You are on page 1of 16

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/3259204

Asset-Management of Transformers Based on Condition Monitoring and


Standard Diagnosis [Feature Article]

Article  in  IEEE Electrical Insulation Magazine · August 2008


DOI: 10.1109/MEI.2008.4581371 · Source: IEEE Xplore

CITATIONS READS
147 3,133

2 authors, including:

Ernst Gockenbach
Leibniz Universität Hannover
280 PUBLICATIONS   4,016 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Lightning Impulse evaluation View project

power transformer condition evaluation View project

All content following this page was uploaded by Ernst Gockenbach on 02 April 2016.

The user has requested enhancement of the downloaded file.


F E A T U R E A R T I C L E

Asset-Management of Transformers
Based on Condition Monitoring and
Standard Diagnosis
Key Words: asset management, condition monitoring, diagnosis, international test standard,
transformerdynamics, space environment, printed circuit boards, homocharge, heterocharge

Introduction Xiang Zhang and Ernst Gockenbach


U nder present deregulation policies of electric power sys-
tems, every utility is trying to cut its costs, while being
acutely aware that the prevention of accidental loss is more im-
Institute of Electric Power Systems, Department of
High Voltage Engineering, Schering Institut,
portant than ever; for example, the capital loss of an accidental Leibniz Universität Hannover, Germany
outage is often counted in millions of dollars for transformers. To
meet the growing demand of the electric power grid and to main-
tain system reliability, significant changes may be required in the
way a utility operates and cares for its transformers. It is usually
not economically feasible to subject every aging transformer to The important aim of the
rigorous inspection and extensive testing. A promising industry standardization is to develop the
strategy for life-cycle management is to set monitoring priorities
and to provide strategic maintenances for all transformers.
multiple diagnostic models that
This is the reason why monitoring, analyzing, or diagnostic combine results from the different
systems have become an essential part of the supervision of tests and give an overall assessment
transformers. With the help of measuring techniques, technical
diagnostics permit a standard evaluation, which goes beyond of reliability and maintenance for
summarizing the obvious signs of defects. Different monitoring transformers.
methods that cover a multiplicity of physical effects are used;
from the measurement of the parameters; to the analysis of data
and diagnosis of failure; and lastly to electrical, thermal, mechani-
cal, and optical techniques. Therefore, the aims of the diagnostic
methods are the evaluation of the operating conditions, finding
the causes of aging, recommending measures to improve quality, formers. The risk-based FMEA process (failure mode and effect
and the assessment of lifetime. analysis) uses expert systems to identify and prioritize the highest
With these technical diagnostic methods it is possible to record risk for transformers.
typical values from which conclusions can be drawn about the There are a number of failure mechanisms which affect the
future operational behavior of transformers. The operating con- life expectancy of transformers, and transformer failure can occur
ditions of transformers are the important inputs to the technical as a result of different causes and conditions (Figure 1). Failure
and economic models used to determine the most cost-effective factors in transformers include electrical breakdown, lightning,
alternative for operation, refurbishment, or replacement. dielectric fault, loose connection, incorrect maintenance, mois-
ture, excessive overloading, and other causes [1]. Contamination,
Failure Survey on Transformers thermal aging, repetitive excessive voltage stress, and mechanical
There are many different risk assessment methods and strate- deformation hasten electrical breakdown. Dielectric failure is a
gies available to the utility industry for a large family of trans- common failure occurrence and can have a profound effect on

26 0883-7554/07/$25/©2008IEEE IEEE Electrical Insulation Magazine


Figure. 1. Transformer failure causes [1]. Figure 3. Transformer failure detection methods (TTR:
transformer turns ratio; DGA: dissolved gas analysis; TCG:
total combustible gas; PD: partial discharge) [3].
useful life. Contamination and thermal aging can be monitored
through testing. Voltage stress can be controlled by design of the
transformer protection and operating philosophy.
Figure 2 illustrates the failure statistics of the defective compo- Condition Monitoring and Standard
nents and identifies those areas where failure-reducing efforts can Diagnosis
be best directed. When analyzing the failure causes, information One of the most important tasks for utilities is the maintenance
on faults is given in load tap changer (LTC), bushing, winding, of transformers to provide high customer reliability. There are
tank, core, and relay [2]. some basic procedures by which a utility can better judge the con-
Figure 3 shows the most common detection methods of trans- dition of its transformers: monitoring, diagnosis, and maintenance.
former failures and the percentage of all the detection methods These basic evaluation steps in condition assessment provide the
representing studies conducted for many years: relay test, inspec- data for analysis and prioritization of maintenance measures. For
tion, turns ratio test (TTR), dissolved gas analysis (DGA), resis- effective maintenance, testing and diagnostics must be applied in
tance test, total combustible gas test (TCG), current test, power a careful coordinated way that uses the results from international
factor test, temperature test, capacitance test [3]. In the following, testing standards to identify overall transformer condition and
we will discuss the diagnostic methods. performance. The results of these investigations are important
Once the FMEA process has established a priority list, diag-
nostic testing and condition assessment can establish a detailed
asset management strategy. The importance of diagnostic methods
can recognize which diagnostic parameter affects the transformer
condition to a greater or lesser degree than other parameters [4].
Transformer diagnostics are somewhat subjective, relying on
(1) analysis of oil and paper; (2) power factor, capacitance, and
excitation current tests; (3) turns ratio, leakage reactance, wind-
ing resistance, frequency response, core insulation resistance,
ultrasonic/sonic, and vibration analysis. Figure 4 ranks the
importance of different diagnostic methods for the estimation of
transformer conditions.

