You are on page 1of 32

Catalogue Power Quality Electrical Protection

Mun Hean Lightning Protection Industrial Electrical


The Mun Hean group represents an extensive
network throughout Asia providing technical
solutions in industrial electrical as its core expe ise.
The group has o ces in 10 regions; Singapore,
Malaysia, Indonesia, Hong Kong, Philippines,
Vietnam, Myanmar, Taiwan, Beijing and Shenzhen.

The core of Mun Hean’s business lies in industrial


electrical technical marketing in four key areas:

Ÿ Power Quality;
Ÿ Electrical Protection;
Ÿ Lightning Protection;
Ÿ Industrial Electrical

The group sta ed from Mun Hean Singapore Pte Ltd


which was established in 1981 and has long been the
market leaders in industrial electrical marketing.
The group is the exclusive agent for many leading
international brands as shown in our Product
Po folio.
T Features REA 200n
Microprocessor-based with highest accuracy
Combined IDMTL Overcurrent & Earth Fault Relay
- Mechanical Trip Button (MTB) fault indication system
- No requirement tor auxiliary power supply for fault indication
- Safeguard against automatic reset before fault rectification
- Curve selection in accordance with ANSI, /AC, /EC, 1.3110, Hong Kong Utilities Curve
• Normally Inverse (Nlj
• Very Inverse (VI)
• Extremely Inverse (Elj
• Short Time Inverse (STlj
• Moderate Inverse (Ml)
- Trip value recording (4-memory)
- Date and time stamping tor tripping
- Integrated surge arrester against transient overvoltages
- High set mode is incorporated tor instantaneous protection
- Tamper-proof design tor settings protection
- Serial interface RS485 for Modbus RTU communication (optionalj
- Type tested* tor EMC compliance in acc. with /EC 61000
- High immunity to electrical interference (tested to 2.5GHz)
- Type tested in acc. with /EC 60255
- Comply to ANSI 86, 51N/51G, 51, 50N/50G, 50

T Technical Data
Power supply Working temperature range Electrical Life
AC / DC 85 - 265V -10 ° c to 55°C 1x 105
(other voltages available on request) Storage temperature range Mechanical Life
Operating frequency -20 °C to 65 °C 5 x10 5
50/60HZ Relative humidity (IEC 60068-2-30) Optional interface
Earth fault setting 95% at+ 40°C
RS485 to Modbus RTU/Slave
2.0 - 50.0% in step of 0.1% Protection Class (IEC 60529)
IP54 (optional with IP65 front cover) LED status indication
Overcurrent setting Normal operation, fault current detected
20_-200% in step of 1% Overcurrent withstand ability
Time multiplier setting 20 x lrated for 3 sec (100A for 0/C, 20A for E/F) Safety feature
Mechanical Trip Button
0.03 -2.00 in step of 0.01 (IEC, 1.3/10) Power consumption (MTB) complying with ANSI 86
0.3 :_20.0 in step of 0.1 (ANSI, IAC) <6VA
Definite time delay setting (DTL) Housing material
Relay Output ABS resin complying with UL94VO
0.03 - 2.00 sec in step of 0.01 sec 1 x C/0 (Changeover)
Instantaneous Mode (High Set) 1 x N/0 (Normally Open) Net weight
2.0 - 10.0 times setting Approx. 390g
Contact Rating
current in step of 0.1 current 5A at 250VAC
Pick-up current
100-115% of the setting
current in step of 1%
Reset current value
<90% of the operating value
IDMTL OVERCURRENT & EARTH FAULT RELAY IDMTL OVERCURRENT & EARTH FAULT RELAY

T MTB:
- Protrude out when relay triggered RELAY STATUS

- Hold on status without power supply Q TRIP


Q >0/C Q »0/C

- Push back in to reset O>EIF O»E/F

Trip Reset
T Features
Microprocessor-based with highest accuracy
ROA207n
IDMTL Overcurrent Relay
- Mechanical Trip Button (MTB) fault indication system
- No reqwrement for auxiliary power supply for fault indication
- Safeguard against automatic reset before fault rectification
- Curve selection in accordance with ANSI, /AC, /EC, 1.3110, Hong Kong Ultilities Curve
• Normally Inverse (NI)
• Very Inverse (VI)
• Extremely Inverse (El)
• Short Time Inverse (ST/)
• Moderate Inverse (Ml)
- Trip value recording (4-memory)
- Date and time stamping for tripping
- Integrated surge arrester against transient overvoltages
- High set mode is incorporated tor instantaneous protection
- Tamper-proof design for settings protection
- Serial interface RS485 for Modbus RTU communication (optional)
- Type tested tor EMC compliance in acc. with /EC 61000
- High immunity to electrical interference (tested to 2.5GHz)
- Type tested in acc. with /EC 60255
- Comply to ANSI 86, 51N/51G, 51, 50N/50G, 50

