Professional Documents
Culture Documents
CONTENT
CONTENT
1. GENERAL PROVISIONS
2. TECHNICAL CLASSIFICATION OF FIRE
3. GUARANTEE PERSON'S SAFETY
4. FIRE PREVENTING LAN
5. FIRE WATER SUPPLY
6. FIRE FIGHTING AND FIRE-FIGHTING
7. MANAGEMENT REGULATIONS
8. RESPONSIBILITIES OF ORGANIZATIONS AND INDIVIDUALS
9. ORGANIZATION OF IMPLEMENTATION
Appendix A Additional regulations on fire safety for some specific groups of buildings
Appendix B Classification of building materials by fire characteristics
Appendix C Classification of buildings and rooms according to fire and explosion hazards
Appendix D Regulations on smoke protection for houses and buildings
Appendix E Requirements on fire prevention and fighting distances between buildings and structures
Appendix F Nominal fire resistance limit of some structural members
Appendix G Regulations on the distance to the exits and the width of the exits
Appendix H Some regulations on the limited number of floors (allowable height) and the area of the fire
compartment of the building
Appendix I (for reference) Some drawings illustrating the content of regulations
Preface
QCVN 06:2020/BXD compiled by the Institute of Construction Science and Technology, submitted by the
Department of Science, Technology and Environment, appraised by the Ministry of Science and
Technology, and promulgated by the Ministry of Construction together with Circular 01/2020/ TT-BXD
dated April 6, 2020 of the Minister of Construction.
QCVN 06:2020/BXD replaces QCVN 06:2010/BXD issued together with Circular No. 07/2010/TT-BXD,
dated July 28, 2010 of the Minister of Construction.
2 I 15 3 2
2 LOW 60 2 first
3 LOAD 45 2 first
4 LOW 15 3 2
Fire resistance limits of fire doors and valves in fire prevention parts are specified in Table 2.
The fire resistance limit of parts of the fire-blocking spacer (wall, floor, door and fire-blocking valve) at the
door and fire-blocking valve in the fire-blocking part must comply with the regulations in Table 3.
Class 1 fire-blocking parts must be of fire danger class K0. In separate cases, it is allowed to use fire
hazard class K1 in fire-blocking parts of classes 2 to 4.
Table 2 - Fire resistance limits of fire prevention doors and valves in fire prevention parts
Fire doors and valves in the fire Type of fire prevention door Fire resistance limit, not less
stop unit and valve in the fire stop unit than
2 I 30 2)
3 I 15
Window first 60
2 30
3 15
Diaphragm first I 60
NOTE 1 The fire resistance limit of fire prevention valves is allowed to be taken according to integrity only
(E) if these valves are installed inside channels, wells and pipelines which ensure the required fire
resistance, for both integrity (E) and insulation properties (I).
NOTE 2: The fire resistance limit of the door of the lift well is allowed to be taken not less than E 30.
Table 3 - Fire resistance limits of parts of the buffer compartment at doors and fire prevention
valves in fire prevention parts ngăn
first EI 45 REI 45 EI 30
2 EI 15 REI 15 EI 15
2.5 Stairs and stairwells
2.5.1 Stairs and staircases used for escape are classified into the following types:
NOTE: Appendix I presents some illustrative drawings of different types of stairs and stair chambers.
a) Types of stairs:
- Type 1 - stairs inside the house, located in the stairwell.
- Type 2 – stairs inside the house, open.
- Type 3 – stairs outside the house, open.
NOTE: Open means not placed in the elevator chamber.
b) Types of common stairs:
- L1 – with openings in the outer wall on each floor (open or glazed).
- L2 – is naturally lit through holes in the roof (open or glazed).
c) Types of stairs without smoke:
- N1 – there is an entrance to the elevator from each floor through a smoke-free buffer space made by
suitable natural ventilation solutions. In some cases, elevator chamber N1 has a structure considered
suitable for 3.4.10.
It is allowed to replace the N1 staircase with a staircase with an entrance to the elevator from each floor
passing through the buffer space. Both the spacer and the elevator must have positive air pressure in the
event of a fire. The air supply to the spacer and to the elevator is independent of each other.
- N2 – has positive air pressure (air pressure in the elevator is higher than outside) in the elevator when
there is a fire.
- N3 – there is an entrance to the elevator from each floor through the buffer chamber with positive air
pressure (positive air pressure in the buffer space is regular or when there is a fire).
2.5.2 Fire fighting ladders for fire fighting and rescue are classified into two types as follows:
- P1 - vertical ladder.
- P2 – ladder with inclination not more than 6:1 (not more than 80º).
2.6 House, fire compartment, room
2.6.1 Buildings or parts of buildings are separated separately by fire-blocking walls of type 1 (called fire
compartments) which are grouped according to fire resistance grade, structural fire hazard class and fire
hazard group according to construction. power. It is allowed to divide the fire compartment in buildings
with fire resistance grades IV and V by type 2 fire-blocking walls.
- The fire resistance level of the building and the fire compartment is determined by the fire resistance
limit of its building components.
- The structural fire hazard class of the building and the fire compartment is determined according to the
degree of participation of the construction components in the fire development and the formation of the
dangerous factors of the fire.
- The functional fire hazard group of the building and its parts is determined according to the purpose of
use and the characteristics of the technological processes arranged inside it.
2.6.2 Buildings and fire compartments are classified according to fire resistance grades as shown in
Table 4.
The load-bearing elements of the building include load-bearing walls and columns, braces, connections,
stiffeners, and floor components (beams, beams or slabs) that are involved in ensuring overall stability.
and the shape of the house when there is a fire.
Load-bearing parts that do not contribute to the overall stability of the building must be indicated by the
designer in the building's technical documentation.
No fire resistance limit for vent seals (doors, gates, windows, flaps, skylights, including top doors and
other light-passing parts of the roof sheet) is not specified. except for doors, fire prevention valves in the
fire prevention unit and the cases specified in particular.
When the minimum fire resistance limit of the required member is R 15 (RE 15, REI 15), it is allowed to
use uncoated steel structures regardless of its actual fire resistance limit, except for the cases when the
fire resistance limit of the load-bearing parts of the building according to the test results is less than R 8.
In smoke-free stairwells of type N1 it is allowed to use ladders and stairs with fire resistance limit R 15
and fire danger class K0.
2.6.3 According to structural fire hazard, buildings and fire compartments are classified into 4 levels S0,
S1, S2, S3 as shown in Table 5 called structural fire hazard class of the building.
There is no regulation on fire danger for doors, gates, windows and lids in the building's enclosure, except
for specific cases.
Table 4 - Fire resistance level of the house
DRAW No specified
NOTE 1: In buildings with fire resistance levels I, II, III, the floor and ceiling of the basement and semi-
basement must be made of non-combustible materials and have a fire resistance limit of at least REI 90.
Floors of the 1st floors and the top floor must be made of materials with flammability not lower than Ch1.
NOTE 2: In buildings with fire resistance levels IV, V, the floor of the basement or semi-basement must
be made of materials with a flammability not lower than Ch1 and with a fire resistance limit of not less
than REI 45.
NOTE 3: For houses with 2 or 3 basements (houses of group F1.3 and mixed buildings), the load-
bearing structures in the basement must have a minimum fire resistance limit of R 120.
