If you want to see also if UPS is on manual by-pass then you can change setting for rele 1:
CP(P,0x0143/02,O00);
So the whole string will be:
CP(P,0x0143/02,O00);CP(P,0x014B/00,O01);CP(P,0x0143/01,O02);CP(P,0x0143/00,O03);
But because you have parallel system you could use only one ADC card because you can monitor
complete system and not only unit by unit.
In such case:
rele 3 for Output on auto by-pass: CP(P,0x0140/01,O02);
rele 1 Manual by-pass: CP(P,0x0140/02,O00);
So whole string:
CP(P,0x0140/02,O00);CP(P,0x014B/00,O01);CP(P,0x0140/01,O02);CP(P,0x0143/00,O03);