T Technical Data
Power supply Storage temperature range Contact Rating
AC / DC 85 - 265V - 20 ° c to 65 ° C 5 X 106
(other voltages available on request)
Relative humidity (IEC 60068-2-30) Optional interface
Operating frequency 95% at+ 40 °C RS485 to Modbus RTU/Slave
50/60HZ
Protection Class (IEC 60529) LED status indication
Overcurrent setting
IP54 (optional with IP65 front cover) Normal operation,
20-200% in step of 1%
fault current detected
Time multiplier setting Overcurrent withstand ability
0.3 - 20.0 in step of 0.1 (ANSI, IAC) 20 times 1 rated for 3 sec (1OOA) Safety feature
0.03 - 2.00 in step of 0.01 (IEC, 1.3/10) Mechanical Trip Button
Power consumption
(MTB) complying with ANSI 86
Definite time delay setting (DTL) <6VA
0.03 - 2.00 sec in step of 0.01 sec Relay Output Housing material
Instantaneous Mode (High-set) 1 x C/0 (Changeover), 1 x N/0 (Normally Open) ABS resin complying with UL94VO
2.0 - 10.0 times setting current in step on 0.1 Net weight
Contact Rating
Approx. 390g
Pick-up current 5A at 250VAC
100 - 115% of the setting current in step of 1% Electrical Life
Reset current value 1x105
<90% of the operating value
Working temperature range
- 10 ° C to 55 °C

T MTB:
- Protrude out when relay triggered
- Hold on status without power supply I
- Push back in to reset I
1t . .� � "

Trip
T Features
Microprocessor-based with highest accuracy
REF 052n
IDMTL Earth Fault Relay
- Mechanical Trip Button (MTB) fault indication system
- No reqU/rement for auxiliary power supply for fault ind/cation
- Safeguard against automatic reset before fault rectification
- Curve selection In accordance with ANSI, /AC, /EC, 1.3110, Hong Kong Utilities Curve
• Normally Inverse (Nlj
• Very Inverse (VI)
• Extremely Inverse (El)
• Short Time Inverse (STlj
• Moderate Inverse (Ml)
- Trip value recording (4-memory)
- Date and time stamping for tripping
- Integrated surge arrester against transient overvoltages
- High set mode is Incorporated for instantaneous protection
- Tamper-proof design for settings protection
- Serial Interface RS485 for Modbus RTU communication (optionalj
- Type tested for EMC compliance In acc. with /EC 61000
- High immunity to electrical Interference (tested to 2.5GHz)
- Type tested In acc. with /EC 60255
- Comply to ANSI 86, ANSI 51N/51G, and ANSI 50N/50G

T Technical Data
Power supply Working temperature range Mechanical Life
AC / DC 85 - 265V - 10° c to 55° c 5 x10 8
(other voltages available on request) Storage temperature range
- 20° c to 65° C Optional interface
Operating frequency RS485 to Modbus RTU/Slave
50/60HZ Relative humidity (IEC 60068-2-30)
95% at+ 40° C LED status indication
Earth fault setting Normal operation, fault current detected
2.0- 50.0% in step of 0.1% Protection Class (IEC 60529)
IP54 (optional with IP65 front cover) Safety feature
Overcurrent setting Mechanical Trip Button
20 - 200% in step of 1% Overcurrent with stand ability
20A for 3 sec (MTB) complying with ANSI 86
Time multiplier setting Power consumption Housing material
0.03 - 2.00 in step of 0.01 (IEC, 1.3/1O) <6VA ABS resin complying with UL94VO
0.3 - 20.0 in step of 0.1 (ANSI, IAC)
Relay Output Net weight
Definite time delay setting (DTL) 1 x C/0 (Changeover),
0.03 - 2.00 sec in step of 0.01 sec Approx. 390g
1 x N/0 (Normally Open)
Instantaneous Mode (High Set)
2.0 - 10.0 times setting Contact Rating
current in step of 0.1 5A at 250VAC
Pick-up current Electrical Life
100-115% of the setting 1 X 105
current in step of 1%
Reset current value .,,---�� -
<90% of the operating value
ICJMTL EARTH FAULT RELAY IOMTL EARTH FAULT RELAY

