Professional Documents
Culture Documents
Fire Detection
Fire Detection
The purpose of a building fire alarm system is to detect fires, notify occupants, summon emergency
responders, and provide information to help manage the response.
Fire Detection and Alarm System is electronic equipment which detects fire and raises alarm as warning of
fire
FIRE PROTECTION
ACTIVE
FIRE DETECTION
is an integral part of the
building layout and materials of
LIFE SAFETY
construction
Heat
PASSIVE
Three things
LIFE SAFETY produced by fire forms
Underlyin the basis of detection
g principle
for
detectioncome into play only when a
fire is present and require
activation through a
combination of sensors or
Light Smoke means.
mechanical
Fire Detection: Components
The purpose of a building fire alarm system is to detect fires, notify occupants, summon emergency
responders, and provide information to help manage the response.
Fire Detection and Alarm System is electronic equipment which detects fire and raises alarm as warning of
fire
M
C M A EA A M
a
o au ll En Ei
n nt ea lc m s
ut uo cr ei ec
a r am tm cl re
lo la r tl gl
ol Ct oD ra el
rP ai ne or na
a lc iv ny cn
u
n l ci i ye
te P& c cE o
ol o Se q tu
m iM os Bu es
a na u ei l
t tn n lp e
i su d lm p
c Sa e se h
ml r n o
oD s Rt n
Fire Detection: System Types
Fire detection
Conventional/ Analogue
Addressable
Fire Detection: Conventional
consist of a fire alarm must be wired in fire
Each detection zone
panel, which will have resistant cables for
is run in a radial from
a number of ‘zone- the bell circuits, and
the fire alarm panel to
circuits’ run from it can be wired in a
various initiation
(respective detection standard cable for the
devices
and signalling circuit) detection circuit
These systems are actually monitoring and controlling circuits, and not individual
devices
Fire Detection: Addressable
Addressable detectors
detectors are
alarm control panel
wired in
is system may contain detector individually
are themselves,
'zoning' of the system
a loopable
around
to the one or more loops and receives
'intelligent' a status
devices & also
is not necessary,
display/indicate
building with eachthe depending upon the report,
able i.e. 'Healthy',
to provide pre-alarm
although it may be warnings when
precise
detector location
havingofits
the size of the system and 'In Alarm' or 'In Fault',
ownLoops
Theunique
for
device
loop
detection,
'address'
also has
and radials
done for convenience. Loops that
design requirements. can
smoke/heat both act for
levels reach
etc
Each devices number is
‘isolator’ for the sounders unique to that loop, anddetection and asounders
devices pre-set leveltogether
These systems utilizes a
installed in the loop at once all devices are minimum of two loops,
selected points, numbered, the fire generally one per floor,
(normally where the alarm panel is then with upto a maximum of
loop cable passes programmed to 128 devices on a loop.
through a wall). recognize
Fire Detection: Comparison
Conventional Addressable
DISADVANTAGES
-extensive
amounts of wire
that are necessary ADVANTAGES
to accurately
ADVANTAGES monitor initiating - Reduced
devices. possibility of false
- relatively simple -no accurate way alarms, by means DISADVANTAGES
for small to of determining of Control station
intermediate size which detectors reset. -Requires trained
buildings. are in need of -they are able to servicemen, to
servicing. monitor the status install and
- Servicing does - If a fault occurs, of each detector, operate.
not require a large the "trouble" thus providing
amount of indication only enhanced
specialized states that the maintenance.
training. circuit has failed, -Accuracy and
but does not ease of
specifically state modification
where the problem
is occurring.
Fire Detection: Initiating devices
Smoke detector
Ionization
Optical/ photoelectric
Heat detector
Fixed temperature
Rate of rise
Flame detector
Infrared detectors
UV detectors
Fire Detection: Smoke Detectors
A smoke detector is a device that detects smoke, typically as an indicator of fire.
Smoke Detector
In corridors up to 2 m wide
Fire Detection: Positioning of Detectors
• Sleeve
• •Sleeve
Prevents the passage of fire • Prevents the passage of
• Curtain Blade
through a duct, opening or air smoke through ductwork
• Smoke Blades
opening in a fire rated wall • opening
Breakaway or Joints
air opening in a
• •Breakaway Joints in wall & floor
Can be installed • smoke barrier or smoke
Fusible Link
openings. partition.
• Damper Actuator • Access Door
• Fusible Link • Curtain Blades
• Access Door
• Ductwork
FIRE DAMPER SMOKE DAMPER
Installed in ducts ducts
Designed to Close automatically upon Resist the passage of air and
detection of heat. smoke.
Primary function Prevent the passage of flame Prevent the passage of smoke
from one side of a fire-rated through the heating, ventilation and
separation to the other. air conditioning system, or from
one side of a fire-rated separation
to the other.
Operated by A fusible device, typically a Either a factory-installed electric or
melting link. a pneumatic actuator. Controlled
by smoke detectors and fire
alarms.
Their Application Static fire dampers can only be Passive smoke control system in
applied in HVAC systems that which they close upon detection of
are designed to shut down in the smoke engineered smoke control
event of a fire, system.
Dynamic fire dampers have
been tested for closure under
airflow and carry both an airflow
velocity (fpm) and pressure
differential rating.
NBC GUIDELINES
NBC GUIDELINES
Escape routes like staircases, common corridors, lift lobbies, etc., shall not be used
as return air passage. The ducting shall be constructed of substantial gauge metal
in accordance with good practice
Wherever the ducts pass through fire walls or floors, the opening around the ducts
shall be sealed with materials having fire resistance rating of the compartment.
Where duct crosses a compartment which is fire rated, the ducts shall be fire rated
for same fire rating. Further depending on services passing around the duct work,
which may get affected in case of fire temperature rising, the ducts shall be
insulated.
As far as possible, metallic ducts shall be used even for the return air instead of
space above the false ceiling.
Where plenum is used for return air passage, ceiling and its fixtures shall be of
noncombustible material.
NBC GUIDELINES
The materials used for insulating the duct system (inside or outside)
shall be of noncombustible materials. Glass wool shall not be
wrapped or secured by any material of combustible nature.
Air ducts serving main floor areas, corridors, etc., shall not pass
through the staircase enclosure.
The air-handling units shall be separate for each floor and air ducts
for every floor shall be separated and in no way inter-connected with
the ducting of any other floor.
NBC GUIDELINES
No combustible material shall be fixed nearer than 150 mm to any duct unless
such duct is properly enclosed and protected with noncombustible material
(glass wool or spun-glass with neoprene facing enclosed and wrapped with
aluminium sheeting) at least 3.2 mm thick and which would not readily
conduct heat.
FIRE DAMPERS
These shall be located in conditioned air ducts and return air ducts/passages at
the following points:
• At the fire separation wall.
• Where ducts passages enter the central vertical shaft.
• Where the ducts pass through floors.
• At the inlet of supply air duct and the return air duct of each compartment on every
floor.
The dampers shall operate automatically and shall simultaneously switch off the
air-handling fans. Manual operation facilities shall also be provided.
NBC GUIDELINES
Fire/smoke dampers (for smoke extraction shafts) for buildings more than 24
m in height :