You are on page 1of 10

CHANGSHA CHENGNAN WWTP UPGRADE

Contract No. : EPC Project No. :


Anchor Bolt Strength Calculation Sheet Page 1 / 10
Doc No. : Rev.A EPC Doc No. : - Rev.A

Anchor Bolt Strength Calculation Sheet

A 18/04/2023 ISSUED FOR APPROVAL


DATE
REV. DESCRIPTION PREPARED CHECKED REVIEWED APPROVED
(dd/mm/yyyy)

Confidential : This document is confidential and must not be copied or reproduced except with the express permission of
Evoqua Co., Ltd
CHANGSHA CHENGNAN WWTP UPGRADE

Contract No. : EPC Project No. :


Anchor Bolt Strength Calculation Sheet Page 2 / 10
Doc No. : Rev.A EPC Doc No. : - Rev.A

REVISION LOG

Rev Date
Item Page Ariticle Description
A 18/04/2023 All All All New issues

Confidential : This document is confidential and must not be copied or reproduced except with the express permission of
Evoqua Co., Ltd
CHANGSHA CHENGNAN WWTP UPGRADE

Contract No. : EPC Project No. :


Anchor Bolt Strength Calculation Sheet Page 3 / 10
Doc No. : Rev.A EPC Doc No. : - Rev.A

Contents

1. Anchor Bolt Design

1.1. 앵커 볼트 하중 및 안전성 결과 p. 4

1.1.1. 앵커에 작용하는 인장력, 전단력 및 결과

1.2. 인장 하중 설계 p. 5

1.2.1. 앵커의 강재강도 및 연성 요구사항


1.2.2. 인장력을 받는 앵커의 강재강도
1.2.3. 인장력을 받는 앵커의 콘크리트 파괴강도
1.2.4. 인장력을 받는 앵커의 뽑힘강도
1.2.5. 인장력을 받는 앵커의 콘크리트 측면 파괴강도
1.2.6. 설계 공칭 인장강도 결정

1.3. 전단 하중 설계 p. 8

1.3.1. 전단력을 받는 앵커의 강재강도


1.3.2. 전단력을 받는 앵커의 콘크리트 파괴강도
1.3.3. 전단력을 받는 앵커의 콘크리트 프라이아웃 강도
1.3.4. 설계 공칭 전단강도 결정
1.3.5. 인장력, 전단력 및 인장력 과 전단력이 동시에 작용하는 경우 강도 설계

Confidential : This document is confidential and must not be copied or reproduced except with the express permission of
Evoqua Co., Ltd
CHANGSHA CHENGNAN WWTP UPGRADE

Contract No. : EPC Project No. :


Anchor Bolt Strength Calculation Sheet Page 4 / 10
Doc No. : Rev.A EPC Doc No. : - Rev.A

1. Anchor Bolt Design


1.1. 앵커 볼트 하중 및 안전성 결과

1 .2 .1 앵커에 작용하는 인장력, 전단력 및 결과

Tension Shear 𝑁𝑢𝑎 𝑉𝑢𝑎 𝑁𝑢𝑎 𝑉𝑢𝑎


No Load combination < 1.0 < 1.0 + < 1.0 Remark
Loading Loading (𝑁𝑛 /𝛺) (𝑉𝑛 /𝛺) (𝑁𝑛 /𝛺) (𝑉𝑛 /𝛺)
1 ANCHOR-1 15.3 kN 7.9 kN 0.402 < 1.000 0.401 < 1.000 0.804 < 1.000 O.K
2 ANCHOR-2 16.8 kN 7.6 kN 0.441 < 1.000 0.383 < 1.000 0.824 < 1.000 O.K
3 ANCHOR-3 15.7 kN 8.6 kN 0.414 < 1.000 0.434 < 1.000 0.848 < 1.000 O.K
4 ANCHOR-4 17.0 kN 8.3 kN 0.447 < 1.000 0.418 < 1.000 0.865 < 1.000 O.K
5 ANCHOR-5 15.8 kN 7.5 kN 0.416 < 1.000 0.378 < 1.000 0.794 < 1.000 O.K
6 ANCHOR-6 14.9 kN 8.0 kN 0.390 < 1.000 0.406 < 1.000 0.796 < 1.000 O.K
7 ANCHOR-7 17.8 kN 8.4 kN 0.467 < 1.000 0.423 < 1.000 0.890 < 1.000 O.K
8 ANCHOR-8 16.2 kN 8.5 kN 0.425 < 1.000 0.429 < 1.000 0.854 < 1.000 O.K

*Axial compressive force acting on the anchor bolt is considered as zero force since anchor bolt is only subjected to tension force.