Note 4 to entry: In rooms where flammable liquids are produced or stored, the floor must be made of
non-combustible materials.
S0 K0 K0 K0 K0 K0
S1 K1 K2 K1 K0 K0
S2 K3 K3 K2 K1 K1
WILL No specified K1 K3
2.6.4 When applied to the actual construction of structures or structural systems where it is impossible to
determine their fire resistance limit or fire hazard class on the basis of standard fire resistance tests or
according to calculations, fire-resistance tests should be carried out on samples similar to the actual
construction of such parts as required by current regulations on fire-resistance testing.
2.6.5 Buildings and building parts (rooms or groups of rooms with related functions) are classified into
groups of fire hazards according to function depending on the characteristics of their use and the level of
threat. to the safety of people in the event of a fire taking into account: age, physical condition, the
possibility of someone sleeping, the group of users according to the main function and the number of
people in that group. Classification of fire hazard according to function is specified in Table 6.
Houses and rooms used for production or storage are classified (A, B, C (C1, C2, C3, C4), D, E)
according to fire and explosion hazards depending on the quantity and nature of the goods. explosion
hazards of substances and materials contained therein, taking into account the characteristics of the
production technology. The classification is specified in Appendix C.
The room production and the time Stockroom, including laboratories and workshops covering an area of
50 m 2 , the rooms do food preparation with cooking with a capacity of 10 KW in the attached Groups F1,
F2, F3 and F4, are placed in Group F5.
2.6.6 In buildings with a fire hazard class according to the specified function, which, in the general case,
is allowed to arrange a group of rooms and rooms with a fire danger level according to other functions, in
addition to complying with the requirements. the general requirements of this regulation, additional
conditions must also be met according to the design standards of specific types of buildings and
corresponding technical equipment.
Table 6 - Grouping of houses based on fire hazard by function
F1 Permanent or temporary housing (including round-the- These rooms in the house are
clock accommodation). usually used both day and
night. This group of people can
F1.1 Kindergartens, kindergartens, specialized homes for the elderly include many different ages and
and disabled (non-apartment homes), hospitals, dormitory physical states. The
blocks of boarding schools and facilities for children, and characteristic of these houses is
homes with special needs. similar point of use. that there are bedrooms.
F3.3 Station.
F4 Schools, workplaces, scientific and design organizations, The rooms in these houses are
regulatory agencies. used for certain times of the day,
inside which are usually fixed
F4.1 High schools, non-school training institutions, professional high groups of people, accustomed to
schools, vocational schools, and homes with similar usage the local conditions, of a definite
characteristics. age and physical condition.
Population, x 1,000 Number of Water flow for outdoor fire fighting for 1 fire, l/s
people simultaneous
fires Building houses with no more than Building houses with 3 floors or
2 floors regardless of fire more regardless of fire resistance
resistance level level
Over 10 to 25 2 ten 15
Over 25 to 50 2 20 25
Over 50 to 100 2 25 35
NOTE 8: Water flow for fire fighting outside the house in a residential area must not be less than the
water flow for fire fighting for the house according to Table 8.
NOTE 9 When implementing regional water supply, the water flow for outdoor fire fighting and the
number of simultaneous fires in each area is taken depending on the number of people living in the area.
NOTE 10: The number of simultaneous fires and the water flow for 1 fire for an area with a population
over 1 million people are subject to the argument of special technical requirements.
NOTE 11: For the system of group (common) pipeline clusters, the number of simultaneous fires is taken
depending on the total number of people in the clusters connected to the pipeline system.
The water flow to recover the amount of fire fighting water according to the group of pipes is determined
by the total amount of water for the residential area (corresponding to the number of simultaneous fires)
for fire fighting according to 5.1.3.3 and 5.1.3.4 .
NOTE 12: The number of simultaneous calculated fires in a residential area must include both
manufacturer and warehouse fires in that residential area. Then the calculated water flow includes the
corresponding fire fighting water flow for those buildings, but not less than the value in Table 7.
NOTE 13: For residential areas with more than 100,000 people and buildings with no more than 2 floors,
the water flow for fire fighting outside the house for 1 fire must be equal to the regulations for residential
areas with 3 buildings. floors and higher.
Table 8 - Water flow rate for outdoor fire fighting of houses in fire hazard group according to
function F1, F2, F3, F4
Kinds of house Water flow for outdoor fire fighting regardless of fire resistance grade
calculated for 1 fire, l/s, according to building volume, 1 000 m 3
2 ten(*) ten 15 15 20
Over 2 to 12 ten 15 15 20 20
Over 12 to 16 - 20 20 25 25
Over 16 - 20 25 25 30
2 ten(*) ten 15 20 25
Over 2 to 12 ten 15 20 25 30
Over 12 to 16 - 20 25 30 35
Over 16 - 25 30 30 35
NOTE: (*) for residential areas of villages and communes (rural), the water flow rate for 1 fire is 5 l/s.
NOTE 14: If the efficiency of the outdoor piping network is not sufficient to transmit the calculated water
flow for fire fighting or when connecting the inlet pipe to the dead pipe network, it is necessary to
consider the installation of tanks, tanks, with a volumetric volume. must ensure water flow for fire fighting
outside the house for 3 hours.
NOTE 15: In a residential area where there is no fire-fighting water pipe, there must be a water tank or
tank to ensure fire fighting for 3 hours.
5.1.2.4 Water flow for outdoor fire fighting for houses divided by fire prevention walls shall be taken
according to the part of the house where the maximum flow is required.
5.1.2.5 Water flow for outdoor fire fighting for houses separated by fire partitions is determined according
to the general volume of the building and according to the highest class of fire and explosion hazard
class.
5.1.2.6 The flow of fire fighting water must be ensured even when the flow for other needs is the largest,
specifically taking into account:
- Drinking water.
- Individual business households.
- Industrial and agricultural production facilities, where drinking water quality requirements or economic
purposes are not suitable for making separate pipes.
- Water treatment station, network of pipes and channels...
- In case technology conditions allow, a part of produced water can be used for fire fighting, then it is
necessary to connect the water pole on the production pipeline network with the water pole on the fire
fighting pipeline network to ensure the flow rate. necessary fire fighting water.
Table 9 - Water flow for outdoor fire fighting for buildings of group F5
The fire Structural House Water flow for outdoor fire fighting for buildings with a width of
resistance fire fire and not more than 60 m, calculated for 1 fire, l/s, according to building
level of hazard explosion volume, 1 000 m 3
the house class of hazard
the house class 3 > 3 to 5 > 5 to 20 > 20 to > 50 to > 200 to > 400 to
50 200 400 600
(first) (2) (3) (4) (5) (6) (7) (8) (9) (ten)
IV S0, S1 D, E ten 15 20 30 40 - -
IV S0, S1 A, B, C 15 20 25 40 60 - -
IV S2, S3 D, E ten 15 20 30 45 - -
IV S2, S3 OLD 15 20 25 40 65 - -
DRAW - D, E ten 15 20 30 55 - -
DRAW - OLD 15 20 25 40 70 - -
5.1.2.7 Fire-fighting water supply systems of establishments (water pipelines, pumping stations, tanks,
fire-fighting water storage tanks) must ensure that the water supply cannot be stopped for more than 10
minutes and the water flow is not reduced by more than 30 minutes. % calculated water flow for 3 days.
