Table.

1 Operation switch condition (start-up)


No. Operation item Location condition Checked Note
1 Sea water System - -
1.1 Master / Function Group DCS Master
1.2 Condenser return waterbox-A vent valve DCS Auto
1.3 Condenser return waterbox-A vent valve DCS Auto
1.4 CWP-A DCS Auto
1.5 ACOV DCS Auto
1.6 DV-A DCS Auto
1.7 CWP-B DCS Auto
1.8 BCOV DCS Auto
1.9 DV-B DCS Auto
1.10 Debris Filter DCS Auto

2 Turbine oil system - -

3 Turning/Condensate system - -
3.1 Turning system - -
3.2 CFP - -
3.3 Condensate pump - -
3.3.1 CP-A DCS Auto
3.3.2 CP-B DCS Auto
3.3.3 CP-A discharge valve DCS Auto
3.3.4 CP-B discharge valve DCS Auto
3.3.5 Condensater mini flow control DCS Auto

4 Preparation of initial firing - -


4.1 Draft function DCS Auto MC/FWC logic
4.2 Heavy oil pump pressure control DCS Auto MC logic
4.3 Boiler drain & vent valves DCS Auto MC/FWC logic

5 Vacuum up - -
5.1 Start-up Dea pegging control A - -
5.2 Vacuum up - -
5.2.1 No.6 HP heater drain warming valve DCS Auto
5.2.2 No.7 HP heater drain warming valve DCS Auto
5.2.3 Condenser level control (make-up) DCS Auto
5.2.4 Condenser level control (spil over) DCS Auto
5.2.5 Gland steam header pressure control DCS Auto
5.2.6 Hogging ejector driving steam inlet valve DCS Auto
5.2.7 Hogging ejector gas inlet valve DCS Auto
5.2.8 Gland steam condenser fan-A DCS Auto
5.2.9 Gland steam condenser fan-B DCS Auto
5.2.10 Steam jet air ejector driving steam inlet valve-A DCS Auto
5.2.11 Steam jet air ejector-A gas inlet valve DCS Auto
5.2.12 Steam jet air ejector driving steam inlet valve-B DCS Auto
5.2.13 Steam jet air ejector-B gas inlet valve DCS Auto
5.2.14 Aux. steam stop valve DCS Auto
5.2.15 Turbine gland steam supply warming valve DCS Auto
5.2.16 Vacuum breaker valve DCS Auto

6 Boiler ignition - -
6.1 1st BFP - -
6.1.1 Deaerator recirculation pump DCS Auto
6.1.2 Deaerator recirculation pump discharge valve DCS Auto
6.1.3 BFP booster pump-A strainer inlet valve DCS Auto
6.1.4 BFP booster pump-B strainer inlet valve DCS Auto
6.1.5 BFP booster pump-C strainer inlet valve DCS Auto
6.1.6 BFP booster pump-A strainer outlet valve DCS Auto
6.1.7 BFP booster pump-B strainer outlet valve DCS Auto
6.1.8 BFP booster pump-C strainer outlet valve DCS Auto
6.1.9 BFP-A warming inlet valve DCS Auto
6.1.10 BFP-B warming inlet valve DCS Auto
6.1.11 BFP-C warming inlet valve DCS Auto
6.1.12 BFPBP-A discharge vent valve DCS Auto
6.1.13 BFPBP-B discharge vent valve DCS Auto
6.1.14 BFPBP-C discharge vent valve DCS Auto
6.1.15 BFP-A discharge vent valve DCS Auto
6.1.16 BFP-B discharge vent valve DCS Auto
6.1.17 BFP-C discharge vent valve DCS Auto
6.1.18 BFP-A mini flow control DCS Auto
6.1.19 BFP-B mini flow control DCS Auto
6.1.20 BFP-C mini flow control DCS Auto
6.1.21 Boiler feed water pump-A DCS Auto
6.1.22 Boiler feed water pump-B DCS Auto
6.1.23 Boiler feed water pump-C DCS Auto
6.1.24 BFP-A auxiliary oil pump DCS Auto
6.1.25 BFP-B auxiliary oil pump DCS Auto
6.1.26 BFP-C auxiliary oil pump DCS Auto
6.1.27 Boiler feed water pump-A discharge valve DCS Auto
6.1.28 Boiler feed water pump-B discharge valve DCS Auto
6.1.29 Boiler feed water pump-C discharge valve DCS Auto
6.1.30 BFP-A intermediate discharge valve DCS Auto
6.1.31 BFP-B intermediate discharge valve DCS Auto
6.1.32 BFP-C intermediate discharge valve DCS Auto
6.1.33 BFP-A service DCS Auto
6.1.34 BFP-B service DCS Auto
6.1.35 BFP-C service DCS Auto
6.2 Boiler ignition preparation DCS Auto MC/FWC logic
6.3 HP & LP heater level control - -
6.4 Hydrazine pump DCS Auto
6.5 Ammonia pump DCS Auto
6.6 LP bypass hydraulic power - -
6.7 Boiler purge / HFO leak test DCS Auto MC/FWC logic
6.8 Ignition of mill "A" igniters DCS Auto MC/FWC logic
6.9 Ignition of mill "C" igniters DCS Auto MC/FWC logic
6.10 Igniters flow control / SH spray control DCS Auto MC/FWC logic

7 Turbine start - -
7.1 MSP (L) drain valve DCS Auto MC/FWC logic
7.2 MSP (R) drain valve DCS Auto MC/FWC logic
7.3 MSP warming valve DCS Auto MC/FWC logic
7.4 RSP (L) drain valve DCS Auto MC/FWC logic
7.5 RSP (R) drain valve DCS Auto MC/FWC logic
7.6 RSP warming valve DCS Auto MC/FWC logic
7.7 CRP drain valve (upstream of CRH chk vlv) DCS Auto MC/FWC logic
7.8 CRP drain valve (downstream of CRH chk vlv) DCS Auto MC/FWC logic
7.9 MCV (L) inlet drain valve DCS Auto
7.10 MCV (R) inlet drain valve DCS Auto
7.11 RSV (L) inlet drain valve DCS Auto
7.12 RSV (R) inlet drain valve DCS Auto
7.13 ICV (L) inlet drain valve DCS Auto
7.14 ICV (R) inlet drain valve DCS Auto
7.15 MCV (L) outlet drain valve DCS Auto
7.16 MCV (R) outlet drain valve DCS Auto
7.17 HP turbine casing drain valve DCS Auto
7.18 ICV outlet drain valve DCS Auto
7.19 LP balance piping drain valve DCS Auto
7.20 Gland steam piping drain valve DCS Auto
7.21 Gland steam header pressure control DCS Auto
7.22 Lube oil temperature control DCS Auto Turn to "Auto" at Tubine oil system FG
7.23 H2 gas temp. control DCS Auto
7.24 Seal oil temp. control DCS Auto
7.25 AVR / MVR mode DCS AVR

8 Synchronization - -
8.1 TGR operation mode 65P/65L DCS 65P
8.2 Power set DCS Auto
8.3 52G synchronization mode SYP Auto

9 Load up (1) - (2) - -


9.1 MWD upper limit set 40% - -
9.2 MWD lower limit set 0% - -
9.3 Ignition of remaining 12 igniters DCS Auto MC/FWC logic
9.4 Load set 75MW (25%L) - -
9.5 LP heater service in - -
9.5.1 No.4 extraction steam stop valve DCS Auto
9.5.2 No.5 extraction steam stop valve DCS Auto
9.5.3 No.3 extraction steam stop valve DCS Auto
9.5.4 No.2 LP heater level control DCS Auto
9.5.5 No.3 LP heater level control DCS Auto
9.6 HP heater service in - -
9.6.1 No.1 extraction steam stop valve DCS Auto
9.6.2 No.2 extraction steam stop valve DCS Auto
9.6.3 No.3 extraction steam stop valve DCS Auto
9.6.4 No.5 HP heater vent valve DCS Auto
9.6.5 No.6 HP heater vent valve DCS Auto
9.6.6 No.7 HP heater vent valve DCS Auto
9.6.7 No.5 HP heater drain warming valve DCS Auto
9.6.8 No.6 HP heater drain warming valve DCS Auto
9.6.9 No.7 HP heater drain warming valve DCS Auto
9.6.10 No.5 HP heater level control DCS Auto
9.6.11 No.6 HP heater level control DCS Auto
9.6.12 No.7 HP heater level control DCS Auto
9.7 1'st mill start DCS Auto MC/FWC logic
9.8 PAFs start DCS Auto
9.9 Load set 90MW (30%L) - -
9.10 Load set 120MW (40%L) - -

10 Load up (3) - (5) - -


10.1 2'nd mill start DCS Auto MC/FWC logic
10.2 Fuel oil to coal change DCS Auto MC/FWC logic
10.3 Fuel oil to coal change (unit master) - -
10.4 2'nd BFP start - -
10.4.1 Deaerator recirculation pump DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.2 Deaerator recirculation pump discharge valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.3 BFP booster pump-A strainer inlet valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.4 BFP booster pump-B strainer inlet valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.5 BFP booster pump-C strainer inlet valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.6 BFP booster pump-A strainer outlet valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.7 BFP booster pump-B strainer outlet valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.8 BFP booster pump-C strainer outlet valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.9 BFP-A warming inlet valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.10 BFP-B warming inlet valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.11 BFP-C warming inlet valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.12 BFPBP-A discharge vent valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.13 BFPBP-B discharge vent valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.14 BFPBP-C discharge vent valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.15 BFP-A discharge vent valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.16 BFP-B discharge vent valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.17 BFP-C discharge vent valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.18 BFP-A mini flow control DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.19 BFP-B mini flow control DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.20 BFP-C mini flow control DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.21 Boiler feed water pump-A DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.22 Boiler feed water pump-B DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.23 Boiler feed water pump-C DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.24 BFP-A auxiliary oil pump DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.25 BFP-B auxiliary oil pump DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.26 BFP-C auxiliary oil pump DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.27 Boiler feed water pump-A discharge valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.28 Boiler feed water pump-B discharge valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.29 Boiler feed water pump-C discharge valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.30 BFP-A intermediate discharge valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.31 BFP-B intermediate discharge valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.4.32 BFP-C intermediate discharge valve DCS Auto checked "Auto" mode at 1'st BFP start FG
10.5 MWD upper limit set 50%+a - -
10.6 MWD lower limit 30%-a - -
10.7 MWD set 150MW (50%L) - -
10.8 3'rd mill start DCS Auto MC/FWC logic
10.9 MWD upper limit set 75%+a - -
10.10 MWD Lower limit set 30%-a - -
10.11 MWD set 225MW (75%L) - -
10.12 4'th mill start DCS Auto MC/FWC logic
10.13 MWD upper limit set 100%+a - - *) Three mill selected
10.14 MWD lower limit set 30%-a - - *) Three mill selected
10.15 MWD set 300MW (100%L) - - *) Three mill selected
Table.2 Operation switch condition (shut-down)
No. Operation item Location condition Checked 備考
1 Load down (1) - -