Confidential : This document is confidential and must not be copied or reproduced except with the express permission of
Evoqua Co., Ltd
CHANGSHA CHENGNAN WWTP UPGRADE

Contract No. : EPC Project No. :


Anchor Bolt Strength Calculation Sheet Page 5 / 10
Doc No. : Rev.A EPC Doc No. : - Rev.A

1. Anchor Bolt Design


1.2. 인장 하중 설계

1 .2 .1 앵커의 강재강도 및 연성 요구사항

Bolt Head = Hex nut : 앵커 볼트 헤드의 종류


𝑑𝑎 = 16mm (M16) : 앵커의 외경
𝑛 = 1 EA : 앵커의 수
ℎ𝑒𝑓 = 250 mm : 앵커의 유효묻힘깊이
ℎ𝑎 = 500 mm : 콘크리트 높이
𝑑ℎ = 19 mm : 지압 보강판의 구멍 직경
𝑊 = 100 mm : 지압 보강판 너비
𝑇 = 10 mm : 지압 보강판의 두께
𝐶𝑎1 = 500 mm : 앵커 샤프트 중심부터 콘크리트 단부까지의 거리
𝑓𝑦𝑎 = 170.0 MPa : 앵커 강재의 설계항복강도
𝑓𝑢𝑡𝑎 = 485.0 MPa : 앵커 강재의 설계인장강도
𝑁𝑢𝑎 = 16.2 kN : 앵커에 작용하는 인장하중
𝑉𝑢𝑎 = 8.5 kN : 앵커에 작용하는 전단하중
𝑓𝑐𝑘 = 35.0 MPa : 콘크리트의 설계압축강도
𝜖 = 18.0% : 앵커 강재의 연실율(%)
∆𝐴 = 52.0% : 앵커 강재의 단면 수축율(%)
Class = Ductile material : ε ≥ 14% 이고 ΔA ≥ 30%인 경우는 Ductile material, 그 이외는 Brittle material
𝐴𝐷 = 201 mm² : 앵커 강재의 총 단면적
𝐴𝑠𝑒,𝑁 = 157 mm² : 앵커 강재의 유효 단면적
𝐴𝑏𝑟𝑔 = 9,716 mm² : 앵커 볼트 머리 또는 너트의 지압면적 ( Abrg = W2 - (π x dh2) / 4 )
𝐶𝑎𝑐 = 625 mm : 언더컷앵커(2.5hf) / 비틀림제어 앵커(4.0hf) /변위제어 앵커(4.0hf)
𝐶𝑎,𝑚𝑖𝑛 = 500 mm : 앵커 샤프트 중심부터 콘크리트 단부까지의 거리

Confidential : This document is confidential and must not be copied or reproduced except with the express permission of
Evoqua Co., Ltd
CHANGSHA CHENGNAN WWTP UPGRADE

Contract No. : EPC Project No. :


Anchor Bolt Strength Calculation Sheet Page 6 / 10
Doc No. : Rev.A EPC Doc No. : - Rev.A

1. Anchor Bolt Design


1.2. 인장 하중 설계

1 .2 .2 인장력을 받는 앵커의 강재강도 (KDS 14 20 54:2016 4.3.1절 / ACI318-14 Para.17.4.1)

𝑓𝑢𝑡𝑎 = 485.0 MPa ≤ Min( 1.9𝑓𝑦𝑎 , 860.0 MPa ) = 323.0 MPa


= 323.0 MPa

𝑁𝑠𝑎 = 𝑛𝐴𝑠𝑒,𝑁 𝑓𝑢𝑡𝑎 : 인장을 받는 단일 앵커가 지배하는 경우의 공칭강도


= 50.7 kN

𝜙 = 0.75 : 연성재질(φ = 0.75) / 취성재질(φ = 0.65)


𝜙 𝑁𝑠𝑎 = 38.0 kN

1 .2 .3 인장력을 받는 앵커의 콘크리트 파괴강도 (KDS 14 20 54:2016 4.3.2절 / ACI318-14 Para.17.4.2)

𝐴𝑁𝑐 Τ𝐴𝑁𝑐𝑜 = 1.000


2
𝐴𝑁𝑐𝑜 = 9ℎ𝑒𝑓 : 연단거리 또는 간격에 제한을 받지 않는 경우 단일 앵커의 콘크리트 파괴면 투영면적
= 562,500 mm²

𝐴𝑁𝑐 = (𝐶𝑎1 + 1.5ℎ𝑒𝑓 ) × (3.0ℎ𝑒𝑓 ) ≤ 𝐴𝑁𝑐𝑜 : 인장강도 산정을 위한 단일 앵커의 콘크리트 파괴면 투영면적
= 562,500 mm²