5.1.2.8 In case the work is located in an area where there is no fire-fighting water supply infrastructure
outside the house, or there is one but it is not guaranteed according to the provisions of Tables 8, 9 and
10, the instructions of the Police Department shall be followed. competent fire department and fire
department.
5.1.3 Number of simultaneous calculated fires
5.1.3.1 The number of simultaneous calculated fires for an industrial facility must be taken according to
the area of that facility, specifically as follows:
- If the area is up to 150 ha, 1 fire is taken.
- If the area is over 150 ha, 2 fires are taken.
NOTE: The number of simultaneous calculated fires in an open or closed storage area containing wood-
based materials is taken as follows: warehouse area up to 50 ha is taken as 1 fire; the area over 50 ha is
taken as 2 fires.
Table 10 - Water flow for outdoor fire fighting for buildings of group F5
The fire Structural House Fire fighting water flow outside the house for a house with a width
resistance fire fire and of 60 m or more, calculated for 1 fire, l/s, according to the volume
level of hazard explosion of the house, 1 000 m 3
the house class of hazard
the house class 50 > 50 to > 100 > 200 > 300 > 400 > 500 > 600 > 700 to
100 to 200 to 300 to 400 to 500 to 600 to 700 800
I and II S0 A, B, C 20 30 40 50 60 70 80 90 100
I and II S0 D, E ten 15 20 25 30 35 40 45 50
5.1.3.2 When combining the fire-fighting pipeline of a residential area and an industrial facility located
outside the residential area, the number of simultaneously calculated fires is calculated as follows:
- When the area of the industrial facility reaches 150 ha and the population of the residential area reaches
10 thousand people, take as 1 fire (take the larger side water flow); similar to the population from 10 to 25
thousand people take as 2 fires (1 fire for industrial facilities and 1 fire for residential areas).
- When the area of the industrial facility is over 150 hectares and the population is up to 25,000 people,
take as 2 fires (2 fires calculated for industrial establishments area or 2 fires calculated for residential
areas, whichever is the case). larger party required water flow).
- When the population in the area is over 25,000 people, the water flow is determined by the sum of the
larger required flow (calculated for industrial facilities or residential areas) and 50% of the smaller
required flow ( for establishments or residential areas).
5.1.3.3 Fire fighting time must be taken as 3 hours, except for the specific provisions stated below:
- For buildings of fire resistance class I, II with structure and insulation layer made from non-combustible
materials with areas of fire and explosion hazard class D and E, 2 hours are taken.
- For open warehouses containing wood-based materials - not less than 5 hours.
5.1.3.4 Maximum time to recover fire fighting reserve water is not more than:
- For residential areas and industrial establishments with areas under fire and explosion hazard classes
A, B, C, 24 hours is taken.
- For industrial establishments with areas of fire and explosion hazard class D and E, take 36 hours.
- For residential areas and agricultural establishments, it is 72 hours.
Note 1 to entry: For industrial facilities that require water flow for outdoor fire fighting to 20 l/s, it is allowed
to increase the recovery time for fire fighting water as follows:
- For areas of fire hazard class D and E, up to 48 hours is allowed.
- For areas of fire danger class C, up to 36 hours is allowed.
Note 2 to entry: When it is not possible to guarantee the recovery of the fire fighting water in the
prescribed time, it is necessary to provide n times the amount of fire fighting reserve water. The value of n
(n = 1.5; 2.0; 2.5; 3.0 ...) depends on the actual recovery time, t tt , and is calculated by the following
formula:
where: t tt - time recovery of water reserves actual fighting.
t td – time to restore fire-fighting reserve water (according to 5.1.3.4).
5.1.4 Fire safety requirements for pipeline networks and structures built on them
5.1.4.1 When installing 02 or more supply pipelines, a switch valve must be installed between them. In
case of disconnection of 1 supply line or part of it, the fire fighting will still be guaranteed 100%.
5.1.4.2 The fire-fighting water pipeline network must be a loop. It is allowed to make dead-end pipes
when: water supply for fire fighting or daily life - fire fighting when the pipe length is not greater than 200
m, regardless of the required fire fighting water flow.
It is not allowed to connect the pipe network outside the house with the pipe network inside the house and
the building.
NOTE: In residential areas up to 5,000 people and the requirement for water flow for outdoor fire fighting
up to 10 l/s or the number of indoor fire hydrants up to 12, it is allowed to use dead-end network over 200
m in length. if there is a tank, pressure water tower or regulation tank for dead end network, which
contains the entire amount of water for fire fighting.
5.1.4.3 Valves on pipelines of all diameters when operated remotely or automatically shall be electrically
operated valves.
Allows the use of pneumatic, hydraulic or solenoid valves.
When not remotely or automatically controlled, shut-off valves up to 400 mm diameter can be manual
locking, with diameters larger than 400 mm electric or hydraulic; in specific cases, it is permissible to
install valves over 400 mm with manual locking.
In all cases, manual opening and closing shall be permitted.
5.1.4.4 The diameter of the supply pipe and the network after the supply pipe must be calculated on the
following basis:
- According to technical and economic factors.
- Working conditions when interrupting each segment separately.
The diameter of the fire-fighting water pipe outside the house for residential areas and production facilities
should not be less than 100 mm, for rural areas - not less than 75 mm.
5.1.5 Requirements for water storage tanks and tanks for outdoor fire fighting
5.1.5.1 Tanks and tanks for water supply according to function must include for regulation, fire fighting,
emergency and priming water.
5.1.5.2 If taking fire fighting water directly from water sources is not suitable with economic and technical
conditions, in all cases, water storage tanks and tanks must have enough fire fighting water according to
calculation. maths.
5.1.5.3 The volume of fire fighting water in the tank or tank must be calculated to ensure:
- Implement fire fighting water supply from water poles outside the house and other fire fighting systems.
- Provide specialized fire fighting equipment (sprinkler, drencher, ...) without separate tanks.
- Maximum amount of water for domestic use and production during the fire fighting process.
5.1.5.4 Ponds and ponds for fire trucks to absorb water must have an access way and a parking lot of
not less than 12 m x 12 m in size with a surface to ensure the load for fire trucks.
NOTE: When determining the volume of fire fighting water in tanks and tanks, it is allowed to include the
additional loading into the tanks and tanks during the fire fighting time if it has a water supply system that
meets the requirements specified in 5.1.2.7.
5.1.5.5 When supplying water according to 01 supply pipeline, an additional amount of water must be
reserved for fire fighting, determined according to 5.1.5.3.
NOTE: It is allowed not to take into account the amount of additional water for fire fighting when the
length of a supply pipeline is not more than 500 m for residential areas with a population of up to 5 000
people, as well as for objects with high requirements. The demand for water flow for outdoor fire fighting
is not more than 40 l/s.
5.1.5.6 The total number of tanks and tanks for fire fighting in a pipe network must not be less than 2.
Between tanks and tanks in the pipe network, the lowest and highest water levels of fire fighting water
must be the same.
When disconnecting a tank or tank, the amount of water stored for fire fighting in the remaining tanks or
tanks must not be less than 50% of the amount of water required for fire fighting.