T MTB: EAR"ll! Ff"HIL�T


ie e:-�
l'

- Protrude out when relay triggered


- Hold on status without power supply
- Push back in to reset

Trip Reset
T Features
- Provides elementary protection functions
OA 703e
- Added security against nuisance trip handling
DTL Overcurrent relay
- Manual test button for relay operation checking
- ntegrated surge arrester against transient overvoltages
- Tamper-proof design for settings protection
- EMC type tested in accordance with /EC 60255-26 I /EC 61000-4 series

T Technical Data
Power supply Reset current value Output contact
AC110/240V � 90% of the operating value Mechanical > 5 x 1O operations
Voltage variation ±15% Operating and storage temperature range AC250V 2A
(other voltage available upon request) Operating-10 ° to 55 ° C Indication
Operating frequency Relative humidity Red LED (relay tripped)
50/60 z 95% at +40 ° C Green LED (aux. power)
Rated Current Degree of protection Housing material
5A (1A available upon request) IP51 (Front)/ IP20 (Rear) ABS resin complying with UL94VO
Current Setting Unit Weight
AC 2- 7A Approximately 500g
Delay Time Setting Power Consumtion
o- 1 sec �2VA
( * O to 1O sec available upon request)
Operation life expectancy
Electrical > 10,000 operations

T Connection Diagram T Dimension


3P3W 3P4W

LI L LI L
L2-------i---+-+-- 0 L2-------i----+-+-- 0 Panel cut-out
L3------------�
91.5 x 91.5 mm

mdg
L3

N------------------
A�"'/,'f,.,�Y

I I I

OA703cl On. OVERCURRENT RELAY OA703e DTL OVERCURRENT RELAY

T Compliance with standards


IEC 60255-27 Genral rules for residual-current protection devices
IEC 61000-4-2,3,4,5,6,8,11 (IEC 60255-26) Electromagnetic Compatibility
IEC 60255-21-1 Vibration, Shock and Bump Test
IEC 60255-21-2 Vibration, Shock and Bump Test
IEC 60068-2-2, 78, 30 (IEC 60255-1) Dry eat, Damp eat, Steady State, Cyclic Temperature with umidity Test

Ordering lnfomation
Model: Description
OA 703e DTL Overcurrent relay
T Features REL 10 / REL 30
Provide elementary leakage protection
Added security against nuisance trip handling
Earth Leakage panel type relay
Integrated surge arrester against transient overvoltages
Manual test button for relay operation checking
Real-time monitoring of leakage current(%)
Detection of "No-connection" to ZCT (Zero phase sequence current transformer)
Tamper-proof design for setting protection

T Technical Data
Auxiliary power supply Auxiliary supply Degree of protection (IEC 60529)
220V ±15% Green indicator Front: IP40; Back: IP20
(other voltages available upon request) Trip Assembly as per IEC 60999-1
Operating frequency Red indicator Front panel installation
50/60HZ Real-time leakage current Cable cross section
Power Consumption Green indicator; red indicator for above 75% Supply voltage 0.5 to 2.5mm2
Approximately 2.5VA ZCT connection error Output contact 0.5 to 2.5mm2
REL 1 O sensitivity current (A) Red indicator in Trip (blink) Temperature range
0.1 / 0.3 / 0.5 / 1 / 2 / 3/ 5 / 10 Outputs switching voltage Operation: -10° c to 55°C
REL 30 sensitivity current (A) Max. 250VAC Transport and storage: -20°C to 65°C
0.5 I 1 / 3/ 5 / 10 / 15 / 20 / 30 Outputs switching current Relative humidity
Delay time (sec) Max. 5A 95% at +40°C
Inst. / 0.1 / 0.15 / 0.2 / 0.25 / 0.3 / 0.4 / 0.5 Weight