𝜓𝑒𝑑,𝑁 = 0.7 + 0.3(𝐶𝑎,𝑚𝑖𝑛 Τ1.5ℎ𝑒𝑓 ) : 연단거리 영향에 따른 인장강도에 대한 수정계수


= 1.000

𝜓𝑐,𝑁 = 1.000 : 선설치 앵커의 콘크리트 균열이 발생하는 경우 ψc,N = 1.0 / 균열이 발생하지 않는 경우 ψc,N = 1.25
후설치앵커(kc= 7)가 균열이 발생하는 경우 ψc,N = 1.0 / 균열이 발생하지 않는 경우 ψc,N = 1.4
𝜓𝑐𝑝,𝑁 = 0.800 : 후설치앵커를 제외한 선설치앵커 및 다른 모든 경우 ψcp,N = 1.0 / 후설치 앵커: Cmin / Cac
𝑘𝑐 = 7 : 인장에 의한 기본 콘크리트 파괴강도 계수 (선설치 앵커: kc = 10, 후설치 앵커: kc = 7)
𝜆 = 0.75 : λ = 0.75(전경량콘크리트) , λ = 0.86(모래경량콘크리트)

𝑁𝑏 = 𝑘𝑐 𝜆 𝑓𝑐𝑘 ℎ1.5
𝑒𝑓 : 단일 앵커의 기본 콘크리트 파괴강도
= 123 kN

5/3
𝑁𝑏 = 3.9𝜆 𝑓𝑐𝑘 ℎ𝑒𝑓 : 280mm < hef < 636mm인 선설치 헤드스터드 및 헤드볼트인 경우
= -

𝑁𝑐𝑏 = (𝐴𝑁𝑐 Τ𝐴𝑁𝑐𝑜 ) ∙ 𝜓𝑒𝑑,𝑁 ∙ 𝜓𝑐,𝑁 ∙ 𝜓𝑐𝑝,𝑁 ∙ 𝑁𝑏


= 98.2 kN

𝜙 = 0.45 : 후설치 앵커 강도감소계수 (보조철근 포함한 경우, φ = 0.55 보조철근이 없는 경우, φ = 0.45)
𝜙 𝑁𝑐𝑏 = 44.2 kN
Confidential : This document is confidential and must not be copied or reproduced except with the express permission of
Evoqua Co., Ltd
CHANGSHA CHENGNAN WWTP UPGRADE

Contract No. : EPC Project No. :


Anchor Bolt Strength Calculation Sheet Page 7 / 10
Doc No. : Rev.A EPC Doc No. : - Rev.A

1. Anchor Bolt Design


1.2. 인장 하중 설계

1 .2 .4 인장력을 받는 앵커의 뽑힘강도 (KDS 14 20 54:2016 4.3.3절 / ACI318-14 Para.17.4.3)

𝑁𝑝 = 8𝐴𝑏𝑟𝑔 𝑓𝑐𝑘 : 균열 콘크리트에서 인장력을 받는 단일 앵커의 뽑힘강도


= 2,720.6 kN

𝜓𝑐,𝑃 = 1.000 : 균열이 없는 것으로 가정한 경우: ψc,P = 1.4 / 균열이 발생으로 가정한 경우: ψc,P = 1.0
𝜙 = 0.45 : 후설치 앵커 강도감소계수 (보조철근 포함한 경우, φ = 0.55 보조철근이 없는 경우, φ = 0.45)

𝑁𝑝𝑛 = 𝜓𝑐,𝑃 ∙ 𝑁𝑝 : 인장력을 받는 단일 앵커의 공칭뽑힘강도


2,720.6 kN

𝜙𝑁𝑝𝑛 = 1,224.3 kN

1 .2 .5 인장력을 받는 앵커의 콘크리트 측면 파괴강도 (KDS 14 20 54:2016 4.2절 (6)항 / ACI318-14 Para.17.4.4)

ℎ𝑒𝑓 = 250 mm < 2.5𝐶𝑎1 = 1250 mm : 콘크리트 측면 파열 발생 없음"

𝑁𝑠𝑏 = 13𝐶𝑎1 (𝐴𝑏𝑟𝑔 )0.5 ∙ 𝜆 ∙ (𝑓𝑐𝑘 )0.5 : 단일 앵커의 공칭 측면 파열강도


= 2,842.9 kN

𝜙 = 0.45 : 후설치 앵커 강도감소계수 (보조철근 포함한 경우, φ = 0.55 보조철근이 없는 경우, φ = 0.45)
𝜙𝑁𝑠𝑏 = 1,279.3 kN

