You are on page 1of 11

Downloaded from https://iranpaper.

ir
https://www.tarjomano.com https://www.tarjomano.com

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 68, NO. 8, AUGUST 2021 7485

Detection of Turn-to-Turn Faults in the Stator and


Rotor of Synchronous Machines During Startup
Saeed Afrandideh , Farhad Haghjoo , Senior Member, IEEE, Sérgio Cruz , Senior Member, IEEE,
and Mostafa Eshaghi Milasi

Abstract—An invasive diagnostic technique is proposed of faults [1]. Typically, they are the result of an insulation failure
in this article for the detection and discrimination of turn-to- in adjacent turns, whose main causes are the thermal insulation
turn faults in the stator and rotor windings of synchronous deterioration of the stator/rotor windings, overheating, overvolt-
machines during the startup period. For this purpose,
search coils are installed in the machine to sense the rota- age, vibration, and thermal cycling [2], [3]. TTFs are likely to
tional magnetic field along the air-gap circumference, while occur in both the rotor poles windings and in the stator windings.
the difference in the related induced voltages (differential In the case of a rotor turn-to-turn fault (RTTF), the shorted turns
voltages) reveals its distortion, using it as a criterion for are bypassed and they lead to a reduction of the effective number
the detection of the faulty condition. Nevertheless, the rotor
of active turns of the excitation winding. Therefore, a RTTF
speed is a time-variant parameter, which changes from zero
at the starting instant up to its rated value at a synchronous increases the excitation current and decreases the output reactive
speed. Consequently, during the generator startup, the fre- power of the machine, may cause the rotor to be grounded at one
quency of the induced voltages in the search coils needs or two points, and the shaft magnetization [4]–[7]. In addition,
to be updated continuously for obtaining reliable values for the temperature of the shorted turns is reduced in comparison
the differential voltages. A simple method is presented to with the rest of the winding and a temperature difference will
achieve this goal by detecting the sequential zero cross-
ing of the voltage waveforms. The proposed method is appear in the rotor body. The high temperature difference may
verified through simulation and experimental results. They cause the main shaft to bow, which will culminate in machine
show that the proposed diagnostic technique is capable of vibration. On the other hand, RTTFs create rotor asymmetric
detecting and discriminating stator and rotor turn-to-turn poles and will subsequently increase the machine vibrations.
faults during the machine startup period, both in generating In the case of stator turn-to-turn faults (STTFs), similarly to
and motoring conditions, with suitable accuracy and secu-
rity. In addition, the region of stator turn-to-turn faults can RTTFs, the number of active turns of the winding is reduced.
be easily identified. In addition, a reverse ampere-turn appears in the faulty region
Index Terms—Fault detection, fault location, rotor wind- caused by the high current circulating in the shorted turns.
ing, startup period, stator winding, synchronous machine, Therefore, unexpected heat is generated in the faulty region,
turn-to-turn faults (TTFs). which may damage the insulation of adjacent turns and may
even burn the insulation of the magnetic core [8]. Since a STTF
I. INTRODUCTION occurs inside the stator windings and at an unknown location,
URN-TO-TURN faults (TTFs) usually occur in syn- its detection is very difficult [9]. When the fault is located inside
T chronous generators (SGs) both in a steady-state operation
and in the startup period, when the rotor is accelerating. TTFs
a slot and cannot be isolated from the adjacent turns, if it is not
detected at an early stage, it will cause serious damage to the
are not uncommon in SGs, accounting for about 39% of all types generator [10]–[12]. Therefore, it may take several weeks for
the faulty generator to be repaired/replaced. On the other hand,
the generator outage may overload the rest of the grid [13].
Manuscript received February 3, 2020; revised March 31, 2020 and
May 16, 2020; accepted June 10, 2020. Date of publication June 25, Accordingly, several methods [14]–[26] have been proposed for
2020; date of current version April 27, 2021. This work was supported the detection of STTFs by evaluating the stator current harmon-
by FCT/MCTES through national funds and when applicable co-funded ics or signatures [14]–[18], zero-sequence voltage component
by EU funds under the project UIDB/EEA/50008/2020. (Corresponding
author: Farhad Haghjoo.) [19], [20], the machine inductance variations [21], [22], the
Saeed Afrandideh, Farhad Haghjoo, and Mostafa Eshaghi Milasi total harmonic distortion of the leakage flux [23], the air-gap
are with the HV/MV Equipments Protection Research Laboratory magnetic flux components [24], [25], and the harmonic content
(HV/MV EPRL), Department of Electrical Engineering, Abbaspour
School of Engineering, Shahid Beheshti University, Tehran 19839 of the field current [26]. Moreover, several methods [27]–[37]
69411, Iran (e-mail: s.afrandideh@mail.sbu.ac.ir; f_haghjoo@sbu.ac.ir; have been proposed for the detection of RTTFs by evaluating the
m.eshaghimilasi@mail.sbu.ac.ir). stator frame vibration [27], the shaft-induced voltage [28], the
Sérgio Cruz is with the University of Coimbra, Department of Electrical
and Computer Engineering, 3030-290 Coimbra, Portugal, and also with zero-load electromotive force [29], the electromagnetic power of
the Instituto de Telecomunicações, 3030-290 Coimbra, Portugal (e-mail: the machine [30], the external flux of the machine [31], [32], the
smacruz@ieee.org). circulating current in the parallel branches of the stator winding
Color versions of one or more of the figures in this article are available
online at https://ieeexplore.ieee.org. [33], and the radial air-gap magnetic flux [34]–[37]. However, all
Digital Object Identifier 10.1109/TIE.2020.3003626 of them were proposed to detect TTFs in steady-state conditions

0278-0046 © 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.