2 Load down (2) - -


2.1 3'rd mill stop FG DCS Auto MC/FWC logic
2.2 MWD upper limit set FG - -
2.3 MWD lower limit set FG - -
2.4 MWD sedt 90MW FG - -
2.5 Coal to fuel oil change ON DCS Auto MC/FWC logic
2.6 2'nd mill stop FG DCS Auto MC/FWC logic
2.7 1'st BFP stop FG - -
2.7.1 BFP-A warming inlet valve DCS Auto
2.7.2 BFP-B warming inlet valve DCS Auto
2.7.3 BFP-C warming inlet valve DCS Auto
2.7.4 BFP-A auxiliary oil pump DCS Auto
2.7.5 BFP-B auxiliary oil pump DCS Auto
2.7.6 BFP-C auxiliary oil pump DCS Auto
2.7.7 CP-A discharge valve DCS Auto
2.7.8 CP-B discharge valve DCS Auto
2.7.9 Boiler feed water pump-A DCS Auto
2.7.10 Boiler feed water pump-B DCS Auto
2.7.11 Boiler feed water pump-C DCS Auto
2.7.12 BFP-A mini flow control DCS Auto
2.7.13 BFP-B mini flow control DCS Auto
2.7.14 BFP-C mini flow control DCS Auto
2.7.15 BFP booster pump-A strainer inlet valve DCS Auto
2.7.16 BFP booster pump-B strainer inlet valve DCS Auto
2.7.17 BFP booster pump-C strainer inlet valve DCS Auto
2.7.18 BFP booster pump-A strainer outlet valve DCS Auto
2.7.19 BFP booster pump-B strainer outlet valve DCS Auto
2.7.20 BFP booster pump-C strainer outlet valve DCS Auto
2.7.21 BFP-A intermediate discharge valve DCS Auto
2.7.22 BFP-B intermediate discharge valve DCS Auto
2.7.23 BFP-C intermediate discharge valve DCS Auto
2.8 Deaerator recirculation pump FG - -
2.8.1 Deaerator recirculation pump DCS Auto
2.9 LP heater service out FG - -
2.9.1 No.4 extraction steam stop valve DCS Auto
2.9.2 No.5 extraction steam stop valve DCS Auto
2.9.3 No.3 extraction steam stop valve DCS Auto
2.10 HP heater service out FG DCS Auto
2.10.1 No.1 extraction steam stop valve DCS Auto
2.10.2 No.2 extraction steam stop valve DCS Auto
2.10.3 No.3 extraction steam stop valve DCS Auto
2.10.4 No.5 HP heater vent valve DCS Auto
2.10.5 No.6 HP heater vent valve DCS Auto
2.10.6 No.7 HP heater vent valve DCS Auto
2.10.7 No.5 HP heater drain warming valve DCS Auto
2.10.8 No.6 HP heater drain warming valve DCS Auto
2.10.9 No.7 HP heater drain warming valve DCS Auto

3 Disconnection - -

4 Pulling out fire - -


Shut down all igniters FG DCS Auto MC/FWC logic

5 Aux. equipment stop - -


5.1 Start-up Dea pegging control Auto - -
5.2 Vacuum break FG - -
5.2.1 No.6 HP heater drain warming valve DCS Auto
5.2.2 No.7 HP heater drain warming valve DCS Auto
5.2.3 Condenser level control (make-up) DCS Auto
5.2.4 Condenser level control (spil over) DCS Auto
5.2.5 Gland steam header pressure control DCS Auto
5.2.6 Hogging ejector driving steam inlet valve DCS Auto
5.2.7 Hogging ejector gas inlet valve DCS Auto
5.2.8 Gland steam condenser fan-A DCS Auto
5.2.9 Gland steam condenser fan-B DCS Auto
5.2.10 Steam jet air ejector driving steam inlet valve-A DCS Auto
5.2.11 Steam jet air ejector-A gas inlet valve DCS Auto
5.2.12 Steam jet air ejector driving steam inlet valve-B DCS Auto
5.2.13 Steam jet air ejector-B gas inlet valve DCS Auto
5.2.14 Aux. steam stop valve DCS Auto
5.2.15 Turbine gland steam supply warming valve DCS Auto
5.2.16 Vacuum breaker valve DCS Auto
5.3 2'nd BFP stop FG - -
5.3.1 BFP-A warming inlet valve DCS Auto
5.3.2 BFP-B warming inlet valve DCS Auto
5.3.3 BFP-C warming inlet valve DCS Auto
5.3.4 BFP-A auxiliary oil pump DCS Auto
5.3.5 BFP-B auxiliary oil pump DCS Auto
5.3.6 BFP-C auxiliary oil pump DCS Auto
5.3.7 CP-A discharge valve DCS Auto
5.3.8 CP-B discharge valve DCS Auto
5.3.9 Boiler feed water pump-A DCS Auto
5.3.10 Boiler feed water pump-B DCS Auto
5.3.11 Boiler feed water pump-C DCS Auto
5.3.12 BFP-A mini flow control DCS Auto
5.3.13 BFP-B mini flow control DCS Auto
5.3.14 BFP-C mini flow control DCS Auto
5.3.15 BFP booster pump-A strainer inlet valve DCS Auto
5.3.16 BFP booster pump-B strainer inlet valve DCS Auto
5.3.17 BFP booster pump-C strainer inlet valve DCS Auto
5.3.18 BFP booster pump-A strainer outlet valve DCS Auto
5.3.19 BFP booster pump-B strainer outlet valve DCS Auto
5.3.20 BFP booster pump-C strainer outlet valve DCS Auto
5.3.21 BFP-A intermediate discharge valve DCS Auto
5.3.22 BFP-B intermediate discharge valve DCS Auto
5.3.23 BFP-C intermediate discharge valve DCS Auto
5.4 Condensate pump stop FG - -
5.4.1 CP-A DCS Auto
5.4.2 CP-B DCS Auto
5.4.3 CP-A discharge valve DCS Auto
5.4.4 CP-B discharge valve DCS Auto
5.4.5 Condensater mini flow control DCS Auto
5.4.6 BFP-A warming inlet valve DCS Auto
5.4.7 BFP-B warming inlet valve DCS Auto
5.4.8 BFP-C warming inlet valve DCS Auto
APS test

Table.3 Operation test item (start-up)


Schedule 1 2 3 4 5 6 7 8

Event

Boiler ignition
-
Sea water system
Steam addmision
-
Turbine start
Rated speed
-
Turbine start
Synchronizing
-
Turbine start
50% Load
-
Turbine start
100% Load
-
Turbine start
100% Load
-
Sea water system
100% Load
-
Sea water system
Start-up mode(C : Cold, W : Warm, H : Hot, VH : Very hot) C H W C W H C H
APS(Start-up) (X : Use, S : Section, - : not use) X S S S X X X X
No. APS
Operation item KKS No. Output Interface APS USE/OUT (U : Use, Not-use : -)
flow
1 Sea water System U - - - - - U U
1.1 Second CWP start FG - - - MGL21 U - - - - - U U
1.1.1 Second CWP start XXXX DO MCC TC124 U - - - - - U U
1.1.2 Priming vaccum pump auto mode - - - TC124 U - - - - - U U

2 Turbine oil system U - - - - - U U


2.1.1 Turbine oil system FG - - - MGL21 U - - - - - U U
2.1.2 Main oil tank vapor extractor start MAV10AN001 DO MCC TB104 U - - - - - U U
2.1.3 MOP auto mode MAV21AP001 DO TPR TB104 U - - - - - U U
2.1.4 Turbine lube oil temp. control auto mode MAV42AA151 - - TB104 U - - - - - U U
2.1.5 EOP auto mode MAV24AP001 - - TB104 U - - - - - U U
2.1.6 JOP auto mode MAV61AP001 DO MCC TB104 U - - - - - U U

3 Turning/Condensate system U - - - - - U U
3.1 Turning system FG - - - MGL21 U - - - - - U U
3.1.1 Solenoid valve for turning device MAK10AA005 DO F - U - - - - - U U
3.2 CFP start FG - - - MGL21 U - - - - - U U
3.2.1 Control fluid radiator fan auto MAX35AN001 - - TB114 U - - - - - U U
3.2.2 Control fluid heating pump auto MAX15AH001 - - TB114 U - - - - - U U
3.2.3 MAX21AP001 U - - - - - U U
Control fluid pump start DO MCC TB114
MAX22AP001
3.3 Condensate pump start FG - - - MGL21 U - - - - - U U
3.3.1 LCA21AA001 U - - - - - U U
CP discharge valve close DO F TC104
LCA22AA001
3.3.2 Condensate mini flow control auto LCA30AA151 - - TC104 U - - - - - U U
3.3.3 LCB10AP001 U - - - - - U U
CP start DO 6.6kV TC104
LCB20AP001
3.3.4 LCA21AA001 U - - - - - U U
CP discharge valve open DO F TC104
LCA22AA001

4 Preparation of initial firing U - - - - - U U


4.1 Draft function group FG XXXX XX XX MGL22 U - - - - - U U
4.2 Heavy oul pump pressure control XXXX XX XX MGL22 U - - - - - U U
4.3 Boiler drain & vent valves FG XXXX XX XX MGL22 U - - - - - U U