Figure 2. Defective components of a transformer (LTC: load Figure 4. The importance of different diagnostic methods to
tap changer) [2]. estimate transformer conditions with color distinction.

July/August 2008 — Vol. 24, No.4 27


Table 1. DGA Analysis

Limit Diagnostics Interpretation Measures

1. Four IEEE® Conditions The measured parameters < 1. Overheating destroys oil insulation 1. The different measures are made
2. Duval Triangle Analysis recommended safety limits: and reduces life expectancy of according to conditions of transformers.
3. Rogers Ratio The most severe intensity of energy transformers. 2. Internal inspection should be
Analysis dissipation occurs with arcing, less with 2. The quality of oil is reflective of the considered.
4. Doernenberg Ratio Analysis heating, and least with corona. health of transformers.

Table 2. Typical Faults and Possible Findings in Transformers

Fault types Possible findings

Partial discharge Weakened insulation from aging and electrical stress.

1. Pinhole punctures in paper insulation with carbon and carbon tracking.


2. Possible carbon particles in oil.
Discharge of low energy
3. Possible carbon particles in oil.
4. Possible loose shield, poor grounding of metal objects.

1. Metal fusion, poor contacts in LTC or lead connections.


Discharge of high energy 2. Weakened insulation from aging and electrical stress. Carbonized oil.
3. Paper destruction if it is in the arc path or overheated.

1. Discoloration of paper insulation.


2. Overloading and/or cooling problem.
Thermal fault < 300°C
3. Bad connection in leads or LTC.
4. Stray current path and/or stray magnetic flux.

1. Paper insulation destroyed.


Thermal fault 300°C–700°C
2. Oil heavily carbonized.

1. Same as above with metal discoloration.


Thermal fault > 700°C
2. Arcing may have caused a thermal fault.

to determine the most cost-effective alternative for operation, electrical or thermal stresses break down to liberate small quanti-
refurbishment, or replacement. ties of gases. The composition of these gases is dependent upon
To reliably assess the overall condition of a transformer, several the type of fault (Tables 1 and 2). The most important diagnostic
monitoring techniques are used or are under investigation. In ad- parameters are the individual and total dissolved combustible gas
dition to the traditional routine tests, there are some specialized
tests including partial discharge measurement, frequency response
analysis, infrared examination, vibration analysis, and degree of
polymerization. These monitoring tests may detect problems such
as local partial discharge, winding looseness and displacement,
mechanical faults, hot spot at connectors, moisture in paper and
aging of paper, as well as insulation degradation. The careful
recording and plotting of the test results makes it possible to get
the full information out of a test and to compare the values with
those of previously accomplished tests and international testing
standards.
Interpretive discussions are also included to provide guidance
on acceptance criteria. These activities may help identify existing
weaknesses or faults and also give some indication of expected
service reliability and remaining life.

A. Dissolved Gas Analysis (DGA)


DGA has proven to be a valuable and reliable diagnostic
technique for the detection of incipient fault conditions within
liquid-immersed transformers. Insulating oils under abnormal Figure 5. Duval Triangle Analysis for DGA [6].

28 IEEE Electrical Insulation Magazine


Figure 6. Roger Ratio Criteria for DGA [7].

concentrations (TDCG) and their generation rates [5]. By means The first step is to establish whether or not a fault exists by
of dissolved gas analysis (DGA), it is possible to distinguish fault using the IEEE method [5]. Only when these levels exceed some
types such as internal arcing, bad electrical contacts, hot spots, threshold value is a fault suspected. The second step is to deter-
partial discharge, or overheating in oil, cellulose paper, tank, or mine the type of fault. Three methods are most commonly used:
conductors, etc. Duval Triangle (Figure 5), Roger Ratio Criteria (Figure 6) and

Table 3. Moisture Test of Oil

Limit Diagnostics Interpretation Measures

M/DW 1. Moisture in presence of oxygen is 1. Paper insulation has a much greater 1. Transformer should have a dry out
(moisture/dry weight) > 2.5% extremely hazardous to insulation of affinity for water than oil does. with vacuum or do round-the-clock re-
paper and transformer. 2. Temperature is also a big factor in how circulation with a Bowser.
2. Moisture and oxygen form acids, metal water distributes itself between the oil 2. DGA and Doble tests should be
soaps and sludge, causing transformer and paper. examined.
cooling to be less efficient, 3. Each time the moisture is doubled in a
temperature to rise slowly over time and transformer, the life of
paper insulation to decay. insulation is cut by one-half.
3. Moisture reduces the dielectric 4. This is a vicious cycle of increasing
strength of oil. speed with deterioration forming more
4. Above 4% M/DW, it is in danger of acid and causing more decay.
flashover if temperature rises to 90°C.

Table 4. IFT Test of Oil

Limit Diagnostics Interpretation Measures

Number of interfacial tension < 22 1. Oil is very contaminated and sludge 1. As oil ages, it is contaminated by Oil should be reclaimed to prevent sludge
dynes/cm is formed. oxidation products of oil and paper when it reaches 25 dynes/cm.
2. Sludge will settle on windings, insulation. These oxidation products will
insulation, cooling surfaces, and cause weaken the surface tension between oil
loading and cooling problem. This will and water and lower IFT number.
greatly shorten transformer life. 2. IFT and acid number together are an
excellent indication of when oil needs to
be reclaimed.

