After installing all the modules in each Pull cord or Belt sway switch and Termination
Module in the last switch, Two wire control bus is connected to the Master Controller.
To field +ve, field –ve & field return. As per the wiring diagram shown.
There is a slide switch on the Front side of Master controller.It has got 8 switches in it.
ON
1 2 3 4 5 6 7 8
Calibration is done by turning slid switch ON 1 & 5 configuration for Pull chord switch
mode.Now keep all the Pull chord switches OFF i.e. In healthy condition.Power to the
Master controller should turn ON. Display will show ‘bLt’,‘PC’ and then ‘SCn’ which
indicates Master starts scanning..Now turn First switch ON which you want to give as
no.1. Display will Display as’ ‘P01’.It means that Pull cord 1 is stored in memory.
Now switch off No.1 switch and turn ON 2nd switch ON.The Display will show ‘P02’ so Pull
cord 2 is stored.These way proceed all the switches upto the end.. One by one serially
and stores its address in the memory of Microcontroller. . All total No. of pull cord switches it
should indicate on Display. e.g. Suppose 32 pull cord switches connected to the master
controller then it should Display 1 to 32 no. If it had detected all the 32 switches that means all
the wiring is correct & system is ready for detection. After completing all switches turn slide
switch 5 OFF.The display will show ‘---‘ which indicates all reading is stored and scaning of
ON
1 2 3 4 5 6 7 8
Now Keep Slide switch 2 & 5 ON for Belt sway switch calibration. Switch off the the power to
the Panel. Again Switch ON the Power to the Panel. All Belt Sway should be Off i.e.Healthy
condition. Display will show ‘bS’,’bLt’ and then ‘SCn’. which indicates Master started
scanning..Now turn First switch ON which you want to give as no.1.Display will Display as’
b01’.It means that Belt sway switch 1 is stored in memory. Now switch off No.1 switch and turn
ON 2nd switch ON.The Display will show ‘b02’ so Belt Sway switch 2 is stored.
These way proceed all the switches upto the end.. One by one serially and stores its address
in the memory of Microcontroller . . All total No. of Belt sway switches it should indicate on
Display After completing all switches turn slide switch 5 OFF.The display will show ‘---‘ which
3. Repeat same procedure for Loop 3 i.e Chute Jam Loop by keeping switch 3 & 5 ON.
4. Repeat same procedure for Loop 4 i.e. Speed Monitor Loop Keeping Switch 4 & 5 ON.
ON
1 2 3 4 5 6 7 8
Now turn slide switch ‘1’ ON and Turn off ‘5’scan switch.from configuration mode to Its normal
mode.The display will show healthy by ‘HLy’.Now the calibration is over and system is ready for
Detection..
These scanning process is also used for fault finding when the cable is broken Between any two
switches and controller is showing Cable fault as ‘Open’ on front display of Master controller. In
such cases the nos.stops advancing where cable is broken .e.g. If the cable is broken between
switch 10 & switch 11.The display will stops scanning after switch 10.So we will immediately
come to know that there is cable broken between switch 10 & switch 11.It is also useful to
check the wiring in the begining. i.e If the Sensor module In and Out wires are interchanges or
wrongly connected can be detected by these scanning Procedure. In this case in those pull
cord switch in which wiring is incorrect that no. will be skipped or Omitted in scanning and total
no. of switches will show one no.less.i.e. In above Case instead of 32 total it will indicate 31 no.