5.1.5.7 The storage of fire fighting water in specialized tanks, tanks or open pools is allowed for:
- Residential area up to 5,000 people.
- Buildings, regardless of function, standing separately outside residential areas without a domestic or
production water pipeline system, to provide the necessary amount of water for the external water supply
system.
- Different functional buildings have the required water flow for outdoor fire fighting water supply not
exceeding 10 l/s.
- A house with 1 to 2 floors, regardless of the function, has a construction area not larger than the area of
the fire compartment allowed for that type of house.
5.1.5.8 Fire fighting water volume of tanks, tanks and artificial lakes is determined on the basis of
calculation of water consumption and fire fighting time according to 5.1.2.2 to 5.1.2.6 and 5.1.3.3.
Note 1 to entry: Calculation of the fire fighting water volume of an open artificial lake must take into
account the possibility of water evaporation and freezing. The minimum water level should not be less
than 0.5 m.
NOTE 2: The entrance must be ensured for the fire truck to access the tank, lake, etc.
5.1.5.9 Tanks , tanks, fire hydrants outside the house, natural and artificial fire fighting pools must be
located at positions ensuring the service radius:
- When there is a pump truck is 200 m.
- When there is a mobile pump, it is 100 m to 150 m within the technical operating range of the pump.
- In order to increase the service radius, it is allowed to install dead-end pipes with a length of no more
than 200 m from tanks, tanks and artificial lakes guaranteed according to 5.1.5.8.
- The distance from the point of water intake from an artificial tank, tank or lake to the house with fire
resistance levels III, IV and V or to the open storage containing combustible materials must not be less
than 30 m, to the house of fire resistance level I and II. must not be less than 10 m.
5.1.5.10 When it is not possible to draw fire fighting water directly from a tank, tank or lake by means of a
pump truck or mobile pump, sumps with a volume of 3 m 3 to 5 m 3 must be provided . The diameter of the pipe
connecting the tank, tank or lake to the sumps is taken according to the conditions for calculating the
water flow for outdoor fire fighting, but not less than 200 mm. On the connecting pipe, there must be a
valve box to block the water circulation, the opening and closing of the valve must be done from outside
the box. The end of the connecting pipe at the side of the artificial lake must have a net.
5.1.5.11 Pressure tanks and tanks for fire fighting must be equipped with water level gauges, water level
signaling devices for pumping stations or water distribution stations.
Pressure tanks and tanks of high pressure fire fighting water pipes must be equipped with devices to
ensure automatic disconnection of water to tanks and towers when the fire pump is in operation.
5.1.5.12 Pressure tanks and tanks using pressurized gas, in addition to the operating press, must have
a backup press.
5.2 Indoor fire fighting hydrant system
5.2.1 Houses, public houses as well as administrative - auxiliary buildings of industrial works must install
indoor fire hydrant system, minimum water flow for fire fighting determined according to Table 11, for
manufacturers and warehouses are taken according to Table 12.
When determining the required fire-fighting water flow, it must be based on the height of the solid water
jet and the diameter of the nozzle of the fire-fighting nozzle taken according to Table 13. Then calculate
the simultaneous operation of the hydrant and fire-fighting systems. other.
NOTE: In case the fire hydrant uses equipment with parameters not according to Table 13, it must ensure
the minimum water flow for fire fighting for a single jet and the height of the solid water jet as prescribed.
5.2.2 To calculate pump capacity and water reserve for fire fighting, the number of sprinklers and water
flow for fire fighting in a public house for the part of the building located at an altitude of over 50 m must
be taken as respectively. 4 rays, each beam 2.5 l/s. For buildings of group F5, class A, B, and C with a
volume greater than 50 000 m 3, 4 rays, 5 l/s each, are taken, respectively.
Table 11 - Number of fire sprinklers and minimum water flow for indoor fire hydrant systems
Housing and public buildings Number of fire Minimum flow rate for indoor
sprinklers on 1 fire, l/s, for a single jet
floor
2- Administration house
5.2.3 For manufacturers and warehouses using structures that are susceptible to damage when
subjected to fire, according to Table 12, the minimum water flow to calculate pump capacity and reserve
water The storage for fire fighting determined according to Table 12 must be increased on a case-by-case
basis as follows:
- When using non-fire-protected steel structures in buildings of fire resistance grades III, IV (groups S2,
S3), as well as structures of natural or pressed wood (in this case, treated wood) fire protection), must be
increased by 5 l/s.
- When using combustible materials surrounding the building structure of fire resistance level IV (groups
S2, S3), it must be increased by 5 l/s for houses with volume up to 10 000 m 3 . When a volume greater
than 10 000 m 3 shall be increased by 5 l / s per 100 000 m 3 increase or fraction of 100 000 m 3 increase.
Table 12 - Number of fire sprinklers and minimum water flow for indoor fire fighting for
manufacturers and warehouses
The fire House fire Minimum number of fire sprinklers and water flow, l/s, for 1 spray, for
resistance and indoor fire fighting for manufacturers and warehouses up to 50 m in
level of the explosion height and by volume, 1 000 m 3
house hazard
class From 0.5 to 5 Above 5 to Over 50 to Over 200 to Over 400 to 800
50 200 400
IV, VU D, E ** 2 x 2.5 * * *
Note 1 to entry: “*” water flow and number of jets must be formulated according to a special technical
justification.
Note 2 to entry: For buildings with fire resistance grades and fire hazard classes not listed in Table 12,
the water flow is taken according to a special technical justification.
Note 3 to entry: “**” does not require a fire-extinguishing jet.
5.2.4 The number of fire-fighting sprays for each fire point is taken as 02 for works requiring the number
of sprays greater than 02.
5.2.5 For building parts with different functional areas, the water flow for fire fighting must be calculated
separately for each part according to the provisions of 5.2.1 and 5.2.2. Then, the indoor fire fighting water
flow is calculated according to the following regulations:
- For houses not divided by fire-blocking walls, it must be calculated according to the common volume.
- For houses divided by fire-blocking walls of type 1 or 2, it must be calculated according to the volume of
the part of the house with higher water flow requirements.
When connecting buildings with fire resistance levels I and II by aisles made of non-combustible materials
and installing fire doors, the volume of the building serving the determination of fire fighting water flow is
calculated as specific volume of each house; when there is no fire door, it shall be calculated according to
the total volume and according to the higher fire hazard class.
5.2.6 The hydrostatic pressure in the domestic - fire fighting water system measured at the sanitary -
technical equipment set at the lowest water level should not exceed 0.45 MPa.
The hydrostatic pressure of the separate fire extinguishing system measured at the fire hydrant set at the
lowest water level should not exceed 0.90 MPa.
When calculating, if the pressure in the fire fighting system exceeds 0.45 MPa, a separate fire fighting
system network must be installed.
NOTE When the pressure between the valve and the connection of the fire hydrant is more than 0.4 MPa,
a diaphragm and pressure regulator must be installed to reduce the residual pressure.
