Professional Documents
Culture Documents
All calculations must be clearly presented, the final answer alone is not
sufficient to score full marks.
You will not be able to upload your work on the eclass platform
after the given deadline
Question Q1 (Total 30 Marks)
Q1(a)
The ordinary hazard sprinkler system shown in Figure 1 below is to be installed in a
compartment. The sprinkler heads are in a standard grid formation with the spacing
shown.
Determine the correct location of the design point for the array.
Size all the range pipes.
Size the distribution pipes up to the design point.
(ii) Determine the distribution pipe sizes between the design point and the
control valve using hydraulic calculations based on a maximum pressure
loss of 500 mbar at a flow rate of 1000 l·min-1.
(iii)Re-sketch the system noting the design point and all pipe sizes.
Use the old BS: 5306-2 to help calculate the pressure losses within the pipes and the
equivalent length of each turn can be assumed to be 3.2 m.
2900 3100
14000
32000
All dimensions in mm
17000
Control Valve
Each sprinkler covers an area of 14m2 and you can assume that the sprinkler spacing
and coverage meets with standard design guidance for an OH system.
Φ20mm Φ25mm
Using the information provided (including the appended tables which have been
extracted from the relevant BS EN standards) perform the necessary hydraulic design
calculations clearly showing all steps taken to determine the flow and associated
pressure for each sprinkler head.
Where information is taken from the tables provided then the correct tables must be
referenced.