July/August 2008 — Vol. 24, No.4 29


Table 5. Oxygen Test of Oil

Limit Diagnostics Interpretation Measures

O2 concentration > 2000 ppm 1. High oxygen means a leakage in 1. Under the same temperature 1. Oil should be de-gassed and new
conservator. conditions, cellulose insulation in high- oxygen inhibitor installed when oxygen
2. Oxygen in oil greatly accelerates oxygen oil will last 10 times shorter than reaches 10000 ppm.
paper deterioration. insulation in low-oxygen oil. 2. DGA test must be done.
2. This becomes even more critical with
moisture above safe level.

Ditertiary Butyl Paracresol by total 1. Inhibitor is used up. 1. Oxygen inhibitor is a key to extend the 1. Inhibitor needs to be replaced.
weight of oil > 0.3% 2. Transformer ages. life of transformers. 2. Oil needs to be treated.
2. This works similarly to a sacrificial 3. DGA test must be done.
anode in grounding circuits. Oxygen
attacks inhibitor instead of cellulose
insulation.

Table 6. Acid Test of Oil

Limit Diagnostics Interpretation Measures

Acid number > 0.4 mg KOH/gm 1. Oxidation of insulation and oil form 1. Acid attacks metals in tank and forms Oil should be reclaimed to prevent
acids and sludge. soaps. Acid also attacks cellulose and sludge when it reaches 0.2 mg KOH/gm.
2. Sludge will settle on windings, accelerates insulation degradation.
insulation, cooling surfaces and cause 2. IFT and acid number together are an
loading and cooling problems as excellent indication of when oil needs to
temperature rises slowly. This will greatly be reclaimed.
shorten transformer life.

Table 7. Power Factor Test of Oil

Limit Diagnostics Interpretation Measures

Power factor > 1.0% (25 °C) 1. The insulation integrity of oil may be 1. The dielectric loss indicates 1. Replacement or reclaiming of oil is
broken down. deterioration or contamination of oil from required immediately.
2. The state of humidity of oil is by-products such as water, carbon, or 2. Internal inspection should be
determined. other conducting particles, including considered before re-energized.
3. Transformer failure is imminent when metal soaps and oxidation products. 3. Above 2%, oil should be removed
the power factor is above 2%. 2. A trend can be established as from service and replaced because oil
insulation system ages. cannot be longer reclaimed.
3. Test values are compared to previous
or factory tests.

Table 8. Dielectric Strength Test of Oil

Limit Diagnostics Interpretation Measures

1. Minimum oil breakdown voltage < It indicates the amount of contaminants This test is not extremely valuable since 1. Oil should be reclaimed.
20kV (for rated voltage < 288kV) (water and oxidation) in oil. moisture will destroy cellulose insulation 2. DGA test needs to be done.
2. Minimum oil breakdown voltage long before the dielectric strength of oil
<25kV (for rated voltage ≥ 287.5kV) has indicated.

30 IEEE Electrical Insulation Magazine


Figure 8: The relationships between IFT, acid number, and
Figure 7: The relationships between water concentration, service year [12].
temperature, and moisture [11].

Doernenberg Ratio. Interpretation of fault conditions associated significance are recommended for classification purposes and to
with gas concentration and combinations of these gases are also determine the suitability for use of reclaimed oils.
provided in [5].
C. Insulation Tests of Cellulose Paper
B. Physical and Chemical Tests of Oil Quality Furan analysis, degree of polymerization and CO2/CO ratio
An important part of the life extension of a transformer is the tests [5] may indicate a problem with the insulating paper (Tables
restoration of the insulating fluid quality in the transformer. Physi- 9–11), if the transformer is overheated, overloaded, aged, or after
cal and chemical tests such as moisture test, interfacial tension test, processing the oil (Table 9).
oxygen test, acidity test, power factor test, and dielectric strength The presence of these compounds is related to the strength
test [8], [9], [10] usually indicate oil conditions and operational of the paper as measured by its degree of polymerization (DP).
characteristics (Tables 3–8). DP is the average number of glucose molecules making the cel-
Moisture in a transformer decreases the dielectric strength of its lulose chains. The DP value decreases with time as the cellulose
insulation system (Figure 7). The combination of moisture, heat, molecules break and fragment. The paper is assumed to age at a
and oxygen is the key factor that affects the rate of cellulose deg- more rapid rate where the temperature of the paper and exposure
radation. The interfacial tension (IFT) between insulating fluids to oxygen are the highest. Figure 9 depicts the relation between
and water is a measure of the molecular attractive force between relative depolymerization velocity and the water content and
unlike molecules at the interface. This test provides a means of temperature. When the DP test reveals a value of 200 or less, the
detecting contaminants and products of deterioration (Figure 8). paper is considered to have lost almost all mechanical strength,
The oil conditions can be remedied through various reclamation and the transformer has reached its end of life. The distribution of
processes. Therefore, they are not indicative of overall transformer measured DP values in Figure 10 demonstrates that the technical
condition, which would lead to replacement. lifetime of generator transformers is limited to 25 years whereas
Additional tests such as color, visual appearance, flash point, transmission transformers can reach a technical lifetime up to 50
pour point, specific gravity, and viscosity [8], [9], [10] to detect years [13].
the presence of deleterious products of oxidation or contamination As paper degrades, a number of specific furanic compounds
in service-aged oils also seem appropriate. These tests and their are produced and dissolved in the oil. Furanic compounds are a

Table 9. Furans Test of Cellulose Paper

Limit Diagnostics Interpretation Measures

Furans > 250 ppb 1. Overheating, lightning, oxidation, 1. Furan is especially helpful in 1. Oil should be reclaimed.
acids and high moisture accelerate the estimating remaining life in paper 2. Use in conjunction with IFT and acid
destruction of cellulose insulation and insulation and transformer life. number.
form furanic compounds. 2. Test values are compared to previous 3. DGA is always required.
2. Paper insulation is being deteriorated or factory tests.
and transformer life reduced at a high
rate.