Table 13 - Fire fighting water flow depends on the height of the solid water jet and the diameter of
the sprinkler head
Dense Flow of Pressure, MPa, of fire Flow of Pressure, MPa, of Flow of Pressure, MPa , of fire
jet nozzle, hydrant with hose nozzle, fire hydrant with nozzle, hydrant with hose reel
height, l/s reel length, m l/s hose reel length, m l/s length, m
m
(first) (2) (3) (4) (5) (6) (7) (8) (9) (ten) (11) (twelfth) (13)
Fire hydrant DN 50 ( * )
twelfth 2.6 0.202 0.206 0.210 3.7 0.192 0.196 0.210 5.2 0.206 0.223 0.240
twelfth 2.6 0.198 0.199 0.201 3.7 0.180 0.183 0.186 5.2 0.182 0.190 0.199
14 2.8 0.23 0.231 0.233 4.2 0.230 0.233 0.235 5.7 0.218 0.224 0.230
16 3.2 0.31 0.313 0.315 4.6 0.276 0.280 0.284 6.3 0.266 0.273 0.280
18 3.6 0.38 0.383 0.385 5.1 0.338 0.342 0.346 7.0 0.329 0.338 0.348
20 4.0 0.464 0.467 0.470 5.6 0.412 0.424 0.418 7.5 0.372 0.385 0.397
5.2.7 The free pressure of the fire hydrant must ensure the height of the solid water jet necessary for fire
fighting at all times of the day for the highest and most remote areas.
The minimum height and operating radius of the fire-fighting solid water jet must be equal to the height of
the area, from the floor to the highest point of the beam (ceiling), but not less than the following values:
- For houses, public houses, production houses and auxiliary houses of industrial works with a height of
up to 50 m, not less than 6 m.
- For houses over 50m high, not less than 8m.
- For public buildings, production houses and ancillary buildings of industrial works over 50 m high, not
less than 16 m.
NOTE 1 Fire hydrant pressure must be calculated for 10, 15 and 20 m fire hose reel losses.
NOTE 2: To receive a jet of solid water with a flow rate of up to 4 l/s, a DN 50 fire hydrant must be used,
for a larger flow, a DN 65 throat must be used. When the economic-technical argument allows, used fire
hydrant DN 50 for flow over 4 l/s.
5.2.8 The design of the pressure tank for the house must ensure that a jet of solid water can be supplied
at all times with a height of over 4 m at the top floor or the floor immediately below where the tank is
located, and not less than 6 m for the remaining floors. again; then the number of water jets is
guaranteed: 02 rays of 2.5 l/s each in 10 minutes when the calculated number of rays is 02 or more, 01
ray in the remaining cases.
When installing fire hydrants used as sensors for automatic control of fire pumps, pressure water tanks do
not need to be considered.
5.2.9 In case of installing a separate fire hydrant system with automatic fire fighting systems, the volume
of the reserve water tank must ensure the amount of water used in 01 hour, for one fire hydrant. and
other water needs.
When installing a fire hydrant system on automatic fire fighting systems, the working time of the hydrant is
equal to the working time of the automatic fire fighting system.
5.2.10 For buildings of 06 floors or more, when connecting the domestic water and fire fighting systems,
the vertical pipes must be connected around the top. Then, to ensure the water change in the house, it is
necessary to connect the riser ring to one or several vertical drain pipes with a locking valve.
In dry pipe fire suppression systems installed in unheated buildings, shut-off valves should be installed in
areas where freezing is not likely.
5.2.11 The determination of the location and number of vertical pipes and fire hydrants in the house must
ensure the following provisions:
- It is allowed to install double throat on risers in production houses and public houses when the
calculated number of water jets is not less than 03, and in houses not less than 02.
- In houses with a corridor length of up to 10 m when the number of water jets is equal to 02 for each
point, it is allowed to spray 02 jets from a vertical pipe.
- In houses with a corridor length greater than 10 m, as well as manufacturers and public houses with 02
or more calculated water jets for each point, 02 sprays from 02 fire cabinets next to each other must be
arranged. 02 different water throats).
NOTE 1 Fire hydrants must be installed in technical floors, attic floors and technical basements if there
are materials and structures made of combustible materials.
NOTE 2 The number of jets of water from each cabinet should not be more than 2.
5.2.12 Fire hydrants are installed so that the mouthpiece is located at a height of 1.20 m ± 0.15 m above
the floor and placed in fire-fighting cabinets with ventilation holes and sealed. For double fire hydrants, it
is allowed to install 01 hydrant above 01 lower throat, then the lower throat must be installed with a height
of not less than 1.0 m from the floor.
5.2.13 For buildings with a height of 17 floors or more, the indoor fire hydrant system of each zone must
have a waiting throat and a connector of suitable size to connect to the mobile fire fighting vehicle. These
throats must be fitted with a non-return valve and sealed open.
5.2.14 Fire hydrants inside the building must be installed at the entrances to the inside of the corridor
(where there is no danger of water freezing) of the elevator rooms (except for the smoke-free elevators),
at the halls, corridors, aisles and other easily accessible places, then the arrangement must ensure that it
does not interfere with escape activities.
5.2.15 In areas protected by automatic fire fighting systems, it is allowed to install indoor fire hydrants on
pipes DN 65 or larger, after the control valve assembly of the water sprinkler system.
5.2.16 In closed areas that are likely to be frozen, the pipes of the fire hydrant system in the house
behind the pumping station are allowed to be dry pipes.
5.2.17 Valves to block water from dead-end pipelines as well as large shut-off valves from closed steel
pipelines must be arranged to ensure that each section of pipe can only block at most 05 fire hydrants on
the same floor. .
5.2.18 When the house has more than 12 fire hydrants or is equipped with an automatic fire fighting
system, the fire fighting water supply system inside the house, whether designed separately or in
combination, must also be designed with at least two pipes. water supply and must be connected to a ring
network.
6. FIRE FIGHTING AND FIRE-FIGHTING
6.1 Houses and works must ensure fire fighting and rescue by the following solutions: structure, layout -
space, engineering - works and organizational solutions.
These solutions include:
- Arrange the roads for fire trucks, parking lots for fire fighting vehicles and access ways for fire fighting
forces and vehicles, combined with roads and walkways according to the function of the house or
arranged separately.
- Arrange fire fighting ladders outside the house and ensure other necessary means to bring the fire
fighting force and technical fire fighting equipment to the floors and roofs of the houses, including the
arrangement of fire fighting equipment. the elevators have the mode of "transporting the fire fighting force"
(hereinafter collectively referred to as the fire-fighting elevator).
- Arrange fire-fighting water supply pipes, combined with domestic water supply pipes or arranged
separately, and when necessary, arrange water intake throats and pipes to bring water into the house for
fire-fighting forces. hydrants, fire hydrants or other fire fighting water supplies.
- Smoke protection for the passages of the fire service inside the house.
- Equipping the house with means of saving lives for individuals and groups in case of need.
- Arrange and construct fire prevention and fighting works and stations (teams) in accordance with the
number of employees and necessary fire-fighting technical equipment, meeting the fire fighting conditions
on the works or areas within the operating range of these stations (teams) in accordance with current
regulations.
The selection of the above solutions depends on the fire resistance grade, the structural fire hazard class
and the fire hazard group according to the function of the house.