5 Vacuum up U - - - - - U U
5.1 Start-up Dea pegging control A - - - MGL22 U - - - - - U U
5.1.1 Deaerator storage tank pressure control (start-up U - - - - - U U
LBG50AA151 - - MGL22
pegging steam) auto
5.2 Vaccum up FG - - - MGL22 U - - - - - U U
5.2.1 Vaccum breaker valve close MAG10AA550 DO F TE124 U - - - - - U U
5.2.2 No.6 HP heater drain warming valve open LCH60AA011 DO F TE124 U - - - - - U U
5.2.3 No.7 HP heater drain warming valve open LCH70AA011 DO F TE124 U - - - - - U U
5.2.4 Deaerator level control valve auto LCA26AA151 AO F TE124 U - - - - - U U
5.2.5 Hogging ejector draiving steam inlet valve open LBG42AA001 DO F TE124 U - - - - - U U
5.2.6 Hogging ejector gas inlet valve open MAJ20AA002 DO F TE124 U - - - - - U U
5.2.7 MAM35AN001 U - - - - - U U
Gland steam condenser fan start DO MCC TE124
MAM35AN002
5.2.8 Aux. steam stop valve open MAW10AA001 DO F TE124 U - - - - - U U
5.2.9 LBG40AA001 U - - - - - U U
Steam jet air ejector driving steam inlet valve open DO F TE124
LBG41AA001
5.2.10 MAJ10AA023 U - - - - - U U
Steam jet air ejector gas inlet valve open DO F TE125
MAJ10AA024
5.2.11 Hogging ejector gas inlet valve close MAJ20AA002 DO F TE125 U - - - - - U U
5.2.12 Hogging ejector draiving steam inlet valve close LBG42AA001 DO F TE125 U - - - - - U U
APS test

Schedule 1 2 3 4 5 6 7 8

Event

Boiler ignition
-
Sea water system
Steam addmision
-
Turbine start
Rated speed
-
Turbine start
Synchronizing
-
Turbine start
50% Load
-
Turbine start
100% Load
-
Turbine start
100% Load
-
Sea water system
100% Load
-
Sea water system
Start-up mode(C : Cold, W : Warm, H : Hot, VH : Very hot) C H W C W H C H
APS(Start-up) (X : Use, S : Section, - : not use) X S S S X X X X
No. APS
Operation item KKS No. Output Interface APS USE/OUT (U : Use, Not-use : -)
flow
6 Boiler ignition U - - - - - U U
6.1 1'st BFP start FG MGL023 U - - - - - U U
6.1.1 Deaerator recirculation pump start LCF10AP001 DO MCC TD104 U - - - - - U U
6.1.2 Deaerator recirculation pump discharge valve open LCF12AA001 DO F TD104 U - - - - - U U
6.1.3 BFP-A warming inlet valve open LAB21AA003 DO F TD104 U - - - - - U U
6.1.4 BFP-B warming inlet valve open LAB22AA003 DO F TD104 U - - - - - U U
6.1.5 BFP-C warming inlet valve open LAB23AA003 DO F TD104 U - - - - - U U
6.1.6 BFP booster pump-A strainer inlet valve open LAB11AA001 DO F TD104 U - - - - - U U
6.1.7 BFP booster pump-B strainer inlet valve open LAB12AA001 DO F TD104 U - - - - - U U
6.1.8 BFP booster pump-C strainer inlet valve open LAB13AA001 DO F TD104 U - - - - - U U
6.1.9 BFP booster pump-A strainer outlet valve open LAB11AA002 DO F TD105 U - - - - - U U
6.1.10 BFP booster pump-B strainer outlet valve open LAB12AA002 DO F TD105 U - - - - - U U
6.1.11 BFP booster pump-C strainer outlet valve open LAB13AA002 DO F TD105 U - - - - - U U
6.1.12 BFP-A mini flow valve open LAB31AA151 AO F TD105 U - - - - - U U
6.1.13 BFP-B mini flow valve open LAB32AA151 AO F TD105 U - - - - - U U
6.1.14 BFP-C mini flow valve open LAB33AA151 AO F TD105 U - - - - - U U
6.1.15 BFP-A auxiliary oil pump start LAV10AP001 DO MCC TD105 U - - - - - U U
6.1.16 BFP-B auxiliary oil pump start LAV20AP001 DO MCC TD105 U - - - - - U U
6.1.17 BFP-C auxiliary oil pump start LAV30AP001 DO MCC TD105 U - - - - - U U
6.1.18 BFP-A mini flow valve close LAB31AA151 AO F TD105 U - - - - - U U
6.1.19 BFP-B mini flow valve close LAB32AA151 AO F TD105 U - - - - - U U
6.1.20 BFP-C mini flow valve close LAB33AA151 AO F TD105 U - - - - - U U
6.1.21 BFP-A discharge vent valve open LAB31AA501 DO F TD106 U - - - - - U U
6.1.22 BFP-B discharge vent valve open LAB32AA501 DO F TD106 U - - - - - U U
6.1.23 BFP-C discharge vent valve open LAB33AA501 DO F TD106 U - - - - - U U
6.1.24 BFPBP-A discharge vent valve open LAB21AA501 DO F TD106 U - - - - - U U
6.1.25 BFPBP-B discharge vent valve open LAB22AA501 DO F TD106 U - - - - - U U
6.1.26 BFPBP-C discharge vent valve open LAB23AA501 DO F TD106 U - - - - - U U
6.1.27 BFPBP-A discharge vent valve close LAB21AA501 DO F TD106 U - - - - - U U
6.1.28 BFPBP-B discharge vent valve close LAB22AA501 DO F TD106 U - - - - - U U
6.1.29 BFPBP-C discharge vent valve close LAB23AA501 DO F TD106 U - - - - - U U
6.1.30 BFP-A discharge vent valve close LAB31AA501 DO F TD106 U - - - - - U U
6.1.31 BFP-B discharge vent valve close LAB32AA501 DO F TD106 U - - - - - U U
6.1.32 BFP-C discharge vent valve close LAB33AA501 DO F TD106 U - - - - - U U
6.1.33 BFP-A mini flow valve open LAB31AA151 AO F TD107 U - - - - - U U
6.1.34 BFP-B mini flow valve open LAB32AA151 AO F TD107 U - - - - - U U
6.1.35 BFP-C mini flow valve open LAB33AA151 AO F TD107 U - - - - - U U
6.1.36 BFP-A discharge valve open LAB31AA001 DO F TD107 U - - - - - U U
6.1.37 BFP-B discharge valve open LAB32AA001 DO F TD107 U - - - - - U U
6.1.38 BFP-C discharge valve open LAB33AA001 DO F TD107 U - - - - - U U
6.1.39 BFP-A intermediate discharge valve open LAB21AA004 DO F TD107 U - - - - - U U
6.1.40 BFP-B intermediate discharge valve open LAB22AA004 DO F TD107 U - - - - - U U
6.1.41 BFP-C intermediate discharge valve open LAB23AA004 DO F TD107 U - - - - - U U
6.2 Boiler ignition preparation FG XXXX XX XX MGL23 U - - - - - U U
6.3 HP & LP heater level control FG - - - MGL23 U - - - - - U U
6.3.1 No.2 LP heater level control valve auto LCJ20AA151 AO F MGL23 U - - - - - U U
6.3.2 LCJ30AA151 U - - - - - U U
No.3 LP heater level control valve auto AO F MGL23
LCJ30AA152
6.4 Chemical dosing system FG - - - MGL23 U - - - - - U U
6.4.1 Hydrazine pump start XXXX XX XX XX U - - - - - U U
6.5 Chemical dosing system FG - - - MGL23 U - - - - - U U
6.5.1 Ammonia pumu start XXXX XX XX XX U - - - - - U U
6.6 LP bypass hydraulic unit FG - - - MGL23 U - - - - - U U
6.6.1 LP bypass hydraulic power unit ON MAP10 DO Oil unit MGL23 U - - - - - U U
6.7 Boiler purge / HFO leak test FG XXXX XX XX XX U - - - - - U U
6.8 Ignition of mill "A" igniters FG XXXX XX XX XX U - - - - - U U
6.9 Ignition of mill "C" igniters FG XXXX XX XX XX U - - - - - U U
6.10 Igniters flow control / SH spray control auto FG XXXX XX XX XX U - - - - - U U
APS test

Schedule 1 2 3 4 5 6 7 8

Event

Boiler ignition
-
Sea water system
Steam addmision
-
Turbine start
Rated speed
-
Turbine start
Synchronizing
-
Turbine start
50% Load
-
Turbine start
100% Load
-
Turbine start
100% Load
-
Sea water system
100% Load
-
Sea water system
Start-up mode(C : Cold, W : Warm, H : Hot, VH : Very hot) C H W C W H C H
APS(Start-up) (X : Use, S : Section, - : not use) X S S S X X X X
No. APS
Operation item KKS No. Output Interface APS USE/OUT (U : Use, Not-use : -)
flow
7 Turbine start - U U U U U U U
7.1.1 Turbine reset MAY20EC011 DO TPR TS101 - U U U U U U U
7.2 Turbine drain valve open - - - TS103 - U U U U U U U
7.2.1 MCV(L) inlet drain valve open MAA10AA414 DO F TS103 - U U U U U U U
7.2.2 MCV(R) inlet drain valve open MAA10AA415 DO F TS103 - U U U U U U U
7.2.3 ICV(L) inlet drain valve open MAB10AA416 DO F TS103 - U U U U U U U
7.2.4 ICV(R) inlet drain valve open MAB10AA417 DO F TS103 - U U U U U U U
7.2.5 ICV(L) outlet drain valve open MAA10AA416 DO F TS103 - U U U U U U U
7.2.6 ICV(R) outlet drain valve open MAA10AA417 DO F TS103 - U U U U U U U
7.2.7 HP turbine casing drain valve MAA10AA418 DO F TS103 - U U U U U U U
7.2.8 ICV outlet drain valve MAB10AA420 DO F TS103 - U U U U U U U
7.2.9 LP balance pipe drain valve MAA10AA421 DO F TS103 - U U U U U U U
7.2.10 Gland steam piping drain valve MAW10AA401 DO F TS103 - U U U U U U U
7.3 MSV/RSV open - - - TS105 - U U U U U U U
7.3.1 MSV/RSV open MAY10EC014 DO TPR TS105 - U U U U U U U
7.4 TSE limit condition / Drain valve open - - - TS107 - U U U U U U U
7.4.1 MCV(L) inlet drain valve open MAA10AA414 DO F TS107 - U U U U U U U
7.4.2 MCV(R) inlet drain valve open MAA10AA415 DO F TS107 - U U U U U U U
7.5 Speed-up (1) - - - TS109 - - U U U U U U
7.5.1 Heat soak speed MAY10EC011 DO TGR TS109 - - U U U U U U
7.6 Speed-up (2) - - - TS112 - - U U U U U U
7.6.1 Rated speed MAY10EC012 DO TGR TS112 - - U U U U U U
7.7 Excitation - - - TS114 - - - U U U U U
7.7.1 Field CB 41 ON MKY10EC001 DO TGR TS114 - - - U U U U U

