Professional Documents
Culture Documents
TIM NOONAN*
ESB International
IRELAND
Some of the transformer acceptance tests performed at • Oil dissolved gas analysis.
the transformer manufacturer’s works may act as
fingerprint tests, i.e. partial discharge, winding • Oil furan analysis.
resistance, tan delta or % power factor and capacitance
measurements. • Paper sample degree of polymerisation
measurements [9].
Fingerprint tests performed by ESBI include the
following: • Paper sample moisture content test [10].
• Oil screen tests (breakdown voltage, moisture • Interwinding and winding to ground % power
content, neutralisation value, colour, resistivity, and factor measurements.
relative permittivity).
• Interwinding and winding to ground capacitance
• Oil dissolved gas analysis [1] [2]. measurements.
• Interwinding and winding to ground % power • Bushing main insulation and test tap insulation to
factor measurements [3]. ground % power factor and capacitance
measurements.
• Interwinding and winding to ground capacitance
measurements [3]. • Winding resistance.
• Bushing main insulation and test tap insulation to • Magnetising current measurements.
ground % power factor and capacitance
measurements [3]. • Leakage reactance measurements.
2 .35 .22 .27 .23 .25 .26 • No other mechanical deformation in the
transformer.
Table III: % PF test values on HV bushing • Paper insulation was not involved in the fault.
insulation.
These results indicated the transformer could easily be
% PF repaired. The transformer was sent to a workshop,
Unit where it was untanked. The fault found was an open
R S T N circuit at a burnt connector to the LV r phase bushing.
1 1.91 2.8 3.51 .6 The transformer was repaired. Figure 1 shows the FRA
scans indicating the fault at the bushing end of the
2 .72 .74 .73 .70 winding. (Figure 3 shows FRA scans when the fault is
at the neutral end of the winding.) Figure 2 shows the
burnt connector at the LV winding r phase bushing.
The oil was also wet in Unit l i.e. moisture 30ppm and
breakdown voltage of 59kV / 2.5mm were recorded.
MC/TN5234.REP
DP % PF / Capacitance (pF)
CH CL CT CHL CLT CHT
PREFAULT 662/601 .27/ .33/ .25/ .20/ .22/ -/
4537 1527 13874 8601 13509 74
POSTFAULT 781/893 .76/ .99/ .36/ .29/ .31/ -/
4567 1525 13925 8634 13562 75
Magnetising Currents (mA) Furan Analysis
HV Winding LV Winding
1 Furaldehyde 5 Methyl-2-Furfural
R-N S-N T-N r-n s-n t-n
PREFAULT 60 50 63.5 73 16
POSTFAULT 55 41.8 57.3 .048 319 439 33 4
HV Winding Resistance (m5) LV Winding Resistance (m5)
R–N S–N T-N r–n s–n t-n
PREFAULT 395 391 392 36 36 36
POSTFAULT 395 391 392 0 36.2 36.3
Frequency Response Analysis Leakage Reactance Measurements
Nameplate 22%
R–N S–N T-N
PREFAULT No defect indicated.
POSTFAULT Open circuit on LV winding r phase near the 1630 21.9 27.5
phase bushing end of the winding.
WINDING)
6
4
2
Figure 3: Open circuit on T phase near neutral end of 0
winding 0 2
R V M data
4 6
Medium and large power transformers are high capital [6] Bognar, Kalocsai, Csepes, Nemeth, Schmidt:
cost and critical plant items in the generation, “Diagnostic tests of high voltage oil-paper
transmission and distribution of electrical power. To insulating systems (in particular transformer
ensure continued serviceability, a life management insulation) using DC dielectromectrics” CIGRE,
policy involving on site condition assessment testing is 1990 Session, paper 15/33-08
essential. This ensures:
[7] Dick, EP and Erven, CC: “Transformer Diagnostic
• The high quality of equipment being put into Testing by Frequency Response Analysis”, IEE
service. Trans, Vol. PAS-97, No. 6, PP.2144-2153,
November 1978.
• Continued effective monitoring of equipment in
service. [8] Noonan, TJ and Lapworth JA: “Mechanical
Condition Assessment of Power Transformers
• Present condition trending while in service. using Frequency Response Analysis”, Doble Client
Conference Proceedings, April 1995.
• Identification of required corrective maintenance
tasks for continued serviceability. [9] IEC Publication 450: “Measurement of the
Average Visiometric Degree of Polymerisation of
• Speedy repair and return of equipment to service New and Aged Electrical Papers”, 1974.
after fault.
[10] ASTM Designation: D3277: “Standard Test
• Generation of data to enable refurbishment and life Method for Moisture Content of Oil-Impregnated
extension decisions to be implemented. Cellulose Insulation”, 1992.
5. REFERENCES