6.2 Roads for fire trucks and parking lots must meet the following requirements:
6.2.1 General requirements
a) Clearance width of road surface for fire trucks must not be less than 3.5 m.
b) The fire truck parking lot must have a clear width to ensure the ability to enter to deploy fire fighting
means suitable to the height and fire hazard group according to the function of the building as specified in
Table 14.
c) It is only allowed to have blocking structures above the road for fire trucks and parking lots if all of the
following requirements are met:
- Clearance height for fire fighting vehicles to pass must not be less than 4.5 m;
- The size of the upper blocking structure (measured along the length of the fire truck road and fire truck
parking lot) should not be more than 10 m;
- If there are two upper blocking structures crossing the road for fire engines or fire truck parking lots, the
clearance between these structures should not be less than 20 m;
- The length of the end of the road for fire trucks or fire trucks that is not blocked by the upper blocking
structures should not be less than 20m; and
- The length of the fire fighting car park is not taken into account the sections with the blocking structure
above.
d) Along the outer wall of the building, at positions facing the fire-fighting car park, it is necessary to
arrange passages through the outer wall to the inside of the house from above (entrance from above) in
accordance with regulations in Clause 1 of this Article. 6.3 to conduct fire fighting and rescue operations.
6.2.2 The arrangement of roads for fire trucks and parking lots must satisfy the following requirements:
6.2.2.1 Buildings of groups F1, F2, F3 and F4 with a height of not more than 15 m do not require a
parking lot for fire fighting vehicles, but there must be a way for fire trucks to approach any point on the
flat view of the building. greater than 60 m.
6.2.2.2 The F1.3 group have a height greater than 15 meters must ensure that all the following
requirements:
- There must be a road for fire engines within a moving range of not more than 18 m from the entrance to
all buffer compartments of the fire-fighting elevator or of the escape staircase with a D65 water supply
waiting throat for fire-fighting forces. professional fire fighting (of dry pipe system).
- There must be a fire truck parking lot to access at least the entire exterior of each block. The fire fighting
car park must be located at a distance not closer than 2 m and not more than 10 m from the outer wall of
the house;
- The design of the fire truck parking lot and the road for the fire truck must meet the requirements listed
in Table 14.
Table 14 - Regulations on size of fire fighting parking lots
Group of fire danger according to the Dimensions of the fire fighting car park corresponding to
function of the house / Criteria for the the height of the house, m
size of the parking lot
15 > 15 and 28 (1) > 28
- The length of the fire car park Taken from Table 15 and Table 16
NOTE: (1) Fire car parking is not required for buildings with the number of occupants per floor, calculated
according to Table G.9 (Annex G), not exceeding 50 people and the distance from the road for The fire
truck to the throat to supply water to the house must not be larger than 18 m.
6.2.2.3 Houses or building sections of groups F1.1, F1.2, F2, F3 and F4 with a height of more than 15 m,
at each position with an entrance from above, a fire-fighting car park must be arranged for access. direct
access to the door panels of the entrance from above. The length of the fire truck parking lot shall be
taken according to Table 15 based on the accessible floor area of the floor with the maximum value of the
accessible floor area. In the case of a house with atrium floors, that value is calculated as follows:
a) For buildings with atrium floors, including basements connected to floors above the ground, the
accessible floor area is equal to the cumulative area of the accessible floor area values of all floors. all
attic floors.
b) For buildings with two or more groups of atrium floors, the accessible floor area must be equal to the
cumulative value of the group of atrium floors with the largest area.
6.2.2.4 For buildings of group F5, there must be a fire car park for fire fighting vehicles. The length of the
fire truck parking lot should be taken according to Table 16, based on the total volume of the building
(excluding the basement).
When production conditions do not require an access road, the road for fire engines is allowed to arrange
a 3.5 m wide roadway for vehicles to run, the roadbed is reinforced with materials to ensure that it can
withstand the load of the fire truck. fire and ensure surface water drainage.
The distance from the edge of the road for fire trucks to the wall of the house must be no more than 5 m
for buildings with a height of less than 12 m, not more than 8 m for buildings with a height of over 12 m to
28 m and not more than 10 m for buildings with a height of over 28 m.
In necessary cases, the distance from the near-house edge of the driveway to the outer wall of the house
and structure is increased to 60 m provided that this house and structure have dead-end roads,
accompanied by a turning area. fire trucks and arrange fire hydrants. In that case, the distance from the
house and the construction to the turning point of the fire truck must not be less than 5 m and not more
than 15 m, and the distance between dead ends must not exceed 100 m.
Note 1 to entry: The width of the building and the structure is taken according to the distance between the
positioning axes.
Note 2 to entry: For lakes used for fire fighting, it is necessary to arrange an entrance with a yard with
dimensions of not less than 12 m in each direction.
Table 15 – Regulations on length of fire-fighting parking lots for houses or building sections of
groups F1.1, F1.2, F2, F3, F4
Accessible floor area, Required length of fire fighting car park, calculated by house perimeter,
m2 m
2 000 1/6 circumference and not less than 15 1/6 circumference and not less than 15
m m
> 2 000 and 4 000 1/4 circumference 1/6 and not less than 15 m
Table 16 – Regulations on the length of fire fighting parking lots for buildings of Group F5
Volume scale, m 3 Required length of fire fighting car park, calculated by house perimeter,
m
The house is not protected by House is protected by sprinkler
a sprinkler system system
28 400 1/6 circumference and not less than 1/6 circumference and not less than 15
15 m m
> 28 400 and 56 800 1/4 circumference 1/6 circumference and not less than 15
m
> 113 600 and 170 400 The whole perimeter 1/2 circumference
> 170 400 and 227 200 The whole perimeter 3/4 circumference
6.2.2.5 Arrangement of roads for fire trucks or fire fighting parking lots for mixed houses must satisfy the
following requirements:
a) When the non-residential building (not in group F1.3) is located only in the lower part of the building,
the height of the building to determine the road requirements for fire trucks or fire trucks must be based
on into the non-residential part of the building.
b) For a mixed-use building, with no part of the building in group F1.3, the required length of the road for
fire trucks or the fire truck parking lot must be taken as the greater of the two values for determining the
base. depend on:
- Total volumetric size of the house sections of group F5; or
- Determined according to Table 15.
c) For a mixed-use building with a building part of group F1.3, the length of the fire truck parking lot must
be calculated according to 6.2.2.3 and must meet the requirements in 6.2.2.
6.2.2.6 For basements, there must be a road for fire engines located within 18 m from the above ground
entrance of all buffer compartments of fire-fighting elevators or of escape stairs with arrangement. D65
water supply hydrant for professional fire force (of dry pipe system).
6.2.3 Fire truck parking must be arranged so that the horizontal measurement distance from the nearest
edge of the parking lot to the middle point of the entrance from above is not closer than 2 m and not more
than 10 m. .
6.2.4 The surface of the fire truck parking lot must be level. If lying on an incline, the slope should not
exceed 1:15. The slope of the road for fire engines should not exceed 1:8.3.
6.2.5 If the length of the road for fire trucks or the dead-end fire truck parking lot is more than 46 m, at
the end of the dead end, there must be a turning area designed according to the provisions of 6.4.
6.2.6 A public road can be used as a fire truck parking lot, if its location is in accordance with the
regulations on distance to the overhead entrance in 6.2.3.
6.2.7 Roads for fire trucks and parking lots must be kept clear at all times. The space between the fire
truck parking lot and the entrance from above must not be obstructed by trees or other fixed objects.
