Professional Documents
Culture Documents
technical information
breakers
Discrimination (Selectivity)
IEC/EN 60947-2
E002487-37.eps
What is discrimination?
It is the coordination of automatic cut-off devices for a fault that occurs at any point in
the network to be eliminated by the upstream circuit breaker, the circuit breaker that
is immediately upstream of the fault and by that circuit breaker alone!
Continuity of service
DB421201.eps
D1
Discrimination is an essential element that must be taken into account as early as in
the design of a low voltage installation to enable continuity of the electricity service.
Discrimination means that only the part with the fault is disconnected. It enables:
bb continuity of supply for adjacent circuits,
Fault
bb localization of the faulty circuit.
D1 and D2 in series.
For some installations or installation parts:
bb operating theatre in clinics and hospitals,
bb marine,
bb safety equipment,
bb production site.
The requirements for continuous electricity often make it necessary to verify the
discrimination between upstream and downstream protection devices.
If there is a total lack of discrimination, it will be necessary to try to achieve partial
discrimination. Likewise, if there is a limit to the level of discrimination and this
proves satisfactory in the majority of cases, it can still be attempted to make it total.
Of course, any modification must be made while observing the following main
parameters:
bb protection of personnel,
bb are the thermal stresses I2t of the cables always taken into account?
bb are the breaking capacities of the devices higher than the prospective Isc?
Finally, when it is not possible to achieve discrimination and it is essential for the
correct operation of the installation, the installation of uninterruptible power supplies
(UPS) must be considered. Generator units, inverters, etc. are then used.
There are several types of discrimination that can be used separately or together.
For protection against overcurrent, this generally concerns current discrimination
and time discrimination.
The principle is as follows.
6
Complementary Coordination between circuit
technical information
breakers
Discrimination (Selectivity)
D1
Discrimination involves ensuring coordination between two circuit breakers in series,
so that, in the event of a fault, only one circuit breaker, located immediately upstream
of the fault, trips. A discrimination current Is is defined so that:
bb Ifault < Is: only D2 eliminates the fault, discrimination is ensured,
bb Ifault > Is: both circuit breakers may trip, discrimination is not ensured.
D2
Slight overcurrent or overload
Under the effect of an abnormal inrush current, for example an increase in the
resistive torque of a motor, the current going through the circuit is higher than the
rated current. These currents may damage the installation (risk of an electrical fire).
Devices to protect against overcurrent can be characterized by their operating
curves as a function of prospective current Ip:
bb the operating curve is time-based when the breaking time is greater than 50 ms
(curve t = f (Ip). Discrimination is achieved if the ln upstream / In downstream
operation threshold ratio is > 1.3 and if the current offset of the magnetic curves is
0 D2 Only D2 trips Is D1 and D2 trip I fault observed.
100
10
t (s)
0,1 Motor
curve
0,01
0,01 0,1 1 10
The greater the difference between the ratings of the upstream and downstream
circuit breakers, the more “extensive” the discrimination.
Short circuit
For example when there is contact between two phases we are faced with a full
insulation fault which risks damaging the installation.
The function that makes it possible to protect against this type of fault is magnetic
protection.
To ensure discrimination, we must maintain a ratio between the upstream and
downstream protection devices. This is energy discrimination.
bb Energy: when the intervention time is less than 50 ms and more particularly less
than the time of one half wave (10 ms) of current with limiting circuit breakers.
D1
10 ms
1000000
D2
Limited energy (A2s)
100000
10000
1000
100
10
0,01 0,1 Is 1 10 100
7
Complementary Coordination between circuit
technical information
breakers
Discrimination (Selectivity)
Time discrimination
DB124205.eps
The principle is based on the time difference (Δt) of the upstream magnetic curve.
PARTIAL DISCRIMINATION
TOTAL DISCRIMINATION
only the downstream circuit
Ip
breaker trips
Continuity of service Is
8
Complementary Coordination between circuit
technical information
breakers
Discrimination (Selectivity)
Example
bb Let us take the example of a single phase network where we have a 32 A curve D
D1 circuit breaker in series with a 10 A curve D circuit breaker:
32 A 6 mm2 vv the 32 A circuit breaker protects the 62 cables and the 10 A circuit breaker protects
the 1.52 cables. This combination allows discrimination, but up to what threshold?
vv if current discrimination is considered (t = f (Ip)) it can be seen that the tripping
D2
10 A curve of the downstream circuit breaker is well below the non-tripping curve of the
upstream circuit breaker,
1.5 mm2
vv furthermore, each circuit breaker is well below the maximum stress permitted by
the cables.
10000
DB403510.eps
1000 Cable 62
MCB 32 A
Cable 1.52
MCB 10 A
100
t (s)
10
0,1
1 10 100 1000 10000
Prospective current (kA rms)
Cable 62
Cable 1.52
MCB 32 A
1000000
MCB 10 A
Limited energy (A2s)
100000
10 ms
10000
1000
100
0.001 0.01 0.1 1 10 100
Prospective
current (kA rms)
I fault
Normal Discrimination Is Opening of Breaking capacity
operation both circuit of the downstream
breakers circuit breaker
9
Complementary Coordination between circuit
technical information
breakers
Discrimination (Selectivity)
10
Complementary Coordination between circuit
technical information
breakers
Discrimination (Selectivity)
Circuit breaker with vigi module (Add-On Residual Current Device - RCD):
DB421192.eps
When circuit breakers are equipped with vigi module, discrimination tables are valid
for short-circuit. To ensure discrimination in case of earth fault, upstream and
D1 downstream vigi modules shall satisfy the following conditions:
RCD bb the sensitivity of the upstream residual current device must be at least equal to
three times the sensitivity of the downstream residual current device (IΔn D1 u 3 x
IΔn D2),
bb the upstream residual current device must be:
vv of the selective (S) type (or setting) if the downstream residual current device is an
instantaneous type,
D2 vv of the delayed (R) type (or setting) if the downstream residual current device is a
RCD selective type.
The minimum non-tripping time of the upstream device will therefore be greater than
the maximum tripping time of the downstream device for all current values (Δt (D1) >
Δt (D2)).
11
TOOLS
Ecodial