T Connection Diagram
Approximately 0.3kg
TDimension
ZCT
l1 ____-/ l++---L
L2 ------1 �--0
L3 -------1 --++---A

Aux. Power Panel cut-out


AC 220V/240V
50/S0HZ 91.5 x 91.5 mm

o�0c2 c1(€v�

T Compliance with standards


IEC / EN 60255-27 Measuring relays and protection equipment - Part 27: Product safety requirements
IEC/EN 61000 -4-2 Electrostatic discharge immunity test
IEC/EN 61000 -4-3 Electromagnetic RF field
IEC/EN 61000-4-4 Burst
IEC/EN 61000-4-5 Surge
IEC/EN 61000-4-6 Conducted RF disturbances
IEC/EN 61000-4-8 Power frequency magnetic field
IEC/EN 61000-4-11 Voltage digs
IEC/EN 61000-4-18 Damped oscillatory wave
IEC / EN 55011 / CISPR 11 Conducted & radiated emissions

Ordering lnfomation
Model: Description
REL 10 Earth Leakage relay, panel type
sensitive range from 0.1 to 10A
REL 30 Earth Leakage relay, panel type
sensitive range from 0.5 to 30A
EL 03PP/10P/30
EL 03P/EL 10P/EL 30P

From 0.03 to 3 for EL 03P


From 0.1 to 10 for EL 10P
From 0.5 to 30 for EL 30P

EL 03P

EL 10P Earth Leakage relay


setting range 0.1 to 10A
EL 30P Earth Leakage relay
setting range 0.5 to 30A
EL 03/10/30
EL 03/EL 10/EL 30

From 0.03 to 3 for EL 03


From 0.1 to 10 for EL 10
From 0.5 to 30 for EL 30

EL 10 Earth Leakage relay


setting range 0.1 to 10A
EL 30 Earth Leakage relay
setting range 0.5 to 30A
EL 03D/30D
EL 03D/EL 30D

EL 03D
Setting range from 0.03 to 3A (step 0.01A)

EL 03D Digital Earth Leakage relay


setting range 0.03 to 3A
OUV 400
Over voltage limit protection Over & Under Voltage Relay

OUV 400
Under voltage limit protection
Microprocessor controlled DTL operation
Backlit high contrast LCD display
Wide operating range AUX voltage
4 Trip event records
Sealable tamper proof front cover

The OUV400 is an over and under- voltage relay for industrial and
commercial applica on. It is used in a wide variety of voltage
sensi ve equipment such as 3-phase AC motor, pump and
ven la on fan require a balanced supply voltage to operate
efficiently.

ANSI 59 – Overvoltage
Protec on and Func onality Descrip on
ANSI 27 – Undervoltage
Maximum Delay Time 60 seconds (step of 0.01s)
System Voltage Se ng 60VAC to 480VAC (Line Voltage)
Pick Up Voltage Se ng:
• 100% to 130% of System Voltage (step of 1%)
• Over Voltage
• 70% to 100% of System Voltage (step of 1%)
• Under Voltage
Reset (Clear) Voltage Se ng:
• 100% to 130% of System Voltage (step of 1%)
• Over Voltage
• 70% to 100% of System Voltage (step of 1%)
• Under Voltage
Pick Up Accuracy ± 0.5% of full scale
Reset Accuracy ± 1% of full scale
± 3% of Trip Time or +/- 20ms whichever is higher
Time Accuracy
(at no delay se ing max 50ms)
Opera ng voltage AUX AC/DC 85-265V (other voltage available upon request)
Power consump on < 4VA
Overvoltage – NC/NO (250VAC 5A)
Tripping Output Relay Contacts
Undervoltage – NO (250VAC 5A)
Display type Backlit LCD high contrast display
Relay Status Indicator Tripped – Red Color LED
Opera ng temperature 0 – 60°C
Trip Event recording 4 event recording
Opera ng humidity < 95% RH (non-condensing)
Access control User configurable PIN password
Housing material ABS resin comply with UL94VO
Unit weight Approximately 330g
Unit dimension 96mm (width) x 96mm (height) x 86mm (depth)
OUV 400
User Interface Features
1. Real me system voltage reading
2. Func on indicators
3. Type of fault indicator
4. Trip status indicator
5. Func on bu ons
6. Test and Reset bu ons
7. Trip info display

Radiated Emission (CISPR 11/22)