6.2.8 All corners of fire truck parking lots and fire truck roads shall be marked with the exception of public
roads used as fire truck parking or fire truck roads. The marking must be done with reflective paint strips,
ensuring visibility at night and must be arranged on both sides of the road for fire trucks or fire fighting
parking lots with a distance of not more than 5 m.
At the beginning and the end of the road for fire trucks or the parking lot for fire fighting vehicles, there
must be a signboard with white background and red letters with the letter height not less than 50 mm. The
height from the ground to the lowest point of the sign must be between 1.0 m and 1.5 m. Signboards must
be visible at night and must not be located more than 3 m from the road for fire engines or parking lots. All
sections of the fire truck road or fire truck parking lot should not be more than 15 meters from the nearest
sign.
6.2.9 The road surface for fire trucks and fire fighting parking lots must be able to withstand the load of
fire trucks according to design requirements and suitable with the type of vehicles of the Fire and Rescue
Police agency where the work is to be built. .
6.3 The entrance from above to serve fire fighting and rescue must comply with the following regulations:
6.3.1 The entrance from above must ensure ventilation, unobstructed at all times during the time the
house is in use. Entrance from above can be through openings in exterior walls, windows, balcony doors,
glazed wall panels and door panels that can be opened from inside and outside. Do not arrange furniture
or any objects that can obstruct within 1 m of the floor inside the house from the entrances from above.
6.3.2 Entrance from above shall be located facing a usable space. Not to be located in warehouse or
machine rooms, escape stairs, smoke-free lobby, fire elevator lobby or spaces leading to only one dead-
end point.
6.3.3 The outside of the door panels of the upper entrance shall be marked with a red or yellow
equilateral triangle with a side not less than 150 mm, the top of which can be upward or downward. On
the inside, there must be the inscription "UPPERIOR ENTRY - DO NOT INTEREST" with a letter height of
not less than 25 mm.
6.3.4 Entrances from above shall have a width of not less than 850 mm, a height of not less than 1 000
mm, the lower edge of the entrance being not more than 1 100 mm from the inner floor and the upper
edge above the floor. inside is not less than 1 800 m.
6.3.5 The number and location of the entrance from above for each fire compartment of the building or
part of the building not belonging to group F1.3 must ensure the following provisions:
6.3.5.1 For buildings of group F1.1, F1.2, F2, F3, F4 and F5, the number of entrances from above must
be calculated based on the length of the fire fighting car park. For each sufficient or insufficient 20 m
length of the fire car park, there must be an entrance from above.
6.3.5.2 The entrance from above must be arranged far apart, along the edge of the house. The furthest
distance measured along the outer wall between the centers of two consecutive overhead entrances
served by a fire car park shall not exceed 20 m. The entrance from above must be distributed so that
there must be at least 1 entrance from above on each 20 m length of the fire car park, except for the parts
of 1-storey buildings not in group F5.
6.3.5.3 For houses of groups F1.1, F1.2, F2, F3 and F4 with a height from over 10 m to 50 m, there must
be an entrance from above on all floors except the 1st floor and must be located on the ground floor.
opposite the fire truck parking lot.
6.3.5.4 For Group F5 buildings, overhead entrances must be arranged above a fire car park, up to a
height of 50 m.
6.3.5.5 The requirement for entrance from above does not apply to F1.3 grouphouses, including ancillary
areas (eg Gym, club rooms, etc.) exclusively for residents. population of the building) in the group house
F1.3.
6.4 The design of the parking lot must comply with one of the following regulations:
- An equilateral triangle has a side not less than 7 m, one vertex is at a dead end, and two vertices are
symmetrically located on both sides of the road.
- A square with a side not less than 12 m.
- Round shape, diameter not less than 10 m.
- A rectangle perpendicular to the dead-end road, balanced on both sides of the road, with dimensions
not less than 5 mx 20 m.
NOTE: The above regulations are the minimum threshold, the management agency on fire prevention
and fighting can issue specific regulations based on the technical requirements of fire fighting equipment
in each locality.
6.5 For narrow roads with only one lane for traffic, at least every 100 m, an extension of at least 7 m and
8 m long must be designed so that fire engines and other vehicles can easily avoid each other.
6.6 For buildings with a height greater than or equal to 10 m from the roof edge or the top edge of the
outer wall (retaining wall), there must be direct exits to the roof from the stairwells or through the attic, or
Follow the stairs of type 3, or follow the fire ladder outside the house.
The number of exits to the roof and their arrangement must be based on the fire hazard according to the
function and dimensions of the building, but not less than one exit:
- For each distance less than or equal to 100 m of the length of the house with the attic.
- For each area less than or equal to 1 000 m 2 roofs of houses without attic floors of groups F1, F2, F3
and F4.
- For every 200 m perimeter of the house of group F5, follow the fire ladders. Allow no layout:
- Fire fighting ladders at the main side of the house if the width of the house is not more than 150 m and
in front of the house there is a fire-fighting water supply pipeline.
- Exits to the roofs of single-storey buildings with a roof area not larger than 100 m 2 .
6.7 In the attic floors of buildings, except for buildings of group F1.4, there must be exits to the roof via
fixed ladders and doors, hatches or windows with dimensions not less than 0.6 mx 0, 8 m.
The exits to the roof or to the attic from the stair rooms must be arranged according to the ladders with
the stairs in front of the exit, through the fire doors of type 2, the size is not less than 0.75 m x 1.5 m. The
above ladders and mats can be made of steel
but must have a slope (angle of inclination) not greater than 2 : 1 (63.5º) and a width not less than 0.7 m.
In buildings of groups F1, F2, F3 and F4 up to 15 m high, it is allowed to arrange exits to the attic floor or
to the roof from stairwells through type 2 fire doors with dimensions of 0.6 m x 0, 8 m by permanently
mounted steel ladders.
6.8 In technical floors, including technical basements and technical attic floors, the clearance height of
walkways must not be less than 1.8 m; in attic floors along the entire house - not less than 1.6 m. The
width of these passages must be not less than 1.2 m. In separate sections with a length of not more than
2 m, it is allowed to reduce the height of the walkway to 1.2 m, and the minimum width to be 0.9 m.
6.9 In buildings with attic floors, there must be hatches in the structures that cover the cavities of the
attic.
6.10 At points where the height difference of the roof is greater than 1.0 m (including the height
difference to raise the doors for light and ventilation), there must be a fire ladder.
In the area where the roof height difference is more than 10 m, if each roof section has an area of more
than 100 m 2 with its own door to the roof satisfying the requirements of 6.6, or the lower part of the roof,
determined according 6.6 does not exceed 10 m, then no fire ladder is allowed.
6.11 Fire ladders of class P1 must be used to reach heights of up to 20 m and at places where the height
difference of the roof is from 1.0 m to 20 m. Fire ladders of type P2 must be used to reach heights greater
than 20 m and at places with a height difference of more than 20 m.
Fire ladders must be made of non-combustible materials, placed in a conspicuous place and not less than
1.0 m away from windows. Ladder width 0.7 m. For ladders of type P1, from a height of 10 m or more,
there must be a coverage arc with a radius of 0.35 m, the center of which is 0.45 m from the ladder. The
arcs must be placed 0.7 m apart, in the place of the roof, the mat must be placed to have a railing at least
0.6 m high. For ladder P2, there must be handrails and landing mats placed no more than 8 m apart.