July/August 2008 — Vol. 24, No.4 31


Table 10. DP Test of Cellulose Paper

Limit Diagnostics Interpretation Measures

Degree of polymerization < 200 DP All mechanical strength of cellulose 1. The cellulose molecule is made up of 1. Transformer must be replaced.
insulation has been lost and paper a long chain of glucose rings which form 2. Internal inspection is required.
insulation has reached the end of life. the mechanical strength of molecule
and paper. DP is the average number of
these rings in molecule. As paper ages
or deteriorates from heat, acids, oxygen,
and water; bonds between the rings
begin to break, DP decreases.
2. DP is the most dependable means
of determining paper deterioration and
remaining life.

Table 11. CO2/CO Ratio Test of Cellulose Paper

Limit Diagnostics Interpretation Measures

CO2/CO < 3 1. Imminent danger of failure. 1. Extreme overheating from loss of 1. If there is a sudden increase in H2
2. Severe and rapid deterioration of cooling or plugged oil passages will with CO2 and CO, this test is required.
cellulose is certainly occurring. produce a low CO2/CO ratio along with 2. De-energization and internal
3. The fault is probably caused by a increasing Furans. inspection is recommended.
bad connection on a bushing base or on 2. If H2, CH4, and C2H6 are increasing 3. DGA and Furans tests are taken
LTC, or a problem with a core ground. significantly as well as CO and CO2/ immediately to confirm the problem.
4. An excellent indication of abnormally CO<5, there is probably a problem.
high temperatures and rapidly 3. These problems are probably all
deteriorating cellulose insulation is a reparable in the field where a fault will
CO2/CO<5. not degrade cellulose insulation.
5. The large increase in CO2 could
mean an atmospheric leak when the
ratio is above 10.

family of molecules based on a furan ring structure. The most as blockages of cooling system, locating electrical connection
stable of these compounds is 2-furfuraldehyde, or 2-FAL. Ther- problems and hot spots (Figure 12).
mal degradation of insulating paper could be monitored by furan
analysis, especially when due to overheating conditions. Attempts
have been made to relate the furanic content (2-FAL) of oil to the
degree of polymerization (DP) of paper (Figure 11).

D. Infrared Thermograph Test


The monitoring of temperature is usually not a problem and
is very important to evaluate and to assess the influence of many
other parameters, e.g. the humidity content in the oil or paper.
An increase in temperature can indicate cooling problems or
higher losses in the winding, core, bushing, arrester, tank, LTC,
radiator, cooling system, and oil pump (Table 12). An increase
of about 6 K to 8 K correlates with a doubling of the aging pro-
cesses. An increase of about 75 °C will cause immediate failure
of transformers [15].
Thermography is a non-contact means of identifying thermal
anomalies related to electrical and mechanical components that
are exhibiting an excessive heat loss. The self-emitted radiation
in the infrared portion of the electromagnetic spectrum is mea-
sured at the target surface and converted to electrical signals. It Figure 9: Relative depolymerization velocity at different water
is useful for detecting thermal problems in a transformer, such content and temperature [14].

32 IEEE Electrical Insulation Magazine


Figure 10. Aging behavior of cellulose insulation of transmission and generator transformers (GSU) [13].

E. Power Factor Test as displaced wedging and support in winding and core (Table 14).
Power factor testing is important to determine the insulation The insulation condition of bushings can also be determined by
condition of transformers because it can detect the insulation measurement of capacitance [17]. About 90% of bushing failures
integrity in winding, bushing, arrester, tank, and oil (Table 13). may be attributed to moisture ingress.
The condition of bushings can also be determined by measure-
ment of capacitance. Increased power factor may be the result of G. Excitation Current Test
moisture or polar and ionic compounds in the oil [17]. The aging The purpose of this test is to detect short-circuited turns, poor
of bushings is caused by cracking of the resin-bonded paper and electrical connections, core delaminations, core lamination shorts,
inhomogeneous impregnation with insulating oil. The technical LTC problems, and other possible core and winding problems
life time has a great scatter and should not exceed more than 30 (Table 15). The excitation current test [9], [18] measures the
years (Figure 13). single-phase voltage, current, and phase angle between them,
typically on the high-voltage side with the terminals of the other
F. Capacitance Test winding left floating (with the exception of a grounded neutral).
As the transformer ages and events such as nearby lightning On three-phase transformers, results are also compared between
strikes or through faults occur, changes in the measured capaci- phases. The measured current magnetizes the core and generates
tances indicate winding deformation and structural problems such the magnetic fields in the windings.

Figure 11. Furan versus DP for thermally upgraded and non-thermally upgraded paper [13].

July/August 2008 — Vol. 24, No.4 33


Table 12. Infrared thermograph test

Limit Diagnostics Interpretation Measures

1. Hotspot: unusual thermal patterns 1. Circulating stray currents. 1. Abnormally high temperature can 1. Immediate de-energization and
2. Above ambient temperature 2. Blocked cooling. damage or destroy insulation systems replacement must be undertaken.
>75 °C 3. Bad tap changer contact. and thus reduce life expectancy. 2. Internal inspection need to be
4. High temperature may mean problems 2. An increasing temperature of only 8 investigated.
with winding, core, or connections. to 10 °C will reduce transformer life by 3. Doble test may show the problem.
5. Oil leakage. one-half.
6. Ingress of moisture and air. 3. Test values are compared to previous
7. Loose shields. or factory tests.
5. Catastrophic failure is imminent which
can destroy nearby equipment and be
hazardous to workers.