EMC Emission
Conducted Emission (CISPR 22)
IEC 61000-4-2 (IEC 60255-26)
IEC 61000-4-3 (IEC 60255-26)
IEC 61000-4-4 (IEC 60255-26)
EMC Immunity IEC 61000-4-5 (IEC 60255-26)
IEC 61000-4-6 (IEC 60255-26)
IEC 61000-4-8 (IEC 60255-26)
IEC 61000-4-11 (IEC 60255-26)
IEC 60255-21-1
Vibration, shock, bump
IEC 60255-21-2
Product Safety IEC 60255-27
IEC 60068-2-2 (IEC 60255-1)
Dry heat, damp heat steady state, cyclic
IEC 60068-2-78 (IEC 60255-1)
temperature with humidity
IEC 60068-2-30 (IEC 60255-1)
Level of Protec on IP 54

OUV 400 Over & Under Voltage Relay


VP 006
●The VP-006 is a range of phase failure/under Voltage Protection Relay

VP 006
voltage/over voltage protection relays to
continuously monitor AC power supplies both
single phase and three phase.
●Knob-adjustable separately for over voltage
and under voltage. If voltage is over or under
than the setting voltage for over 0.1-10 sec
(adjustable), then the output relay will be
released.
●Indicators
Power supply ON (Un) Green indicator
Output ON Red indicator
Under voltage limit (U<) Red indicator
Over voltage limit (U>) Red indicator

Operation Chart

ITEM NO. Under Voltage Function


VP-006
RATED VOLTAGE
THREE PHASE/SINGLE PHASE R
220V/127VAC, 380V/220VAC, S
400V/230VAC, 415V/240VAC T
FREQUENCY Hysteresis
50/60HZ
SETTING RANGES Under voltage Limit
UNDER VOLTAGE LIMIT 98%-78% Output ON
OVER VOLTAGE LIMIT 102%-122% Relay 1-3
DELAY OFF T 0.1sec-10sec. <U LED ON
HYSTERESIS
<1% of rated voltage
CONTACT RATING
AC250V 5A (P.F.=1)
Over Voltage Function
SETTING ERROR
±10% Over voltage Limit
Hysteresis
AMBIENT TEMP.
-5℃ ~+55℃
R
AMBIENT HUMIDITY
S
MAX.85%RH T
DIMENSIONS(mm.) Output ON
34(w)×80(h)×90(d) Relay 1-3
MOUNTING & SOCKET >U LED ON
SUREFACE MOUNTING
SOCKET: PF-113AE

VP 006 Voltage Protection Relay


T Features
METERING CT
MH Current Transformers
Tape wound construction for Low Voltage AC network measurement
• Monitoring of kWh/ WI A
• Class 0.51113
• Cast Resin or Insulated Tape Wound
PROTECTION CT
• For detection of clrcU/t fault condition with high peak current handling
• Class 5PI 10PI PX
• Insulated Tape Wound construction
Standard Compliance

T Productselection guide
• /EC 61869-2 for performance of Instrument transformer
• /EC 60044-1 for manufacturing and testing method used
• IP 20 Degree of Protection for indoor application Metering CT
Class 0.5 For kWh revenue meter application where accurate recording of energy
Customized CT consumption is required. 0.5% Current (Ratio) Error at 100% Rated
• MH CT is available in custom built specification such as PX type requirement Current.
• We have over 20 years' experience in making CT Class 1 For general metering of feeder 1 % Current (Ratio) Error at 100% Rated
Current.
with precise tolerance & special performance
Class 3 For industrial load status indication purpose. 3% Current (Ratio) Error at
100% Rated Current.