8 Synchronize / Initial load - - - U U U U U


8.1 Synchronization FG - - - TS116 - - - U U U U U
8.8.1 ASY ON MKY20EC001 DO GPR TS116 - - - U U U U U
8.2 Drain valve close check - - - TS116 - - - U U U U U
8.2.1 MCV(L) inlet drain valve open MAA10AA414 DO F TS116 - - - U U U U U
8.2.2 MCV(R) inlet drain valve open MAA10AA415 DO F TS116 - - - U U U U U

9 Load up (1)-(2) - - - - U U U U
9.1 MWD upper limit set 40% - - - MGL27 - - - - U U U U
9.2 MWD lower limit set 0% - - - MGL27 - - - - U U U U
9.3 Ignition of remaining 12 igniters FG - - - MGL27 - - - - U U U U
9.4 Load set 75MW (25%L) - - - MGL27 - - - - U U U U
9.5 LP heater service in FG - - - MGL27 - - - - U U U U
9.5.1 No.3 LP heater vent valve open LCJ32AA502 DO F TE104 - - - - U U U U
9.5.2 No.5 extraction steam stop valve open LBS30AA001 DO F TE104 - - - - U U U U
9.6 HP heater service in FG - - - MGL27 - - - - U U U U
9.6.1 No.5 HP heater drain warming valve open LCH50AA011 DO F TE114 - - - - U U U U
9.6.2 No.5 HP heater vent valve open LCH52AA502 DO F TE114 - - - - U U U U
9.6.3 No.5 HP heater level control LCH50AA151 AO F TE114 - - - - U U U U
9.6.4 No.3 extraction steam stop valve open LBQ50AA001 DO F TE114 - - - - U U U U
9.6.5 No.6 HP heater vent valve open LCH62AA502 DO F TE114 - - - - U U U U
9.6.6 No.6 HP heater drain warming valve close LCH60AA011 DO F TE114 - - - - U U U U
9.6.7 LCH60AA151 - - - - U U U U
No.6 HP heater level control valve close reset AO - TE114
LCH60AA152
9.6.8 No.2 extraction steam stop valve open LBQ60AA001 DO F TE114 - - - - U U U U
9.6.9 No.7 HP heater vent valve open LCH72AA502 DO F TE114 - - - - U U U U
9.6.10 No.7 HP heater drain warming valve close LCH70AA011 DO F TE114 - - - - U U U U
9.6.11 LCH70AA151 - - - - U U U U
No.7 HP heater level control valve close reset DO F TE114
LCH70AA152
9.6.12 No.1 extraction steam stop valve open LBQ70AA001 DO F TE114 - - - - U U U U
9.7 1'st mill start FG XXXX XX XX MGL27 - - - - U U U U
9.8 PAFs start FG XXXX XX XX MGL27 - - - - U U U U
9.9 Load set 90MW (30%L) - - - MGL27 - - - - U U U U
9.10 Load set 120MW (40%L) - - - MGL27 - - - - U U U U
APS test

Schedule 1 2 3 4 5 6 7 8

Event

Boiler ignition
-
Sea water system
Steam addmision
-
Turbine start
Rated speed
-
Turbine start
Synchronizing
-
Turbine start
50% Load
-
Turbine start
100% Load
-
Turbine start
100% Load
-
Sea water system
100% Load
-
Sea water system
Start-up mode(C : Cold, W : Warm, H : Hot, VH : Very hot) C H W C W H C H
APS(Start-up) (X : Use, S : Section, - : not use) X S S S X X X X
No. APS
Operation item KKS No. Output Interface APS USE/OUT (U : Use, Not-use : -)
flow
10 Load up (3)-(5) - - - - U U U U
10.1 2'nd mill start FG XXXX XX XX MGL27 - - - - U U U U
10.2 Fuel oil to coal change FG XXXX XX XX MGL27 - - - - U U U U
10.3 Fuel oil to coal change FG (UM) XXXX XX XX MGL27 - - - - U U U U
10.4 2'nd BFP start FG - - - TD113 - - - - U U U U
10.4.1 LAC21AP001 - - - - U U U U
BFP start LAC22AP001 DO 6.6kV TD113
LAC23AP001
10.5 BFP service in - - - TD113 - - - - U U U U
10.6 MWD upper limit set 50%+a - - - MGL29 - - - - U U U U
10.7 MWD lower limit set 30%-a - - - MGL29 - - - - U U U U
10.8 MWD set 150MW (50%L) - - - MGL29 - - - - U U U U
10.9 3'rd mill start XXXX XX XX MGL29 - - - - - U U U
10.10 MWD upper limit set 75%+a - - - MGL29 - - - - - U U U
10.11 MWD lower limit set 30%-a - - - MGL29 - - - - - U U U
10.12 MWD set 225MW (75%L) - - - MGL29 - - - - - U U U
10.13 4'th mill start XXXX XX XX MGL29 - - - - - U U U
10.14 MWD upper limit set 100% - - - MGL29 - - - - - U U U
10.15 MWD lower limit set 30%-a - - - MGL29 - - - - - U U U
10.16 MWD set 300MW (100%L) - - - MGL29 - - - - - U U U
APS test

Table.4 Operation test item (shut-down)


Schedule 1 2 3 4 5 6 7 8

Event

Disconnection
-
50%(L)
Disconnection
-
100%(L)
Disconnection
-
100%(L)
Disconnection
-
100%(L)
Pulling out fire
-
100%(L)
Epuipment stop
-
100%(L)
Epuipment stop
-
100%(L)
Epuipment stop
-
100%(L)
Start-up mode(C : Cold, W : Warm, H : Hot, VH : Very hot) - - - - - - - -
APS(Shut-down) (X : Use, S : Section, - : not use) X X X X X S S S
No. Operation item KKS No. Output Interface APS
flow APS USE/OUT (U : Use, Not-use : -)
1 Load down (1) - U U U U U U U
1.1 MWD upper limit set 300MW (100%+a) - - - MGL51 - U U U U U U U
1.2 MWD lower limit set 225MW (100%L+a) - - - MGL51 - U U U U U U U
1.3 MWD set 225MW (75%L) - - - MGL51 - U U U U U U U
1.4 Ignition of all 24 igniters FG XXXX XX XX MGL51 - U U U U U U U
1.5 4'th mill stop XXXX XX XX MGL51 - U U U U U U U
1.6 MWD upper limit set 230MW (75%L+a) - - - MGL51 - U U U U U U U
1.7 MWD lower limit set 85MW (30%L+a) - - - MGL51 - U U U U U U U
1.8 MWD set 150MW (50%L) - - - MGL51 - U U U U U U U

2 Load down (2) U U U U U U U U


2.1 3'rd mill stop XXXX XX XX MGL52 U U U U U U U U
2.2 MWD upper limit set 155MW (50%L+a) - - - MGL52 U U U U U U U U
2.3 MWD lower limit set 85MW (30%L+a) - - - MGL52 U U U U U U U U
2.4 MWD set 90MW (40%L) - - - MGL52 U U U U U U U U
2.5 Coal to fuel oil change ON XXXX XX XX MGL52 U U U U U U U U
2.6 2'nd mill stop XXXX XX XX MGL52 U U U U U U U U
2.7 1'st BFP stop FG - - - TD124 U U U U U U U U
2.7.1 BFP service in - - - TD124 U U U U U U U U
2.7.2 BFP auxiliary oil pump start LAV10AP001 U U U U U U U U
LAV20AP001
LAV30AP001 DO MCC TD124
2.7.3 BFP discharge vent valve close LAB31AA501 U U U U U U U U
LAB32AA501
LAB33AA501 DO F TD124
2.7.4 BFP stop LAC21AP001 U U U U U U U U
LAC22AP001
LAC23AP001 DO 6.6kV TD125
2.7.5 BFP intermediate discharge valve open LAB21AA004 U U U U U U U U
LAB22AA004
LAB23AA004 DO F TD125
2.7.6 BFP auxiliary oil pump stop LAV10AP001 U U U U U U U U
LAV20AP001
LAV30AP001 DO MCC TD125
2.8 Deaerator recirculation pump start FG LCF10AP001 DO MCC MGL52 U U U U U U U U
2.9 MWD upper limit set 85MW (30%L+a) - - - MGL53 U U U U U U U U
2.10 MWD lower limit set 0MW (0%L+a) - - - MGL53 U U U U U U U U
2.11 MWD set 75MW (25%L) - - - MGL53 U U U U U U U U
2.12 LP heater service out FG - - - MGL53 U U U U U U U U
2.12.1 No.5 extraction steam stop valve close LBS30AA001 DO F TE108 U U U U U U U U
2.13 HP heater service out FG - - - MGL53 U U U U U U U U
2.13.1 No.1 extraction steam stop valve close LBQ70AA001 DO F TE117 U U U U U U U U
2.13.2 No.2 extraction steam stop valve open LBQ60AA001 DO F TE117 U U U U U U U U
2.13.3 No.3 extraction steam stop valve open LBQ50AA001 DO F TE117 U U U U U U U U
2.14 All mill stop FG XXXX XX XX MGL53 U U U U U U U U
2.15 PAFs stop FG XXXX XX XX MGL53 U U U U U U U U
2.16 MWD set 30MW (10%L) - - - MGL53 U U U U U U U U