H. Frequency Response Analysis (FRA) previous tests, and similar units to detect deformation of the core
FRA [19] is used to help identify possible deformations and or windings due to shipping damage, through faults, or ground
movements in the transformer core and coil assembly as well faults (Table 19).
as other internal faults (Table 16). This test is also helpful if a
protective relay has tripped or a through fault, short-circuit, or L. Core-to-Ground Test
ground fault has occurred. The core-to-ground resistance test [21] can detect the default
The basis of the FRA technique is that the impedance of the if this connection is loose or indicate if a spurious, unintentional
transformer is related to the construction and geometry of the core ground is the problem (Table 20). It can also supplement
windings. Deformations and movements have an effect on both DGA test that shows the generation of hot metal gases. To check
inductance and capacitance that may be reflected in the resulting for unintentional core grounds, the intentional ground between the
frequency response. Therefore, a change in mechanical structure core and the grounded tank must be removed. If the intentional
results in a change of the resonance frequencies. A change in core ground is intact, the resultant resistance should be very low.
electrical performance due to partial discharges also results in a Experience can help locate the source of the problem.
larger damping of the resonance frequencies.
Different aging mechanisms can be detected and identified at M. Winding Resistance
their respective frequency ranges. Shorted turns, open circuits, or Careful measurement of winding resistance can detect broken
core grounds determine the dielectric loss in the low-frequency conductor strands, loose connections, and bad contacts in LTC
range; core movement or damage is the dominant contributor in [9] (Table 21). Results from these measurements may indicate
the medium-frequency range; and winding displacement or dam-
age is the mechanical defect in the high-frequency range.

I. Vibration Test
Vibration can result from loose core and coil segments, shield
problems, loose parts, or bad bearings on oil cooling pumps
or fans [20] of transformers (Table 17). If wedging has been
displaced due to paper deterioration or through faults, vibration
will increase markedly. It may also show if an internal inspec-
tion is necessary for transformers. Information gained from the
vibration test supplements ultrasonic or acoustic detection and
DGA tests.

J. Turns Ratio Test


The turns ratio (TTR) test detects shorts or open circuits be-
tween turns of the same coil, which indicates insulation failure
between the turns [9] (Table 18). All tap positions and all phases
should be measured and may show the necessity for a further
internal inspection or removal from service.

K. Leakage Reactance Test


This test, sometimes called percent impedance test [18], is
performed in the field and compared to nameplate information, Figure 12. IR image of defective bushing [16].

34 IEEE Electrical Insulation Magazine


Table 13. Power factor test

Limit Diagnostics Interpretation Measures

Power factor > 0.5 % (20 °C) 1. The insulation integrity of windings, 1. The dielectric loss indicates 1. Internal inspection should be
bushings, and insulation systems may deterioration or contamination of considered before re-energized.
be lost. insulation systems from by-products 2. If the problem is severe, the unit may
2. The state of humidity of oil is such as water, carbon, or other have to be taken out of service.
determined. conducting particles.
3. Transformer failure is imminent when 2. A trend can be established as
the power factor is above 2%. insulation system ages.
3. Test values are compared to previous
or factory tests.

the need for an internal inspection. This information supplements This test can detect partial discharge (corona) and full discharge
DGA if DGA shows the generation of heat gases. When comparing (arcing) inside the transformer (Table 22). These devices also can
to factory tests, a temperature correction must be employed. detect loose parts inside the transformer that cause corona, spark-
ing, and arcing. Sonic testing can detect increased core or coil
N. Ultrasonic and Sonic Fault Detection Tests noise (looseness) and vibration, failing bearings in oil pumps and
Partial discharge occurs in an insulating system when a local fans, and nitrogen leaks in nitrogen-blanketed transformers. Infor-
breakdown of the insulating medium causes a redistribution of mation gained from these measurements supplements DGA test-
charge within the insulating system [9], [22]. There may also be ing, and provides additional support information for de-energized
changes to the original impulse (electrical, mechanical, acoustical, tests such as core ground and winding resistance tests.
and optical) due to the propagation characteristics in the insulat-
ing medium. The PD measurement systems principally depend O. Visible Inspection and Internal Inspection
on the bandwidth (narrow-, limited-wide, or wide-band system). If an internal inspection is absolutely necessary, it must be
With the knowledge of the impulse characteristic (spectrum and completed by an experienced person who knows exactly what to
waveform of the PD impulse) different measurement methods for look for and where to look. There are very few reasons for a visible
the apparent charge and the localization of failure are possible. inspection or an internal inspection as shown below [9]:
One technique consists of electrical measurements in millivolts, • corona in bushings, arresters, and all high voltage connec-
picocoulombs, or in microvolts of radio frequency. The other tions
method consists of acoustical measurements with an ultrasonic • incorrect mechanical connections in conservator, bladder,
transducer. breather, etc.
The diagnostic procedure is based on the evaluation of the • increasing C2H2, C2H4, and C2H6 in DGA tests
signal deformation of PD pulses within the transformer by • an additional core ground
mathematical algorithms. Figure 14 describes schematically the • loose windings
localization of failure in a transformer winding which is based on • low CO2/CO ratio
the comparison of the winding model with the transfer function • high furans
measured on the real transformer winding.

Figure 13: Aging behavior of resin-bonded paper bushings [17].

