


© 2015 General Electric Company. Proprietary. All Rights Reserved.
3.2) Rules of slot positioning

© 2015 General Electric Company. Proprietary. All Rights Reserved.


3.3) Rules of slot positioning

Ethernet switch boards can only be mounted in slot 1 or 2

© 2015 General Electric Company. Proprietary. All Rights Reserved.


Summary

1) Generalities Page 3

2) Hardware Page 9

3) Board address and rules of slot positioning Page 50

4) C264 – Process bus Page 54

© 2015 General Electric Company. Proprietary. All Rights Reserved.


4.1)- C264 – Process bus
Traditional Grid Control Full Digital Grid Control
Remote tools/
Rooms Rooms
Cyber Security
SCS HMI PDC
WAN WAN
SCS HMI PDC CM Eng. tools

Proxy Proxy
Switches Switches
IEC61850.8-1 Station Bus IEC61850.8-1 Station Bus PRP / HSR / 1588

BCUs Prot. sPDC BCU sPDC SACU WACU


Prot.

Wired I/O Wired VT&CT


IEC61850.9-2 Process Bus HSR / 1588

FO

DMU/
NMU AMU
CMU
Conventional
VT&CT NCiT

Primary Devices Primary Devices


© 2015 General Electric Company. Proprietary. All Rights Reserved.
4.2)- C264 – Process bus – Digital Input / Output

DPU = Digital Process bus Unit for IEC61850-8-1 digital Inputs/Outputs

SCU

© 2015 General Electric Company. Proprietary. All Rights Reserved.


4.3)- C264 – Process bus – Digital Input / Output

CPU C264 DPU Board


Station Bus
DPU 2FX
FPGA Fiber 100Mb/ 1Gb
PHY
C VHDL PHY Fiber 100Mb/ 1Gb
Binary P Core PHY RJ 45
inputs U
scanning Gooses IEC61850-8-1

CMU SCU

1) DPU port 1 : Wired


Binary acquisition and
controls trough DMU
2) DPU port 2 for CMU 1. Condition Monitoring Unit (CMU)
(Condition monitoring Data ) 2. Digital Merging Unit

© 2015 General Electric Company. Proprietary. All Rights Reserved.


4.4)- C264 – Process bus – SCU-Digital Input / Output

© 2015 General Electric Company. Proprietary. All Rights Reserved.


4.5)- C264 – Process bus – Analog input

SVU

Resembling of sampled values is made by the DSP board

© 2015 General Electric Company. Proprietary. All Rights Reserved.


4.6)- C264 – Process bus – Analog input - AMU

CPU C264 DSPIO Board C264 SVU board

SVU 2FX
FPGA Fiber 100Mb/ 1Gb
PHY
C VHDL PHY Fiber 100Mb/ 1Gb
P Core PHY RJ 45
U
MV Sampled
Automation Values
protection C264 Bus

Bus bar Sampled Sampled


Values IEC61850-9-2 Values IEC61850-9-2
NCIT board has 2
optical ports AMU/NMU AMU/NMU
1 for feeder
1 for Busbar
Va Vb Vc Vn Ia Ib Ic In

1. Analog Merging Unit (AMU)


2. Numerical Merging Unit (NMU)

© 2015 General Electric Company. Proprietary. All Rights Reserved.


4.7)- C264 – Process bus – AMU

. Support for 4 x CTs and 4 x VTs


. Space-saving 4U height and 30TE (6.) case size
. A front USB port and a rear fiber optic Ethernet port
. Power-up diagnostics and continuous self-monitoring
. Time synchronization via fiber optic 1-PPS
. N/O (form A) and N/C (form B) watchdog contacts
. Withdrawability

All events are time tagged to a resolution of 1 ms.

Up to 2048 time-tagged event records are stored in the flash


memory.

Files can be extracted using the USB port.