3 Disconnection U U U U U U U U
3.1 Turbine stop FG (ASD) - - - MGL21 U U U U U U U U
3.1.1 Turbine trip from ASD MAY20EC012 DO TPR TS153 U U U U U U U U

4 Pulling out fire - - - - U U U U


4.1 Shut down all igniters FG XXXX XX XX MGL56 - - - - U U U U
APS test

Schedule 1 2 3 4 5 6 7 8

Event

Disconnection
-
50%(L)
Disconnection
-
100%(L)
Disconnection
-
100%(L)
Disconnection
-
100%(L)
Pulling out fire
-
100%(L)
Epuipment stop
-
100%(L)
Epuipment stop
-
100%(L)
Epuipment stop
-
100%(L)
Start-up mode(C : Cold, W : Warm, H : Hot, VH : Very hot) - - - - - - - -
APS(Shut-down) (X : Use, S : Section, - : not use) X X X X X S S S
No. Operation item KKS No. Output Interface APS
flow APS USE/OUT (U : Use, Not-use : -)
5 Aux. equipment stop - - - - - U U U
5.1 Start-up Dea pegging control Auto - - - MGL57 - - - - - U U U
5.2 Vacuum break FG - - - MGL57 - - - - - U U U
5.2.1 Steam jet air ejector gas inlet valve close MAJ10AA023 - - - - - U U U
MAJ10AA024 DO F TE133
5.2.2 Steam jet air ejector driving steam inlet valve closeLBG40AA001 - - - - - U U U
LBG41AA001 DO F TE133
5.2.3 Vaccum breaker valve open MAG10AA550 DO F TE133 - - - - - U U U
5.2.4 Aux. steam stop valve close MAW10AA001 DO F TE133 - - - - - U U U
5.3 Draft stop FG XXXX XX XX MGL57 - - - - - U U U
5.4 Aux. steam press. control valve inlet valve XXXX XX XX MGL57 - - - - - U U U
5.5 2'nd BFP stop FG - - - MGL57 - - - - - U U U
5.5.1 BFP service out - - - TD133 - - - - - U U U
5.5.2 BFP auxiliary oil pump start LAV10AP001 - - - - - U U U
LAV20AP001
LAV30AP001 DO MCC TD133
5.5.3 BFP-A discharge vent valve close LAB31AA501 DO F TD133 - - - - - U U U
5.5.4 BFP-B discharge vent valve close LAB32AA501 DO F TD133 - - - - - U U U
5.5.5 BFP-C discharge vent valve close LAB33AA501 DO F TD133 - - - - - U U U
5.5.6 BFP stop LAC21AP001 - - - - - U U U
LAC22AP001
LAC23AP001 DO 6.6kV TD133
5.5.7 BFP-A intermediate discharge valve close LAB21AA004 DO F TD133 - - - - - U U U
5.5.8 BFP-B intermediate discharge valve close LAB22AA004 DO F TD133 - - - - - U U U
5.5.9 BFP-C intermediate discharge valve close LAB23AA004 DO F TD133 - - - - - U U U
5.5.10 BFP auxiliary oil pump stop LAV10AP001 - - - - - U U U
LAV20AP001
LAV30AP001 DO MCC TD133
5.5.11 Deaerator recirculation pump start LCF10AP001 DO MCC TD133 - - - - - U U U
5.5.12 Deaerator recirculation pump discharge valve open LCF12AA001 DO F TD133 - - - - - U U U
5.6 Condensate pump stop FG - - - MGL57 - - - - - U U U
5.6.1 CP discharge valve close LCA21AA001 - - - - - U U U
LCA22AA001 DO F TC113
5.6.2 CP stop LCB10AP001 - - - - - U U U
LCB20AP001 DO 6.6kV TC113
5.6.3 BFP-A warming inlet valve close LAB21AA003 DO F TC113 - - - - - U U U
5.6.4 BFP-B warming inlet valve close LAB22AA003 DO F TC113 - - - - - U U U
5.6.5 BFP-C warming inlet valve close LAB23AA003 DO F TC113 - - - - - U U U
5.7 Chemical dosing system FG - - - MGL57 - - - - - U U U
Hydrazine pump stop FG XXXX XX XX XX - - - - - U U U
5.8 Chemical dosing system FG - - - MGL57 - - - - - U U U
Ammonia pump stop FG XXXX XX XX XX - - - - - U U U
Fig. 1 System configuration

HARDWIRE
CHEMICAL DOSING SYSTEM

TG BUILDING GLAND FLOOR


A B C D E F G H

Fig.2 APS flow chart

1 1

Main DCS

UNIT MASTER
NS1-11MAA-I-FES-0503
1
(MMI) OKB-116 UM02

START-UP S
2 PHASE 1 MGL21, MGL22, MGL23, MGL24, MGL25, 2
(MMI) Ro MGL26, MGL27, MGL28, MGL50
PB MASTER GROUP RESET WL
START-UP
PHASE
2 OR
MGL50
1 SHUT-DOWN PHASE
MGL50

(MMI) (MMI) (MMI) (MMI) (MMI) (MMI) (MMI) (MMI) (MMI) (MMI)

SEA WATER TURBINE OIL TURNING / TURBINE LOAD UP LOAD UP


3
SYSTEM SYSTEM CONDENSATE PREPARATION OF VACUUM BOILER START SYNCHRONIZE/ 3
MASTER MASTER SYSTEM MASTER INITIAL FIRING UP IGNITION INITIAL LOAD (1)~(2) (3)~(5)
(ATS)

2nd CWP Start Function Turbine Oil System Turbine System Auto Draft FG Start Up Deaerator Boiler Ignition Turbine Start FG(ATS) Synchronization FG Target Load Set(25%) Target Load Set (50%)
Group Function Group Pegging Steam Control Preparation FG
Confrol Fluid Pump Start Heavy Fuel Oil Pressure Auto Target Load Set(40%) Target Load Set (75%)
Ball Cleaning System FG Control Auto Boiler Purge/HFO Leak
Auto Vacuum Up FG Test FG Ignition of Remaining 12 Target Load Set (100%)
Condensate Pump Start Boiler Drain & Vent Igniters FG
FG Valves FG Mill A HFO Igniters FG 2'nd Mill Start
1'st Mill Start
Mill C HFO Igniters FG Fuel Oil to Coal Change
PAF Start
4 Igniters Flow Control/SH 3'rd Mill Start 4
Spray Control Auto FG HP Heater Service IN
FG 4'th Mill Start
1'st BFP Start FG
LP Heater Service IN 2'nd BFP Start FG
FG

(MMI) :MASTER PB
LAMP FLICER AT PERMISSIVE CONDITION ESTABLISH, AFTER PB_ON
THREE MILL S 3 MGL29 EACH MASTER GROUP SEQUENCE START
5 5
Ro
WL THREE MILL WL FLICKER: CONDITION ESTABLISH
(MMI) WL ON :MASTER START
NOT WL FOUR MILL GL ON :MASTER COMPLETION
FOUR MILL

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. START-UP PHASE BRAKE POINT 20
Title

Checked Sep.-2-2011 M.Okabe a


a : Dec-19-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

Main DCS

1 START-UP PHASE SELECT SEA WATER SEA WATER


A A
1 N SYSTEM N SYSTEM 1
MGL20 D MASTER D MASTER
COMPLETION

CWP-A START SECOND CWP START FG


1 NS1-11MAA-I-FES-0513-1
WA46552 TC122 OR A FG START COMMAND FG END
N NS1-11MAA-I-FES-0513-1
1 3 NS1-11MAA-I-FES-0513-1
D WA46552 TC122 WA46552 TC122
CWP-B START
2 NS1-11MAA-I-FES-0513-1
WA46552 TC122
NOT

2 2

A TURBINE OIL A TURBINE OIL


N SYSTEM N SYSTEM MASTER
D MASTER D COMPLETION
TURBINE OIL SYSTEM FG
1 START-UP PHASE SELECT A FG START COMMAND FG END
N NS1-11MAA-I-FES-0513
2 3 NS1-11MAA-I-FES-0513
D WA46551 TB102 WA46551 TB102
MGL20

NOT
3 3

A TURNING /
N CONDENSATE
D SYSTEM MASTER

TURNING SYSTEM AUTO


1 START-UP PHASE SELECT A AUTO COMMAND SYSTEM AUTO
N NS1-11MAA-I-FES-0513
3 2 NS1-11MAA-I-FES-0513
D WA46551 TB028 WA46551 TB028
MGL20

4 NOT 4

TURNING /
CFP START FG A
N CONDENSATE 6
FG START COMMAND D SYSTEM MASTER
A FG END MGL22
N NS1-11MAA-I-FES-0513
4 3 NS1-11MAA-I-FES-0513
D WA46551 TB112 WA46551 TB112

NOT

5 CODENSATE PUMP START FG 5


A FG START COMMAND FG END
N
NS1-11MAA-I-FES-0513-1
5 3 NS1-11MAA-I-FES-0513-1
D
WA46552 TC102 WA46552 TC102

NOT

Date Name

Ref Dwg.No.
SEA WATER SYSTEM / WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. TURBINE OIL SYSTEM / 21
Title

Checked Sep.-2-2011 M.Okabe a


a : Oct-20-2011 Revised Approved Sep.-2-2011 J.Tsurumine
TURNING/CONDENSATE SYSTEM
A B C D E F G H
A B C D E F G H

Main DCS

1 START-UP PHASE SELECT

MGL20 A PREPARATION OF
N INITIAL FIRING
1 D MC / FWC
1
MASTER
CONDENSATE & MAKE UP DRAFT FUNCTION GROUP
6 WATER SYSTEM COMPLETION A FG START COMMAND FG END
MGL21
N
NS1-11-I-FWC-6270
1 7 NS1-11-I-FWC-6275
D
125127-64-6270 125127-64-6275