July/August 2008 — Vol. 24, No.4 35


Table 14. Capacitance Test

Limit Diagnostics Interpretation Measures

Changes in capacitances 1. Bushing loss and moisture ingress. 1. A trend can be established as 1. The test results are evidenced also by
2. Winding deformation, displaced insulation system ages. an increasing power factor.
wedging and winding support as some 2. Test values are compared to previous 2. Internal inspection should be
events occur, such as near-by lightning or factory tests. considered before re-energized.
strikes or through faults. 3. If the problem is severe, the unit may
have to be taken out of service.

Table 15. Excitation current test

Limit Diagnostics Interpretation Measures

1. Difference between two phase- 1. There are short-circuited turns, 1. When poor electrical connections 1. Other tests should also show
excitation currents >5% for a rated poor electrical connections, core de- occur, the reluctance through the abnormalities;
excitation current < 50mA laminations, core lamination shorts, and magnetic core changes, resulting in 2. Internal inspection should be
2. Difference between two phase- LTC problems. a change in the measured excitation considered before re-energized.
excitation currents >10% for a rated 2. There is an internal problem if the current. 3. If the problem is severe, the unit may
excitation current ≥ 50mA measured value > these limits. 2. The excitation current test relies on have to be taken out of service.
reluctance of core.
3. A trend can be established as
insulation system ages.
4. Test values are compared to previous
or factory tests.

Table 16. Frequency response analysis

Limit Diagnostics Interpretation Measures

Shape change 1. There is winding displacement or 1. By the winding transfer function in 1. This test should be conducted before
>3dB damage if frequency >10000Hz. trace form, this test shows that damage and after transformer has been moved
2. There is core movement or damage if has occurred during shipping or during a or after experiencing a through fault.
frequency <5000Hz. through fault. 2. This test can show the exact phase
3. There are shorted turns, open circuits, 2. Test values are compared to previous position of problem.
or core grounds after shipping or a or factory tests. 3. Internal inspection should be
through fault if frequency < 2000 Hz. considered before re-energized.
4. If the problem is severe, the unit may
have to be taken out of service.

Table 17. Vibration test

Limit Diagnostics Interpretation Measures

The measured frequency is twice the 1. There is a good condition if the Test values are compared to previous or 1. Extreme care must be exercised in
line frequency. measured value is twice the line factory tests. evaluating the source of vibration.
frequency. 2. Internal inspection should be
2. Otherwise, loose parts, loose core, considered.
loose winding, bad bearings on oil
pumps can be detected.
3. If wedging has been displaced due
to paper deterioration or through faults,
vibration will increase markedly.

36 IEEE Electrical Insulation Magazine


Table 18. Turns ratio test

Limit Diagnostics Interpretation Measures

Change in turns ratio to the nameplate 1. False turns ratio indicates the shorted Test values are compared to previous or 1. Set the tap changer position on which
value > 0.5% turns which may result from short factory tests. the nameplate voltage is based.
circuits, open circuits, or insulation 2. Nameplate information for reclamation
failures for service-aged transformers. transformers is based on the tap 3
2. This value is above 0.1% for new position of the tap changer.
transformers. 3. DGA and Doble tests have been
performed.

Table 19. Leakage reactance test

Limit Diagnostics Interpretation Measures

Difference from the nameplate 1. These changes in impedance indicate 1. When winding distortion occurs, the 1. This test complements capacitance
Impedance: winding deformation, displaced wedging reluctance to the magnetic flux changes, and excitation current tests and they are
> 3% and winding support as some events resulting in a change in the measured used together.
occur, such as near-by lightning strikes, leakage reactance. 2. Internal inspection should be
through faults, or other surges. 2. The leakage reactance test relies on considered before re-energized.
2. Winding deformation can lead to reluctance of spaces. 3. If the problem is severe, the unit may
immediate transformer failure after 3. A trend can be established as have to be taken out of service.
a severe through fault or a small transformers age.
deformation can lead to a failure years 4. Test values are compared to previous
later. or factory tests.

Table 20. Core-to-ground resistance test

Limit Diagnostics Interpretation Measures

Resistance A new transformer. A trend can be established as insulation 1. The unintentional core ground must
>1000 MΩ system ages. be corrected before energizing if below
10 MΩ.
Resistance A service-aged transformer. 2. This test is necessary if
> 100 MΩ C2H4, C2H6, and CH4 are present by DGA
test and all connections are good by
Resistance Deteriorating insulation between core winding resistance test.
10-100MΩ and ground.

Resistance It is sufficient to cause destructive


< 10 MΩ circulating currents.

Table 21. Winding resistance test

Limit Diagnostics Interpretation Measures

Resistance change to the factory value 1. Loose connections on bushing, LTC, Test values are compared to previous 1. This test is necessary if C2H4, C2H6,
> 5% and arrester may be detected. or factory tests with the same reference and CH4 are present by DGA test.
2. Shorted winding turns or open temperature. 2. Turns ratio, frequency response, and
winding circuit. Doble tests may indicate that this test is
necessary.

July/August 2008 — Vol. 24, No.4 37


Figure 14. Fault location in a transformer winding [14].