1 .2 .6 설계 공칭 인장강도 결정 (KDS 14 20 54:2016 4.3.4절 / ACI318-14 Table.17.2.3)

𝜙𝑁𝑠𝑎 = 38.0 kN : 인장력을 받는 앵커의 강재강도

𝜙𝑁𝑐𝑏 = 44.2 kN : 인장력을 받는 앵커의 콘크리트 파괴강도

𝜙𝑁𝑝𝑛 = 1,224.3 kN : 인장력을 받는 앵커의 뽑힘강도

𝜙𝑁𝑠𝑏 = 1,279.3 kN : 인장력을 받는 앵커의 콘크리트 측면 파괴강도

𝜙𝑁𝑛 = Min( 𝜙𝑁𝑠𝑎 , 𝜙𝑁𝑐𝑏 , 𝜙𝑁𝑝𝑛 , 𝜙𝑁𝑠𝑏 ) : 인장력에 대한 최소 설계강도


= 38.0 kN

Confidential : This document is confidential and must not be copied or reproduced except with the express permission of
Evoqua Co., Ltd
CHANGSHA CHENGNAN WWTP UPGRADE

Contract No. : EPC Project No. :


Anchor Bolt Strength Calculation Sheet Page 8 / 10
Doc No. : Rev.A EPC Doc No. : - Rev.A

1. Anchor Bolt Design


1.3. 전단 하중 설계

1 .3 .1 전단력을 받는 앵커의 강재강도 (KDS 14 20 54:2016 4.4.1절 / ACI318-14 Para.17.5.1)

𝐴𝑠𝑒,𝑉 = 157 mm² : 앵커 강재의 유효 단면적


𝐴𝑏𝑟𝑔 = 9,716 mm² : 앵커 볼트 머리 또는 너트의 지압면적 ( Abrg = W2 - (π x dh2) / 4 )

𝑓𝑢𝑡𝑎 = 485.0 MPa ≤ Min( 1.9𝑓𝑦𝑎 , 860.0 MPa ) = 323.0 MPa


= 323.0 MPa

𝑉𝑠𝑎 = 𝑛0.6𝐴𝑠𝑒,𝑉 𝑓𝑢𝑡𝑎 : 전단을 받는 단일 앵커가 지배하는 경우의 공칭전단강도


= 30.4 kN

𝜙 = 0.65 : 연성재질(φ = 0.65) / 취성재질(φ = 0.60)


𝜙𝑉𝑠𝑎 = 19.8 kN

1 .3 .2 전단력을 받는 앵커의 콘크리트 파괴강도 (KDS 14 20 54:2016 4.4.2절 / ACI318-14 Para.17.5.2)

𝐶𝑎1 = 500 mm : 앵커 샤프트 중심부터 콘크리트 단부까지의 거리 (인장력 작용 경우는 최소 연단거리)

𝜆 = 0.75 : λ = 0.75(전경량콘크리트) , λ = 0.86(모래경량콘크리트)


𝐴𝑉𝑐 Τ𝐴𝑉𝑐𝑜 = 0.667
𝐴𝑉𝑐𝑜 = 4.5 𝐶𝑎1 2
: 연단거리 또는 간격에 제한을 받지 않는 경우 단일 앵커의 콘크리트 파괴면 투영면적
= 1,125,000 mm²

𝐴𝑉𝑐 = Min( 2(1.5𝐶𝑎1 )ℎ𝑎 , 𝐴𝑉𝑐𝑜 ) : 인장강도 산정을 위한 단일 앵커의 콘크리트 파괴면 투영면적
= 750,000 mm²

𝑙𝑒 = Min( 8𝑑𝑎 , ℎ𝑒𝑓 ) : 앵커 전단력에 대한 지압 저항 길이


= 128 mm

Confidential : This document is confidential and must not be copied or reproduced except with the express permission of
Evoqua Co., Ltd
CHANGSHA CHENGNAN WWTP UPGRADE

Contract No. : EPC Project No. :


Anchor Bolt Strength Calculation Sheet Page 9 / 10
Doc No. : Rev.A EPC Doc No. : - Rev.A