6.12 Between the stairs and between the handrails of the ladder, there must be a gap with a clear width
projected on the ground not less than 100 mm.
6.13 Each fire compartment of buildings has a height of more than 28 m (greater than 50 m for buildings
of group F1.3), or a house with a depth of the bottom basement floor (taking into account the height of the
emergency exits). outside) greater than 9 m must have at least one fire lift.
NOTE: Other technical requirements such as power supply, control system, signal transmission,
communication, equipment for fire protection, etc. must comply with specific technical standards selected
for elevators. fire fighting.
The arrangement and installation of fire fighting elevators must ensure the following basic regulations:
- The elevators mainly for transporting goods are not allowed to be used as fire-fighting elevators.
- Under normal conditions, fire elevators are still used to carry people. Fire elevators can be arranged with
a separate elevator lobby or in a common lobby with passenger elevators and combined by a group
automatic control system.
- Having a calculated number sufficient so that the distance from the location of those elevators to any
point on the floor plan it serves does not exceed 60 m.
- If there is only one fire-fighting elevator, that elevator must reach at least all floors adjacent to the
burning floor of the building.
- If there are many fire-fighting elevators arranged in one well, the elevators can serve different areas of
the building, provided that the service area on each elevator must be clearly indicated.
- In all cases, the form of service of the fire fighting elevators must be the same and common, for
example, the elevators only serve odd floors or even floors or all floors.
- If there are evacuation floors, each floor must be serviced by at least one fire elevator.
- In the normal operation mode, the doors of the fire fighting elevators must not open to those evacuation
floors, and the landing doors of the wells at those evacuation floors must be locked regularly and only be
automatically unlocked when switch to fire service service mode.
- In case of fire, the fire fighting elevators must ensure that the firefighter:
+ is the only person who has the right to control and operate to access the fire with his equipment easily,
familiarly, safely and quickly.
+ be safe when using against the effects of fire and smoke by appropriate solutions, especially when
getting out of those lifts.
+ have clear and safe passage for access to such lifts as well as to the floors served by such lifts.
+ do not have to move more than two floors to reach any fire-prone floors of the building.
- Protected in separate elevator wells (not shared with other types of elevators) and in each such elevator
well, there are only 3 fire-fighting elevators arranged. The structure surrounding the lift well must have a
fire resistance rating of not less than REI 120.
- Fire elevator lobby is a buffer compartment ensuring all of the following regulations:
+ has an area not less than 4 m 2 .
+ When combined with the halls of the staircase chamber without smoke, the area is not less than 6 m 2 .
+ is surrounded by fire partitions of type 1.
+ There is a D65 water supply waiting throat installed for professional firefighting forces.
- The arrangement of fire fighting elevators must be able to estimate the travel path of the professional
fire fighting team and ensure that the fire fighting team can access all rooms on all floors of the building.
- The carrying capacity of fire fighting lifts must not be less than 630 kg for apartment buildings of group
F1.3 and not less than 1,000 kg for manufacturers and other public buildings.
- The moving speed of the fire-fighting elevator must not be less than H /60 (m/s). Where H is the lifting
height (m).
- The covering structure of the fire-fighting elevator cabin must be made of non-combustible or weakly
combustible materials.
6.14 In buildings with roof slope up to 12 %, the height to the roof rim or the top edge of the outer wall
(retaining wall) is more than 10 m, as well as in the buildings with the roof slope greater than 12 % and
the height to the frill Roofs larger than 7m must have railings, handrails on the roof in accordance with
current standards. The railings and handrails of this type must also be arranged for flat roofs, balconies,
loggias, external corridors, external stairs of open type, stairs and stair mats regardless of the height of
the building. .
6.15 Fire-fighting water supply systems for houses must ensure that fire-fighting forces and means can
access and use them at all times.
6.16 The supply of fire-fighting water as well as the equipment and arrangement of other specialized fire-
fighting means and tools for houses and works must comply with the basic provisions in Part 5 of this
regulation and of technical standards. related art.
6.17 Fire control room.
a) Houses and public works over 10 stories high; houses with 2 to 3 basements; public facilities with a
high concentration of people (theaters, cinemas, bars and buildings of similar use, with the number of
people per floor, calculated according to Table G.9 (Appendix G), in excess of 50 people); garage (room
for cars, motorcycles, bicycles), manufacturers, warehouse area of over 18 000 m 2 have rooms directly
control the fire and have staff with expertise often directly in the control room .
b) The fire fighting control room must:
- Having an area sufficient to arrange equipment according to the fire prevention requirements of the
house but not less than 6 m 2 .
- There are two entrances: one with the empty space outside the house and the other with the main
corridor for escape.
- Separated from other parts of the building by fire-blocking parts of class 1.
- Having installed information equipment and the focal point of the fire alarm system to contact all areas of
the house.
- There is a board to monitor and control fire fighting equipment, smoke control equipment and a floor
plan to arrange the fire prevention and fighting equipment of the house.
6.18 All indoor basements with 2 to 3 basements, must be equipped with a two-way emergency
communication system between the fire control room and the following areas:
- The equipment rooms related to the fire fighting system, especially the pump room of the sprinkler
system, the pump room supplying water to the riser system, the switching room, the generator room and
the elevator machine room.
- All rooms are equipped with control equipment for anti-smoke control system.
- Fire elevators.
- All shelters.
- Control rooms for ventilation systems.
7. MANAGEMENT REGULATIONS
7.1 This regulation stipulates the technical requirements and management requirements that must be
complied with in the new construction, renovation, repair or change of functions of the house, which is a
tool of the housing management agency. about fire prevention and fighting and construction investment
activities.
7.2 Transition conditions
- Construction design dossiers which are appraised and approved on fire prevention and fighting by
competent state management agencies before this Regulation takes effect shall continue to be
implemented according to approved design documents.
- Construction design documents approved after the effective date of this Regulation must comply with
the provisions of this Regulation;
8. RESPONSIBILITIES OF ORGANIZATIONS AND INDIVIDUALS
8.1 All organizations and individuals when participating in activities related to new construction,
renovation, repair or change of functions of houses and works, including formulation, appraisal, approval,
implementation organization , management and construction of national standards and local regulations
related to apartment buildings must comply with the provisions of this regulation.
8.2 State management agencies in charge of fire prevention and fighting and construction at the central
and local levels are responsible for inspecting the compliance with this Regulation in the formulation,
appraisal, approval and construction management of houses. and works in the area according to the
provisions of law.
8.3 The local state management agencies in charge of fire prevention and fighting and construction are
responsible for coordinating in promulgating regulations related to technical parameters for the design
and construction of roads for fire engines and fire trucks. fire-fighting vehicle parking in accordance with
the characteristics of the local fire-fighting vehicle.
8.4 During the implementation of this Regulation, if there are any problems, all comments should be sent
to the Department of Science, Technology and Environment (Ministry of Construction) for guidance and
handling.
9. ORGANIZATION OF IMPLEMENTATION
9.1 The Ministry of Construction is responsible for organizing the dissemination and application of this
regulation to relevant entities.
9.2 When legal documents, referenced documents or instructions specified in this Technical Regulation
are changed, supplemented or replaced, the new documents shall apply.