Asset Management of Transformer In oil-impregnated transformers, much attention has been paid
Asset management of transformers has gained an increas- to the condition diagnosis of the cellulose insulating materials (pa-
ing acceptance in the past 15 to 20 years, due to economic and per and pressboard). The insulating paper around the conductors
technical reasons. The fundamental objective is to prolong the decays if it has been aged due to the heat dissipation of windings,
possible service life and to minimize operating costs. Operation, the loss induced by eddy-current, or the presence of water. Thus,
maintenance, and refurbishment of a transformer must all be the effects of temperature and water on the lifetime of insulating
considered together to determine the whole life-cycle cost for paper should be taken into consideration.
the transformer. Furthermore, load tap changers are aged by charged particles
The lifetime of a transformer is affected by the decrease in existing in insulating materials. If the electrical stress continues
electrical, thermal, or mechanical strength, related to the aging for a long time, partial discharges produce so much decomposi-
of windings, tanks, bushings, or load tap changers. The aging tion that conductive paths are formed in dielectric materials and
of windings depends strongly on the operating history of the the dielectric strength of insulating materials tends to decrease
transformer, particularly on the thermal stress due to an overload. with time.
Tanks are affected by corrosion which is related to operating The decrease of mechanical strength is the main cause of fail-
time and maintenance history. The aging of bushings due to ures. Transformers are aged typically due to wear-out processes
thermal stress depends on the operating load of the transformer. such as material fatigue under cyclic loading. This may occur
During the normal operation of load tap changers, the operat- when normal vibration causes failure or during the more severe
ing reliability is affected by the particles produced in insulating forces of through-fault conditions. When mechanical stress is
oils corresponding to the temperature as well as to the operating present, an empirical model based on a fatigue crack propagation
frequency. approach can be described.

Table 22. Ultrasonic and Sonic Fault Detection Tests

Limit Diagnostics Interpretation Measures

Frequency: Audible 1. Partial discharges most often occur 1. Low energy discharges from partial 1. This test should be applied when
near the top of transformer in areas of discharge (corona) or full discharge H2 in DGA test increasing markedly.
high voltage stress which can readily (arcing) emit energy in the order 20 CH4, C2H4, C2H6, and C2H2 may also be
be located. kHz to 200 kHz. These frequencies increasing.
2. Partial discharges located deep within are above levels that can be detected 2. Internal inspection should be
windings may not be sensitive enough to audibly. considered.
detect and locate. 2. Remedying these defects can 3. This defect can be easily remedied.
3. Loose parts inside transformer can be sometimes extend transformer service
located through the test. life.
4. Sonic (audible ranges) fault detection 3. Test values are compared to previous
can find mechanical problems such as or factory tests.
noisy bearings, gas leaks, or other loose
parts.

38 IEEE Electrical Insulation Magazine


References
[1] R. James and W. Bartley, “Transformer asset management,”
Weidmann – ACTI Inc. Second Annual Conference, New Diagnostic
Concepts for Better Asset Management, Nov. 2003.
[2] CIGRE Working Group 12.05, “An international survey on failures
in large power transformers in service,” Electra, no. 88, pp. 21–47,
1983.
[3] Doble Client Committee on Transformers, “Analysis of replies to the
technical questionnaire on power transformer failures and troubles,”
Proceedings of the 65th Annual International Conference of Doble
Clients, pp. 8-2.1–8-2.10, 1998.
[4] IEEE Guide for the Evaluation and Reconditioning of Liquid Im-
mersed Power Transformers, IEEE Std. C57.140, 2006.
[5] IEEE Guide for the Interpretation of Gases Generated in Oil-
Immersed Transformer, IEEE C57.104, 2007.
[6] M. Duval, “Dissolved gas analysis: It can save your transformer,”
IEEE Electr. Insul. Mag., vol. 5, no. 6, pp. 22–27, 1989.
[7] IEC Std 60599, 1999, Mineral Oil-Impregnated Electrical Equip-
Figure 15. Calculated failure probabilities: transmission ment in Service - Guide to the Interpretation of Dissolved and Free
transformer (solid line); distribution transformer (dotted line). Gases Analysis.
[8] IEEE Std. 637, 2007, IEEE Guide for the Reclamation of Insulating
Oil and Criteria for Its Use.
[9] IEEE Std. 62, 1995, IEEE Guide for Diagnostic Field Testing of
Therefore, the failure probability of transformers (P(t)) can be Electric Power Apparatus - Part 1: Oil Filled Power Transformers,
well described by the diagnostic model [23] Regulators, and Reactors.
[10] IEEE C57.106, 2006, IEEE Guide for Acceptance and Maintenance
P(t) = f(E,M,T,t) of Insulating Oil in Equipment.
[11] Y. Du, M. Zahn, B. C. Lesieutre, and A. V. Mamishev, “Moisture
where E, M, T, and t are the electrical, mechanical, thermal stresses, equilibrium in transformer paper-oil systems,” IEEE Electr. Insul.
Mag., vol. 15, no. 1, pp. 11–20, 1999.
and lifetime, respectively.
[12] J. Fitch, “The surface tension test - Is it worth resurrecting?,” Pract.
Figure 15 shows the cumulative probability distribution of fail-
Oil Anal. Mag., Sept. 2002
ure for transmission and distribution transformers which have the [13] P. Thomas and A. K. Shukla Raghuveer, “Aging studies on pa-
obvious dependence on component age. Transmission transformers per - oil to assess the condition of solid insulation used in power
cause primary failures in electric power systems, thus they are very transformers,” IEEE 7th Int. Conf. Solid Dielectrics, Eindhoven, the
maintenance-relevant. For transmission transformers, the decrease Netherlands, 2001.
of mechanical strength is the most frequent cause of failure, also [14] H. Borsi and E. Gockenbach, “Monitoring, diagnosis and life
yielding to the leakage of oil or the damage of metal shells to a management of power transformers”, Conf. Maintenance Opera-
large extent. As significant equipment, distribution transformers tion High-Voltage Electrical Equipment, (TechCon Asia-Pacific),
Sydney, Australia, May 2007.
are affected in three ways by the degradation stress: leakage of
[15] IEEE Std. C57.91, 2002, IEEE Guide for Loading Mineral-Oil-
oil, abnormal operation of on-load tap changers, and accidental
Immersed Transformers.
voltage impulse on transformers. [16] Z. Korendo and M. Florkowski, “Thermography-based diagnostics
of power equipment,” Power Eng. J., pp. 33–42, Feb. 2001.
Conclusions [17] J. Schneider, A. J. Gaul, C. Neumann, J. Hograefer, W. Wellßow, M.
In this paper, a methodology is developed to use data acquisi- Schwann, and A. Schnettler, “Asset management techniques,” Int.
tion derived from condition monitoring and standard diagnosis J. Electr. Power Energy Syst., vol. 28, no. 9, pp. 643–654, 2006.
[18] IEEE Std. C57.12.90, 2006, IEEE Standard Test Code for Liquid-
for rehabilitation purposes of transformers. The interpretation
Immersed Distribution, Power, and Regulating Transformers.
and understanding of the test data are obtained from international
[19] IEEE PC57.149, 2004, A Guide to Frequency Response Analysis
test standards to determine the current condition of transformers. in Oil-immersed Transformers.
In an attempt to ascertain monitoring priorities, the effective test [20] IEEE Standard Requirements, Terminology, and Test Code for Shunt
methods are selected for transformer diagnosis. In particular, the Reactors Rated Over 500 kVA, IEEE Std. C57.21, 2007.
standardization of diagnostic and analytical techniques are being [21] IEEE C57.12.00, 2006, IEEE Standard General Requirements for
improved that will enable field personnel to more easily use the Liquid-Immersed Distribution, Power and Regulating Transform-
test results and will reduce the need for interpretation by experts. In ers.
addition, the advanced method has the potential to reduce the time [22] IEEE C57.113, 1991, IEEE Guide for Partial Discharge Measure-
ment in Liquid-Filled Power Transformers and Shunt Reactors.
greatly and increase the accuracy of diagnostics. The important aim
[23] X. Zhang and E. Gockenbach, “Component Reliability Model-
of the standardization is to develop the multiple diagnostic models
ing of Distribution Systems Based on the Evaluation of Failure
that combine results from the different tests and give an overall Statistics,” IEEE Trans. Dielectr. Electr. Insul., vol. 14, no. 5, pp.
assessment of reliability and maintenance for transformers. 1183–1191, 2007.