NOT PREPARATION OF
A INITIAL FIRING
N
MASTER 6
D
COMPLETION MGL23
MC
HEAVY OIL PUMP PRESSURE CONTROL
2 2
A AUTO COMMAND SYSTEM AUTO
N NS1-18CT-I-IPS-3010
2 * NS1-18CT-I-IPS-3010
D KKZXVG10001 SA-17 KKZXVG10001 SA-17

NOT

MC / FWC
BOILER DRAIN & VENT VALVES FG
A CHECK START CHECKED
N 3 1
D NS1-11H-I-FWC-6265 NS1-11H-I-FWC-6268
125127-64-6265 125127-64-6268
3 3

NOT

4 A A VACUUM UP 4
VACUUM UP
N
MASTER
N MASTER 7
D D COMPLETION
START-UP DEA PEGGING CONTROL A MGL23,MGL25
A AUTO COMMAND SYSTEM AUTO
N 5 x
1 START-UP PHASE SELECT D NS1-11MAA-I-FES-0511
WA46558 RT202
NS1-11MAA-I-FES-0511
WA46558 RT202
MGL20

NOT

VACUUM UP FG
A FG START COMMAND FG END
5 N
NS1-11MAA-I-FES-0513-3
6 3 NS1-11MAA-I-FES-0513-3
5
D
WA46554 TE122 WA46554 TE122

NOT

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. PREPARATION OF INITIAL FIRING / 22
Title

Checked Sep.-2-2011 M.Okabe VACUUM UP a


a : Oct-20-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

Main DCS

1 1

1 START-UP PHASE SELECT


MGL20
A BOILER IGNITION A A
N N N
D MASTER D D
MC / FWC
1'st BFP START FG BOILER IGNITION PREPARATION FG
PREPARATION OF INITIAL FIRING
6 MASTER COMPLETION
A FG START COMMAND FG END A AUTO COMMAND SYSTEM AUTO
N
NS1-11MAA-I-FES-0513-2
2 3 NS1-11MAA-I-FES-0513-2
N
NS1-11H-I-FWC-6276
1 7 NS1-11H-I-FWC-6277
2 D D 2
MGL22 WA46553 TD102 WA46553 TD102 125127-64-6276 125127-64-6277

VACUUM UP
7 MASTER COMPLETION
NOT NOT
MGL22
BOILER MASTER AUTO
* NS1-11MAA-I-FES-0503
OKB-116 BM04

HP & LP HEATER LEVEL CONTROL


3 3
A AUTO COMMAND SYSTEM AUTO MODE
N
NS1-11MAA-I-FES-0511
9 3 NS1-11MAA-I-FES-0511
D
WA46558 RT233 WA46558 RT233

NOT

CHEMICAL DOSING SYSTEM


HYDRAZINE PUMP
A START COMMAND START
N
D NS1-11QCX-I-FES-3005
10 x NS1-11QCX-I-FES-3005
SH01 SH01

4 4
NOT

CHEMICAL DOSING SYSTEM


A
AMMONIA PUMP N 13
D
A START MGL24
START COMMAND x
N
NS1-11QCX-I-FES-3005
11 NS1-11QCX-I-FES-3005
D SH03
SH03

NOT

5 5
LP BYPASS HYDRAULIC UNIT ON
A START COMMAND SATART
N NS1-11MAA-I-FES-0513
12 1 NS1-11MAA-I-FES-0513
D WA46551 TB065 WA46551 TB065

NOT

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. BOILER IGNITION (1) 23
Title

Checked Sep.-2-2011 M.Okabe a


a : Dec-19-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

Main DCS

1 1

HP&LP HEATER, HYDRAZINE PUMP, A A


13 AMMONIA PUMP, BYPASS OPE N N
D D
MGL23 MC / FWC MC / FWC
BOILER PURGE/HFO LEAK TEST FG IGNITION OF MILL “A” IGNITERS FG
A ON COMMAND ON
N 1 3 A IGNITION COMMAND IGNITION
D NS1-11H-I-FWC-6278 NS1-11H-I-FWC-6279 N 2 2
125127-64-6278 125127-64-6279 D NS1-11HJA-I-FWC-6280 NS1-11HJA-I-FWC-6281
125127-64-6280 125127-64-6281

NOT NOT BM AUTO


2 NS1-11MAA-I-FES-0503
6 2
OKB-116 BM04
CHOOSE ANY
D07 STARTUP MODE
NS1-11MAA-I-FES-0503
OKB-116 UM03

A A
N N
D D
3 MC / FWC 3
MC / FWC
IGNITERS FLOW CONTROL / SH SPRAY CONTROL AUTO FG
IGNITION OF MILL “C” IGNITERS FG
A IGNITION COMMAND IGNITION A ON COMMAND ON
N
NS1-11HJA-I-FWC-6282
3 2 NS1-11HJA-I-FWC-6283
N
NS1-11H-I-FWC-6287
4 3 NS1-11H-I-FWC-6288
D D
125127-64-6282 125127-64-6283 125127-64-6287 125127-64-6288

NOT NOT

4 4

A BOILER IGNITION
N MASTER 5
D COMPLETION
MGL25
BOILER MASTER AUTO

5 5
MAIN STEAM PRESS
≧ 4MPa

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. BOILER IGNITION (2) 24
Title

b
b : July-3-2012 Revised Checked Sep.-2-2011 M.Okabe a
a : Oct-20-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

Main DCS

1 START-UP PHASE SELECT


1 MGL20
1
MC / FWC
MFT RESET

A TURBINE START
N
D MASTER
PREPARATION OF INITIAL FIRING
5 MASTER COMPLETION
TURBINE START FG (ATS)
MGL24 A FG START COMMAND FG END
N
NS1-11MAA-I-FES-0515
1 2 NS1-11MAA-I-FES-0515
D
WA46559 TS101 WA46559 TS114
A TURBINE START
VACUUM UP
2 7 MASTER COMPLETION
N MASTER 2
D COMPLETION
NOT
MGL22
TURBINE MASTER AUTO TURBINE SPEED ≧2950rpm
* NS1-11MAA-I-FES-0503 19 NS1-11MAA-I-FES-0511
OKB-116 TM03 WA46558 RT069

3 3

A SYNCHRONIZE/
N INITIAL LOAD
D
MASTER
SYNCHRONIZATION FG
SYNCHRONIZE/
A FG START COMMAND FG END A INITIAL LOAD
1 START-UP PHASE SELECT N 2 3 N 6
D NS1-11MAA-I-FES-0515 NS1-11MAA-I-FES-0515 D MASTER
WA46559 TS114 WA46559 TS116 COMPLETION MGL27
MGL20

NOT

4 4
GEN CB (52G) CLOSE
6 NS1-11MAA-E-FES-0443
WA48222 GA024

GEN OUTPUT≧ 3%
5 NS1-11MAA-I-FES-0511
WA46558 RT121

5 5

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. TURBINE START / 25
Title

Checked Sep.-2-2011 M.Okabe SYNCHRONIZE / INITIAL LOAD a


a : Oct-20-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

Main DCS

A
N 20
D
IGNITION OF REMAINING 12 IGNITERS FG SELF
1 A START COMMAND COMPLETED 1
A
N NS1-11HJA-I-FWC-6284
12 2 NS1-11HJA-I-FWC-6286
N LOAD UP (1)~(2) D
125127-64-6284 125127-64-6286
1 START-UP PHASE SELECT D MASTER
Unit Master
MGL20 NOT
MWD UPPER LIMIT SET 40%
SYNCHRONIZE/ A SET COMMAND SET
N 1 D08 A
6 INITIAL LOAD MASTER D NS1-11MAA-I-FES-0503 NS1-11MAA-I-FES-0503 N A
COMPLETION OKB-116 UM03 OKB-116 UM03 D N
Unit Master D
MGL22
NOT LOAD SET 75MW (25%L)
Unit Master A SET COMMAND SET
N NS1-11MAA-I-FES-0503
3 D09
NS1-11MAA-I-FES-0503
MWD LOWER LIMIT SET 0% D OKB-116 UM02 OKB-116 UM02
3 MFT NOT
A SET COMMAND SET
2 N NS1-11MAA-I-FES-0503
2 D12
NS1-11MAA-I-FES-0503
2
D OKB-116 UM03 OKB-116 UM03 NOT

NOT

A A
N N
D D
LP HEATER SERVICE IN FG
GEN OUTPUT ≧57MW (19%)
8 NS1-11MAA-I-FES-0511 A FG START COMMAND FG END
WA46558 RT121 N NS1-11MAA-I-FES-0513-3
5 3 NS1-11MAA-I-FES-0513-3
D
WA46554 TE102 WA46554 TE102

3 3
NOT

HP HEATER SERVICE IN FG
A FG START COMMAND FG END
N NS1-11MAA-I-FES-0513-3
6 3 NS1-11MAA-I-FES-0513-3
D
WA46554 TE112 WA46554 TE112 Unit Master
MWD SET ≧90MW (30%) 14
LOAD SET 90MW (30%L)
20 NOT MGL52
A SET COMMAND SET
SELF HOT :30min N
NS1-11MAA-I-FES-0503
13 D10
NS1-11MAA-I-FES-0503
Warm:45min D OKB-116 UM02
OKB-116 UM02
Cold :45min A
A *
N GT N LOAD UP (1)~(2)
D min MC / FWC D A
4 NOT N MASTER 11 4
1'st MILL START D COMPLETION
GEN OUTPUT ≧72MW (24%) MGL28
9 NS1-11MAA-I-FES-0511 A START COMMAND START
WA46558 RT121 N NS1-11HFC-I-FWC-6251
7 51
D NS1-11HFC-I-FWC-6226 Unit Master
125127-64-6251 125127-64-6226
LOAD SET 120MW (40%L)
FW CV TRANSFER A
COMPLETED SET COMMAND SET
NOT 16 NS1-11HFC-I-FWC-6318
N
NS1-11MAA-I-FES-0503
9 D11
NS1-11MAA-I-FES-0503
D
125127-64-6318 OKB-116 UM02 OKB-116 UM02