1. Anchor Bolt Design


1.3. 전단 하중 설계

𝑉𝑏 = 0.6 𝑙𝑒 Τ𝑑𝑎 0.2


∙ 𝑑𝑎 0.5 𝜆 𝑓𝑐𝑘 𝐶𝑎1 1.5
: 단일 앵커의 기본 콘크리트 파괴강도
= 180.5 kN

𝜓𝑒𝑑,𝑉 = 1.000 : 연단거리 영향에 따른 전단강도에 대한 수정계수


𝜓𝑐,𝑉 = 1.000 : 보조철근이 없거나 D13 미만의 보강근이 배치된 균열 콘크리트에 설치된 앵커
𝜓ℎ,𝑉 = Max( 1.0 , 1.5𝐶𝑎1 Τℎ𝑎 0.5
) : ha < 1.5Ca1인 콘크리트 부재에 설치된 앵커의 전단강도에 대한 수정계수
= 1.225

𝑉𝑐𝑏 = (𝐴𝑉𝑐 Τ𝐴𝑉𝑐𝑜 ) ∙ 𝜓𝑒𝑑,𝑉 ∙ 𝜓𝑐,𝑉 ∙ 𝜓ℎ,𝑉 ∙ 𝑉𝑏 : 전단을 받는 단일 앵커의 공칭콘크리트 파괴강도
= 147.3 kN

𝜙 = 0.45 : 후설치 앵커 강도감소계수


(보조철근 포함한 경우, φ = 0.55 보조철근이 없는 경우, φ = 0.45)
𝜙𝑉𝑐𝑏 = 66.3 kN

1 .3 .3 전단력을 받는 앵커의 콘크리트 프라이아웃 강도 (KDS 14 20 54:2016 4.4.3절 / ACI318-14 Para.17.5.3)

𝑁𝑐𝑏 = (𝐴𝑁𝑐 Τ𝐴𝑁𝑐𝑜 ) ∙ 𝜓𝑒𝑑,𝑁 ∙ 𝜓𝑐,𝑁 ∙ 𝜓𝑐𝑝,𝑁 ∙ 𝑁𝑏 : 인장력을 받는 앵커의 콘크리트 파괴강도
= 98.2 kN

𝑘𝑐𝑝 = 2.00 : 프라이아웃강도 계수 hef < 65mm, kcp = 1.0 / hef ≥ 65mm, kcp = 2.0

𝑉𝑐𝑝 = 𝑘𝑐𝑝 ∙ 𝑁𝑐𝑏


= 196.4 kN

𝜙 = 0.45 : 후설치 앵커 강도감소계수


(보조철근 포함한 경우, φ = 0.55 보조철근이 없는 경우, φ = 0.45)
𝜙𝑉𝑐𝑝 = 88.4 kN

1 .3 .4 설계 공칭 전단강도 결정 (KDS 14 20 54:2016 4.3.4절 / ACI318-14 Table.17.2.3)

𝜙𝑉𝑠𝑎 = 19.8 kN : 전단력을 받는 앵커의 강재강도

𝜙𝑉𝑐𝑏 = 66.3 kN : 전단력을 받는 앵커의 콘크리트 파괴강도

𝜙𝑉𝑐𝑝 = 88.4 kN : 전단력을 받는 앵커의 콘크리트 프라이아웃 강도

𝜙𝑉𝑛 = Min( 𝜙𝑉𝑠𝑎 , 𝜙𝑉𝑐𝑏 , 𝜙𝑉𝑐𝑝 ) : 전단력에 대한 최소 설계강도


= 19.8 kN

Confidential : This document is confidential and must not be copied or reproduced except with the express permission of
Evoqua Co., Ltd
CHANGSHA CHENGNAN WWTP UPGRADE

Contract No. : EPC Project No. :


Anchor Bolt Strength Calculation Sheet Page 10 / 10
Doc No. : Rev.A EPC Doc No. : - Rev.A

1. Anchor Bolt Design


1.3. 전단 하중 설계

1 .3 .5 인장력, 전단력 및 인장력 과 전단력이 동시에 작용하는 경우 강도 설계 (KDS 14 20 54:2016 4.5절 / ACI318-14 Table.17.6)

1) 수직 인장력에 대한 설계 인장강도

𝑁𝑢𝑎
= 0.425 < 1.000 : O.K
(𝜙𝑁𝑛 )

2) 수평 전단력에 대한 설계 전단강도

𝑉𝑢𝑎
= 0.429 < 1.000 : O.K
(𝜙𝑉𝑛 )

3) 인장력 및 전단력이 동시에 작용할 때, 설계 강도

𝑁𝑢𝑎 𝑉𝑢𝑎
+ = 0.854 < 1.000 : O.K
(𝜙𝑁𝑛 ) (𝜙𝑉𝑛 )

Confidential : This document is confidential and must not be copied or reproduced except with the express permission of
Evoqua Co., Ltd

You might also like