°T'Productdescnption Protection CT
5P For stringent time graded coordination protection scheme. 5% composite
error at rated Accuracy Limit Factor.
MH Current Transformer (MH CT) is used in energy metering and feeder protection application.
Designed for use in low voltage 50/60Hz network, the CT is installed in electrical switch board, 1OP For general time coordination and instantaneous over current scheme.
control panel and motor control centre. High grade annealed grain-oriented silicon steel is 10% composite error at rated Accuracy Limit Factor.
used in the CT core to provide improved accuracy and linearity of measurement.
PX Special application where protection scheme requires precise parameter
The CT can be directly installed onto bare copper busbar up to 720VAC rating. Available in a defined for Knee Point Voltage, Turn Ratio, Maximum Excitation Current at
Knee Point, CT Secondary Resistance. (Customized built item).
wide variety of dimensions and current ratio rating. Connection to the Secondary winding is
made via 2 bolt terminal. Customized model can be manufactured to customer specification. Examples of CT Specification
Metering CT e.g. 400/5, CL1 10VA
400A Primary Full Load, 5A Secondary Output,
MH CT is manufactured to comply with /EC 60044-1 standard and /EC 61869-2. This ensures
10VA Burden, Class 1
that each CT will provide measurement at its rated accuracy when operating at fluctuating
temperature, humidity, surge impulses and radio interference. Additional requirement for Protection CT e.g. 1600/5, 5P10 15VA
1600A Primary Full Load, 5A Secondary Output,
protective CT is applied to ensure its reliable operation in the event of heavy fault condition.
15VA Burden, 5P10 Stringent Time Coordination
with 10x Accuracy Limit Factor.

T Current Transformer TAboutMH Current Transformer


Technical data MH Current Transformer (MH CT) is designed and manufactured by Challenge Industrial Co.
(Malaysia) Sdn. Bhd. which was founded in the year 1993 by a joint venture between Mun
Hean and Challenge Industrial Co. Ltd. The MH Current Transformer is solely made under
Rated insulation voltage 720VAC
MH Instruments, a wing under Mun Hean Group. The founding of MH Current
Transformer is in line with Mun Hean's flagship products, MH Protection Relays and
Rated impulse voltage 3kV/1min Meters. In 1994, the product range for Protection Current Transformer is extended to Class
X Type and subsequently in year 1996, Class 0.5 Metering Current Transformer was
included into the production range. The complete chain of value creation including product
Instrument Wire Distance
design & development, production, and testing is based in Selangor, Malaysia. The major
expansion of production area at the mid of year 2014 shows that the product demand of
MH Current Transformer is increasing. Todar, MH Current Transformer has been sold to
26 Singapore, Malaysia, Hong Kong, Myanmar, Philippines, Indonesia and Vietnam, and it is
24 the market leader in Malaysia and Singapore.
22 - . ./5A
20

v
/
18
/
16
14 I/ l/
v

/
12
v
--
10 v
l/ --------
-
-- - -- -
8 /v /
__,,,..,..
;v
6 /

-v-
4 / __,,,..,...,..
2 / �
i..--
c-

,t p
-
T Mun H ean A C Current Transformer
Model Type Rate Burden (VA) ID(mm) OD(mm) H(mm)

IPS060-15 IPS 60A 15 35 70 55


IPSl00-15 IPS 100A 15 35 70 55
IPSlS0-15 IPS 150A 15 45 80 55
IPS200-15 IPS 200A 15 45 80 55
IPS250-15 IPS 250A 15 45 80 55
IPS300-15 IPS 300A 15 45 80 35
IPS400-15 IPS 400A 15 45 80 35
IPSS00-15 IPS SODA 15 65 100 35
IPS600-15 IPS 600A 15 65 100 35
IPSS00-15 IPS SODA 15 65 100 35
IPSl000-15 IPS 1000A 15 90 130 30
IPS1200-15 IPS 1200A 15 90 130 30
IPS1250-15 IPS 1250A 15 90 130 30
IPS1400-15 IPS 1400A 15 TBA TBA TBA
IPSlS00-15 IPS 1500A 15 90 130 30
IPS1600-15 IPS 1600A 15 90 130 30
IPS2000-15 IPS 2000A 15 130 165 30
IPS2500-15 IPS 2500A 15 130 165 30
IPS3000-15 IPS 3000A 15 130 165 30
IPS3200-15 IPS 3200A 15 130 165 30
IPS3500-15 IPS 3500A 15 125 165 30
IPS4000-15 IPS 4000A 15 125 170 35
IPSS000-15 IPS SOOOA 15 125 170 35
IPS6000-15 IPS 6000A 15 125 170 35

Model Type Rate Burden (VA) ID(mm) OD(mm) H(mm)