NOT
A
N
MC / FWC D
5 5
PAFs START FG
A START COMMAND START
N NS1-11HLB-I-FWC-6289
8 9 NS1-11HLB-I-FWC-6290 GEN OUTPUT ≧117MW (40%)
D 125127-64-6289 125127-64-6290 17 NS1-11MAA-I-FES-0511
WA46558 RT121

NOT

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. LOAD UP(1) 27
Title

b
b : July-3-2012 Revised Checked Sep.-2-2011 M.Okabe a
a : Dec-19-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

Main DCS

1 1

1
MGL29

1 START-UP PHASE SELECT


MGL20 A
N LOAD UP (3)~(5) A A
2 D MASTER N N 5 MGL29 2
MC / FWC D MC / FWC D
LOAD UP (1)~(2)
11 MASTER COMPLETION 2'nd MILL START FUEL OIL TO COAL CHANGE
MGL27 A START COMMAND START A FG START COMMAND FG END
N NS1-11HFC-I-FWC-6251
2 52 NS1-11HFC-I-FWC-6226 N NS1-11HJF-I-FWC-6304
4 3 NS1-11HJF-I-FWC-6304
D 125127-64-6251 125127-64-6226
D 125127-64-6304 125127-64-6304

NOT NOT

Unit Master

3 FUEL OIL TO COAL CHANGE 3


A FG START COMMAND FG END
N NS1-11MAA-I-FES-0503
9 * NS1-11MAA-I-FES-0503
D OKB-116 UM02 OKB-116 UM02

NOT

A
N 8 MGL29
D
4 4
2'nd BFP START FG
A FG START COMMAND FG END
N NS1-11MAA-I-FES-0513-2
6 3 NS1-11MAA-I-FES-0513-2
D WA46553 TD112 WA46553 TD112

NOT

5 5

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. LOAD UP(2)-1 28
Title

b
b : July-3-2012 Revised Checked Sep.-2-2011 M.Okabe a
a : Dec-19-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

Main DCS
A
1 LOAD UP (3) ~(5) MASTER N
D
MGL28 Unit Master MWD SET ≧150MW (50%) 13
MC MGL51
MWD UPPER LIMIT SET 50%+α
MILL NUMBER CONTROL A
1 SET COMMAND FG END 1
ON N 1 D09 A A 20 A
D NS1-11MAA-I-FES-0503 NS1-11MAA-I-FES-0503 N N GT N
OKB-116 UM03 OKB-116 UM03 D Unit Master D min MC / FWC D
FUEL OIL TO COAL
5 CHANGE COMPLETION NOT
MWD SET 150MW (50%) 3'rd MILL START
MGL28 A SET COMMAND SET A START COMMAND START
Unit Master N NS1-11MAA-I-FES-0503
3 D12
NS1-11MAA-I-FES-0503
N NS1-11HFC-I-FWC-6252
4 53 NS1-11HFC-I-FWC-6226
D D
8 2'nd BFP START OKB-116 UM02 OKB-116 UM02 125127-64-6252 125127-64-6226
MWD LOWER LIMIT 30%-α
MGL28 A SET COMMAND SET
N 2 D13
D NS1-11MAA-I-FES-0503 NS1-11MAA-I-FES-0503 NOT NOT
OKB-116 UM03 OKB-116 UM03
GEN OUTPUT ≧147MW (49%)
10 NS1-11MAA-I-FES-0511
NOT WA46558 RT121
2 2

20 A
GT N
min D
MWD SET ≧225MW (75%) 14
Unit Master
MGL51
MWD UPPER LIMIT SET 75%+α
A SET COMMAND SET A A 10 A
N 5 D10 N N GT N
D NS1-11MAA-I-FES-0503 NS1-11MAA-I-FES-0503 D D min
OKB-116 UM03 OKB-116 UM03 Unit Master MC / FWC D

MWD SET 225MW (75%) 4'th MILL START


A SET COMMAND SET A START COMMAND START
3 NOT N NS1-11MAA-I-FES-0503
7 D13
NS1-11MAA-I-FES-0503 N NS1-11HFC-I-FWC-6251
9 54 NS1-11HFC-I-FWC-6226
3
Unit Master D OKB-116 UM02 OKB-116 UM02 D 125127-64-6251 125127-64-6226

MWD LOWER LIMIT 30%-α


A SET COMMAND SET NOT NOT
N 6 D13
D NS1-11MAA-I-FES-0503 NS1-11MAA-I-FES-0503
NOT

OKB-116 UM03 OKB-116 UM03 GEN OUTPUT ≧222MW (74%)


11 NS1-11MAA-I-FES-0511
WA46558 RT121

NOT
10
GT
min

4 4
A
N
D Unit Master
OR
3 THREE MILL SELECTED MWD UPPER LIMIT SET 100%
MGL20 A SET COMMAND SET
N NS1-11MAA-I-FES-0503
10 D11
NS1-11MAA-I-FES-0503
D
OKB-116 UM03 OKB-116 UM03
A A LOAD UP (3) ~(5)
N N MASTER
D D COMPLETION
Unit Master
NOT
MWD SET 300MW (100%)
Unit Master A SET COMMAND SET
N NS1-11MAA-I-FES-0503
12 D14
NS1-11MAA-I-FES-0503
MWD LOWER LIMIT 30%-α D OKB-116 UM02 OKB-116 UM02
5 5
A SET COMMAND SET
N 11 D13
D NS1-11MAA-I-FES-0503 NS1-11MAA-I-FES-0503
OKB-116 UM03 OKB-116 UM03 NOT

GEN OUTPUT ≧299MW (99%)


NOT 12 NS1-11MAA-I-FES-0511
WA46558 RT121

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. LOAD UP(2)-2 29
Title

b
b : July-3-2012 Revised Checked Sep.-2-2011 M.Okabe a
a : Dec-19-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

1 1
Main DCS

UNIT MASTER
NS1-11MAA-I-FES-0503
1
OKB-116 UM02

(MMI)

SHUT-DOWN S 1
2 MGL20, MGL51, MGL52, MGL55, MGL56, 2
PHASE Ro MGL57
SHUT-DOWN
2 MASTER GROUP RESET WL
PHASE
MGL20
OR

1 START-UP PHASE
MGL20

(MMI) (MMI) (MMI) (MMI) (MMI)

LOAD DOWN LOAD DOWN DISCONNECTION PULLING OUT EQUIPMENT


3 (1) (2) (ASD) FIRE STOP 3

Target Load Set (75%) Target Load Set (40%) Turbine Stop FG(ADS) Shut Down All Igniters Draft Stop FG
FG
Target Load Set (50%) Target Load Set (25%) Start Up Deaerator
Pegging Steam Control
Ignition of All 24 Igniters Target Load Set (10%) Auto
FG
3'rd Mill Stop Vacuum Break FG
4'th Mill Stop
Coal to Fuel Oil Change Condensate Pump-A
ON Stop Functional
4 2'nd Mill Stop Aux. Steam Pressure 4
Control Valve Inlet Valve
All Mill Stop Close

PAF Stop 1'st BFP Stop FG

LP Heater Service Out Hydrazine Pump Stop


FG
AMMONIA Pump Stop
HP Heater Service Out
FG :MASTER PB
2'nd BFP Stop FG LAMP FLICER AT PERMISSIVE CONDITION ESTABLISH, AFTER PB_ON
EACH MASTER GROUP SEQUENCE START

5 5
WL FLICKER: CONDITION ESTABLISH
WL ON :MASTER START
GL ON :MASTER COMPLETION

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. SHUT-DOWN PHASE BREAK POINT 50
Title

Checked Sep.-2-2011 M.Okabe a


a : Oct-20-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

Main DCS

1 SHUT-DOWN PHASE SELECT LOAD DOWN(1)


MASTER A
N
MGL50 D Unit Master
1 A A 1
MWD UPPER LIMIT SET 300MW (100%+α) N N
A D Unit Master D
N SET COMMAND SET
14 1 D11
MWD SET≧225MW(75%) D NS1-11MAA-I-FES-0503 NS1-11MAA-I-FES-0503
OKB-116 UM03 OKB-116 UM03 MWD SET 225MW (75%)
MGL29 A
N SET COMMAND SET
D NS1-11MAA-I-FES-0503
3 D13
NS1-11MAA-I-FES-0503
NOT OKB-116 UM02 OKB-116 UM02
Unit Master
MWD LOWER LIMIT SET 225MW (30%L-α)
A NOT
N SET COMMAND SET
D NS1-11MAA-I-FES-0503
2 D13
NS1-11MAA-I-FES-0503 GEN OUTPUT ≦228MW (76%)
OKB-116 UM03 OKB-116 UM03 18 NS1-11MAA-I-FES-0511
WA46558 RT121
2 2
NOT
4'th MILL STOP 11
MGL52
A 10 A 30
N GT N GT
MC / FWC D min MC / FWC D min
IGNITION OF ALL 24 IGNITERS FG 4'th MILL STOP
A START COMMAND COMPLETED A STOP COMMAND SYSTEM STOP
N 10 6 N NS1-11HFC-I-FWC-6253
4 33 NS1-11HFC-I-FWC-6253
D NS1-11HJA-I-FWC-6291 NS1-11HJA-I-FWC-6292 D 125127-64-6253 125127-64-6226
125127-64-6291 125127-64-6292

NOT NOT
3 3

NOT

A
13 MWD SET ≧ 150MW (50%) N
D
MGL29

Unit Master
4 4
MWD UPPER LIMIT SET 230MW(75%L+α)
A SET COMMAND SET
N 5 D10 A
D NS1-11MAA-I-FES-0503 NS1-11MAA-I-FES-0503
N
A LOAD DOWN(1)
OKB-116 UM03 OKB-116 UM03 N MASTER 9
D D
Unit Master COMPLETION MGL52
MWD SET 150MW (50%)
NOT
A SET COMMAND SET
N NS1-11MAA-I-FES-0503
8 D12
NS1-11MAA-I-FES-0503
D OKB-116 UM02 OKB-116 UM02

Unit Master
MWD LOWER LIMIT SET 85MW(30%L-α) NOT
5 A SET COMMAND SET 5
N
NS1-11MAA-I-FES-0503
6 D13
NS1-11MAA-I-FES-0503
D
OKB-116 UM03 OKB-116 UM03