July/August 2008 — Vol. 24, No.4 39


Xiang Zhang received the B.Sc., M.Sc., and Ph.D. degrees 1982, he worked at Siemens AG, Berlin, Germany. From 1982 to
in Electrical Engineering from Xi’an Jiaotong University, Xi’an, 1990, he worked with E. Haefely AG, Basel, Switzerland. Since
China, in 1989, 1992, and from the Aachen University of Tech- 1990, he has been professor and director of the Schering-Institute
nology, Aachen, Germany, in 2002, respectively. From 1992 to of High Voltage Technology at the University of Hanover, Ha-
1997, she was a research engineer at Xi’an High Voltage Apparatus nover, Germany. He is member of VDE and CIGRE, chairman
Research Institute, Xi’an, China. Currently she is a research fel- of CIGRE Study Committee D1 Materials and Emerging Tech-
low on asset management of networks of the Schering-Institute nologies for Electrotechnology, and a member of national and
of High Voltage Technology at the University of Hanover, Ha- international Working Groups (IEC, IEEE) for Standardization
nover, Germany. Her main areas of interest include high voltage of High Voltage Test and Measuring Procedures.
apparatus, gas discharge, arc modeling, and asset management
of networks.

Ernst Gockenbach received the M.Sc. and


Ph.D. degrees in Electrical Engineering from the 02%#)3)/.7/5.$
Technical University of Darmstadt, Germany, - !' . % 4 7 ) 2 % ) . 3 5 , !4 ) / .
in 1974, and 1979, respectively. From 1979 to

& 2 / -
#/..%!54
5TILIZINGADVANCEDTECHNIQUESINWINDINGPOLYGLASSINSULATINGYARNS #ONNEAUT)NDUSTRIES
ISNOWCUSTOMWINDINGLARGERPRECISIONSPOOLSFORMAGNETWIREMANUFACTURERS

4HESE#ONNEAUTSPOOLSPROCESSMOREYARDAGEANDCAPACITYTHANPREVIOUSLYPOSSIBLE
!PROPRIETARYMETHODOFYARNLAYINGENSURESEVEN CONSISTENTANDUNIFORMPACKAGES
!NINNOVATIVEPLASTICSPOOLISAVAILABLEINMETEREDLENGTHSˆUPTOENDS
4HERECOGNIZEDINDUSTRYLEADEROFINSULATINGYARNSANDFIBERS #ONNEAUTPRODUCES
SPECIALTYYARNSFORABROADRANGEOFINDUSTRIALAPPLICATIONSˆBRAIDERPACKAGES SERVINGSPOOLS
ANDHIGHCAPACITYPAYOFFREELSOFFIBERGLASSROVINGREINFORCEMENTSFORIGNITIONWIRES

  9!2.


  &AX  
WWWCONNEAUTCOM
)3/ E MAILINFO CONNEAUTCOM
#ONTACT*OHN03ANTOS )NCORPORATED

3HIPPING(OPKINS(ILL2OAD 7EST'REENWICH 2)-AIL0/"OX #OVENTRY 2) 

40 IEEE Electrical Insulation Magazine

View publication stats

You might also like