IPS060-5 IPS 60A 5 35 70 35


IPS100-5 IPS 100A 5 35 70 35
IPS150-5 IPS 150A 5 35 70 30
IPS200-5 IPS 200A 5 45 70 25
IPS250-5 IPS 250A 5 45 70 25
IPS300-5 IPS 300A 5 45 70 25
IPS400-5 IPS 400A 5 45 70 25
IPS500-5 IPS 500A 5 65 100 25
IPS600-5 IPS 600A 5 65 100 25
IPSS00-5 IPS 800A 5 65 100 25
IPS1000-5 IPS 1000A 5 90 130 30
IPS1200-5 IPS 1200A 5 90 130 30
IPS1400-5 IPS 1400A 5 TBA TBA TBA
IPS1500-5 IPS 1500A 5 90 130 30
IPS1600-5 IPS 1600A 5 90 130 30
IPS2000-5 IPS 2000A 5 130 165 30
IPS2500-5 IPS 2500A 5 130 165 30
IPS3000-5 IPS 3000A 5 130 165 30
IPS3200-5 IPS 3200A 5 130 165 30
IPS3500-5 IPS 3500A 5 125 170 30
IPS4000-5 IPS 4000A 5 125 170 35
IPS5000-5 IPS 5000A 5 125 170 35
IPS6000-5 IPS 6000A 5 125 170 35
Singapore (Headquarter) Hong Kong Indonesia Beijing
MUN HEAN SINGAPORE PTE LTD MUN HEAN ELECTRICAL ENGINEERING (HK) CO LTD PT MUN HEAN INDONESIA MUN HEAN HONG FEI (BEIJING) TECHNOLOGY CO LTD
51 Kim Keat Road, Unit 05-01/02 Unit 602, 6/F, Westlands Centre JI. Tanjung Daren Barat I No. 27-27A Room 3-2223, Gold Spring Times
Mun Hean Industrial Building 20 Westlands Road, Quarry Bay Tanjung Duren Utara, Grogol, Petamburan No. 317, Datun Li, Chaoyang District
Singapore 328821 Hong Kong Jakarta Barat 11470, Indonesia Beijing 100101, China
Tel: +65-6250 0522 Tel: +852-2873 1711 Tel: +62 21-5695 8826 Tel: +86 10-8483 9722
Fax: +65-6253 6885 / +65-6253 5879 Fax: +852-2518 7013 Fax: +62 21-5695 8829 Fax: +86 10-8483 9721
Email: rounbeansing@munhean.com.sg Email: munheanhk@munhean.com.hk E mail: munheanindo@munhean.co.id Email: mhhf@munhean.com.cn

Malaysia Taiwan Vietnam Shenzhen


MUN HEAN (MALAYSIA) SDN BHD MH ELECTRICAL SOLUTIONS CO LTD MUN HEAN VIETNAM CO LTD MUN HEAN POWER TECHNOLOGY (SHENZHEN) CO LTD
No. 15, Jalan SS26/6 Taman Mayang Jaya 5F-3, No. 16, Lane 609 68 Nguyen Quy Due Street Room 2006, Meilan Business Center
47301 Petaling Jaya, Selangor Darul Ehsan Sec. 5 Chongxin Road, Sanchong Dist. An Phu Ward, Thu Duc City, QianJin 2nd Road, Xixiang Street, Baoan District
Malaysia New Taipei City 24159, Taiwan R.O.C. Ho Chi Minh City, Vietnam Shenzhen 518102, China
Tel: +60 3-7804 2288 Tel: +886 2-2999 3993 Tel: +84 28-6281 0817 / 0819 Tel: +86 755-2778 8081
Fax: +60 3-7803 1185 Fax: +886 2-2999 3779 Fax: +84 28-6281 0815 Fax: +86 755-2778 8083
Email: munheanmy@munhean.com.my Email: mhes@mh-tw.com Email: munheanvn@munbean.com.vn Email: sales@munhean.cn

Myanmar Philippines
MH POWER MYANMAR CO LTD MH POLY-ELECTROMECHS, INC
No. 96 Yadanar Myaing Street 11th Floor, CyberOne Building
Off Yangon-lnsein Road (West Side) Eastwood Cyberpark, Brgy. Bagumbayan
Kamaryut Township, Yangon, Myanmar Quezon City 1110, Philippines
Tel: +95 1-505 364 Tel: +63-2 8366 8381 / +63-2 8366 8341
Fax: +95 1-505 364 Fax: +63-2 8366 8451
Email: mhmyanmar@munhean.com Email: mhpoly@munhean.com.ph