GEN OUTPUT ≦153MW (51%)


19 NS1-11MAA-I-FES-0511
NOT WA46558 RT121

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. LOAD DOWN(1) 51
Title

b
b : July-3-2012 Revised Checked Sep.-2-2011 M.Okabe a
a : Oct-20-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

Main DCS
1 SHUT-DOWN PHASE SELECT A LOAD DOWN(2) A
1 N N 1
D MASTER
MGL50 D MC / FWC
3'rd MILL STOP
9 LOAD DOWN(1)
A START COMMAND STOP
MASTER COMPLETION N 1 32
MGL51 D NS1-11HFC-I-FWC-6253 NS1-11HFC-I-FWC-6253
125127-64-6253 125127-64-6226

NOT
14 MWD SET ≧90 MW (30%) 40
GT
MGL27 min Unit Master
A
N
MWD UPPER LIMIT SET 155MW(50%L+α) D
2 11 4th MILL STOP A SET COMMAND SET 2
N
NS1-11MAA-I-FES-0503
2 D09
NS1-11MAA-I-FES-0503
A
MGL52 D N
OKB-116 UM03 OKB-116 UM03 D Unit Master
MWD SET 90MW (40%)
NOT
A SET COMMAND SET
Unit Master N NS1-11MAA-I-FES-0503
4 D11
NS1-11MAA-I-FES-0503
D OKB-116 UM02 OKB-116 UM02
MWD LOWER LIMIT SET 85MW(30%L-α)
A SET COMMAND SET
N 3 D13
D NS1-11MAA-I-FES-0503 NS1-11MAA-I-FES-0503 NOT
OKB-116 UM03 OKB-116 UM03
GEN OUTPUT ≦93MW (31%)
20 NS1-11MAA-I-FES-0511
NOT WA46558 RT121

3 3

COAL TO FUEL OIL


13
CHANGE END
MGL53

MC / FWC
COAL TO FUEL OIL CHANGE ON
A FG START COMMAND FG END
N
NS1-11HJF-I-FWC-6305
8 5 NS1-11HJF-I-FWC-6305
D
125127-64-6305 125127-64-6305
A A
4 N N 12 4
D D
NOT MGL53
1'st BFP STOP FG
MC / FWC
A FG START COMMAND FG END
N NS1-11MAA-I-FES-0513-2
10 3 NS1-11MAA-I-FES-0513-2
2'nd MILL STOP D WA46553 TD122 WA46553 TD122
A STOP COMMAND SYSTEM STOP
N NS1-11HFC-I-FWC-6254
9 51 NS1-11HFC-I-FWC-6253
D 125127-64-6254 125127-64-6226
NOT

NOT

5 DEAERATOR RECIRCULATION PUMP 5


A START COMMAND DRP START
N
NS1-11MAA-I-FES-0513-1
11 1 NS1-11MAA-I-FES-0513-1
D
WA46552 TC031 WA46552 TC031

NOT

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. LOAD DOWN(2)ー1 52
Title

b
b : July-3-2012 Revised Checked Sep.-2-2011 M.Okabe a
a : Dec-19-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

Main DCS
1 1

12 LOAD DOWN (2)-1


Unit Master
MGL52 14 NORMAL STOP 40min
MWD UPPER LIMIT SET 85MW (30%+α) TURBINE COLD 240min
A SET COMMAND SET
SELF
N NS1-11MAA-I-FES-0503
1 D08
NS1-11MAA-I-FES-0503 A 30
D A N GT
OKB-116 UM03 OKB-116 UM03 N min
D D
Unit Master
MWD SET 75MW (25%)
NOT
A SETCOMMAND SET
2 N NS1-11MAA-I-FES-0503
3 D09
NS1-11MAA-I-FES-0503
2
D OKB-116 UM02 OKB-116 UM02 LP HEATER SERVICE OUT FG
Unit Master A FG START COMMAND FG END
N NS1-11MAA-I-FES-0513-3
4 3 NS1-11MAA-I-FES-0513-3
MWD LOWER LIMIT SET 0MW (0%) D A
WA46554 TE107 WA46554 TE107 N
NOT D
A SET COMMAND SET
N NS1-11MAA-I-FES-0503
2 D12
NS1-11MAA-I-FES-0503
D OKB-116 UM03 OKB-116 UM03
NOT

GEN OUTPUT ≦78MW (26%) HP HEATER SERVICE OUT FG


NOT 21 NS1-11MAA-I-FES-0511
WA46558 RT121 A FG START COMMAND FG END
N NS1-11MAA-I-FES-0513-3
5 3 NS1-11MAA-I-FES-0513-3
D WA46554 TE116 WA46554 TE116

3 3
MC
NOT
CALL TO FUEL OIL
13 CHANGE END
MGL52

A A A
N N N
D MC / FWC D MC / FWC BD-SQC D
14
ALL MILL STOP PAFs STOP FG
SELF
A STOP COMMAND SYSTEM STOP A STOP COMMAND STOP
N NS1-11HFC-I-FWC-6254
7 51 NS1-11HFC-I-FWC-6226 N NS1-11HLB-I-FWC-6293
8 3 NS1-11HLB-I-FWC-6294
D 125127-64-6254 125127-64-6226
D 125127-64-6293 125127-64-6294

4 4
NOT NOT

A LOAD DOWN (2)


SH01 APC N MASATER 10
D COMPLETION MGL55
MWD SET 30MW (10%)
A SETCOMMAND SET
N
NS1-11MAA-I-FES-0503
9 D10
NS1-11MAA-I-FES-0503
D
OKB-116 UM02 OKB-116 UM02
5 5

NOT

GEN OUTPUT ≦33MW (11%)


13 NS1-11MAA-I-FES-0511
WA46558 RT121

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. LOAD DOWN(2)-2 53
Title

b
b : July-3-2012 Revised Checked Sep.-2-2011 M.Okabe a
a : Oct-20-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

Main DCS
1 1

2 1 SHUT-DOWN PHASE SELECT 2


MGL50

A A DISCONNECTION
LOAD DOWN (2) DISCONNECTION
10 MASATER COMPLETION
N
MASTER
N MASTER 2
D D COMPLETION
MGL53 MGL56
TURBINE STOP FG (ASD)
A FG START FG END
N NS1-11MAA-I-FES-0515
1 9 NS1-11MAA-I-FES-0515
D WA46559 TS151 WA46559 TS154
GEN OUTPUT ≦51MW (17%)
3 NS1-11MAA-I-FES-0511
WA46558 RT121
3 NOT 3

4 4

5 5

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. PARALLEL OFF 55
Title

Checked Sep.-2-2011 M.Okabe a


a : Oct-20-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

Main DCS
1 1

2 2

3 3

A PULLING OUT A PULLING OUT


1 SHUT-DOWN PHASE SELECT N
FIRE MASTER N MASTER 2
D MC / FWC D COMPLETION
MGL50 MGL57
SHUT DOWN ALL IGNITERS FG
A OFF COMMAND OFF
DISCONNECTION N NS1-11HJA-I-FWC-6295
1 5 NS1-11HJA-I-FWC-6296
10 MASTER COMPLETION
D 125127-64-6295 125127-64-6296
MGL53
NOT
4 4

MC
MFT 5
× NS1-11HHY-I-FWC-1919 9109617-20-5 GT
min
SHEET 15

3
MGL26

5 5

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. BOILER EXTINGUISH 56
Title

Checked Sep.-2-2011 M.Okabe a


a : Dec-19-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H
A B C D E F G H

Main DCS

A AUX. EQUIPMENT
1 SHUT-DOWN PHASE SELECT N
STOP MASTER
D MC / FWC
1 MGL50 1
A DRAFT STOP FG
N
D A FG START COMMAND FG END
PULLING OUT N NS1-11H-I-FWC-6297
1 7 NS1-11H-I-FWC-6298 A
2 MASTER COMPLETION START UP DEA. PEGGING STEAM CONTROL AUTO D 125127-64-6297 125127-64-6298 N
D
MGL56 A AUTO COMMAND AUTO
N NS1-11MAA-I-FES-0511
2 4 NS1-11MAA-I-FES-0511
D
WA46558 RT202 WA46558 RT202 NOT

NOT

2 A 2
N
D

VACUUM BREAK FG AUX. STEAM PRESS. CONTROL VALVE INLET VALVE


A FG START COMMAND FG END A CLOSE COMMAND VALVE CLOSE
N NS1-11MAA-I-FES-0513-3
4 3 NS1-11MAA-I-FES-0513-3 N 5 *
D WA46554 TE132 WA46554 TE132 D

NOT NOT

3 3

A
N
D

2'nd BFP STOP FG CONDENSATE PUMP STOP FG


A FG START COMMAND FG END A FG START COMMAND FG END A EQUIPMENT STOP
N 6 3 N NS1-11MAA-I-FES-0513-1
7 3 NS1-11MAA-I-FES-0513-1 N MASTER
D NS1-11MAA-I-FES-0513-2 NS1-11MAA-I-FES-0513-2 D D
WA46553 TD132 WA46553 TD132 WA46552 TC112 WA46552 TC112 COMPLETION

NOT
NOT

CHEMICAL DOSING SYSTEM


4 4
HYDRAZINE PUMP STOP
A STOP COMMAND STOP
N NS1-11QCX-I-FES-3005
8 x NS1-11QCX-I-FES-3005
ALL BFP STOP D SH01 SH01
10 NS1-11MAA-I-FES-0513-2
WA46553 TD020

NOT

CHEMICAL DOSING SYSTEM


AMMONIA PUMP STOP
A STOP COMMAND STOP
N NS1-11QCX-I-FES-3005
9 x NS1-11QCX-I-FES-3005
D SH03 SH03
5 5

NOT

Date Name

Ref Dwg.No.
WA46567 MGL
Revisions

Drawn Sep.-2-2011 Y.Tanaka


Fuji Electric Systems Co., Ltd. EQUIPMENT STOP 57
Title

b
b : July-3-2012 Revised Checked Sep.-2-2011 M.Okabe a
a : Dec-19-2011 Revised Approved Sep.-2-2011 J.Tsurumine
A B C D E F G H