Authorized licensed use limited to: The University of Toronto. Downloaded on March 04,2023 at 06:29:30 UTC from IEEE Xplore. Restrictions apply.
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

7486 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 68, NO. 8, AUGUST 2021

(at rated frequency). Such techniques are incapable of detecting corresponding SCs. As a consequence, the differential of the
TTFs during the startup at nonrated and/or variable frequencies. induced voltages in SC pairs (that should sense equal magnetic
It should be noted that if the generator is started with a STTF, flux in normal conditions) is nearly zero. When a fault arises, the
very likely the stator windings will be damaged earlier than variation of the magnetic field along the air-gap circumference
the generator reaches the steady-state condition. In addition, is not identical/symmetrical as the ampere-turns in the faulty
starting the machine with a RTTF will increase the vibration, coil of the stator/rotor are reduced. Hence, the symmetry of the
thus, harming the bearings and reducing the winding insulation air-gap rotational magnetic field (RMF) is lost, as sensed by the
lifetime. SC pairs, and the differential of the induced voltages in those
TTFs detection is a significant issue during startup in large- SCs will contain the information need to detect the fault.
scale machines because they have long acceleration times (from The capability of the proposed method to detect and discrim-
3 to 5 min [38]). In pumped-storage power plants, this issue is inate STTFs and RTTFs during the startup is verified by a finite-
even more critical than in SGs, because the machines in these element analysis (FEA) and by experimental tests conducted on
applications are operated sometimes as synchronous motors (to a sample 380 V, 8-kW, 4-pole salient pole synchronous machine
pump the water from the lower reservoir to the upper one) operating in generating and motoring modes, being this method
and sometimes as SGs (to produce electrical power using the able to identify the faulty region in the case of STTFs.
energy of the water flowing from the upper reservoir to the lower Since all methods presented in previous papers were based on
one). Therefore, such machines need to be started and stopped the operation of the machine at rated frequency, the performance
frequently [39], [40] and there is a high probability of occurrence of the proposed technique in this article cannot be compared
of TTFs during the machine startup. with them. However, from a general point of view, the pro-
There are different methods to start synchronous machines. posed technique, although invasive, does not need measuring
Frequency starting is one of them, which can be divided into two transformers (e.g., CT or PT). In addition, it is insensitive to
basic methods. unbalanced voltage sources or to any harmonic content they
1) Back-to-back starting, where the two machines (one of may contain when the machines operates in the motoring mode.
them running as a motor and other one as a genera- These features are due to the fact that the diagnosis uses directly
tor) connected via their stators are excited while still the air-gap magnetic field distortion through the differential of
stationary. the induced voltages in SC pairs. Moreover, the faulty coil
2) Partial frequency starting through a static/startup fre- group (CG) can be identified in the case of STTFs. For the
quency controller (SFC) system, where a voltage of low case of RTTFs, the rotor faulty pole can be identified by offline
frequency is applied to the motor and progressively in- techniques.
creased up to the rated value in order to connect it to the
grid. II. PROPOSED TECHNIQUE FOR THE DETECTION OF TTFS
The advantage of partial frequency starting over back-to-back DURING THE SG STARTUP PERIOD
starting is that there is no need for a separate source of excitation
during the asynchronous stage [41]. A. TTFs Detection
Any existent TTF must be detected as soon as possible, Magnetic flux sensors have been used in power transformers
otherwise it may cause irreparable damage to the machine. Such [42]–[45], induction motors [8], [46], and SGs [24], [25], [34],
problem can also occur in machines with a TTF during their [36] for TTF detection in steady-state conditions, over the past
startup as SGs. years. It has been shown that the RMF measurement by SCs
Since during the startup period, the generator voltage grad- is an effective technique to observe the related distortion as a
ually increases proportionally to the frequency (ϕ ∝ v/f is consequence of TTFs with high security, suitable sensitivity, and
maintained constant during this period of time), the detection reasonable accuracy. Similarly to the papers mentioned above,
of TTFs in this time interval will limit the machine damage SCs are used in this article to observe the RMF and measure the
because at lower frequency and voltage values, the fault current RMF distortion along the air-gap circumference.
in the shorted turns of the stator is lower than the rated value. Fig. 1 shows the stator winding arrangement of phase B and
In addition, the machine vibration at lower speeds and smaller the location of the installed SCs in the sample generator. Each SC
excitation currents is significantly less than at the steady-state senses the RMF in its vicinity. As a common feature of STTFs
condition under the presence of RTTFs. and RTTFs, already reported in previous papers [8], [46], the
These advantages and detrimental effects of TTFs are high magnetic flux density is mainly reduced in the faulty region.
incentives to work in this field of research and to find a reli- Moreover, the defective region remains stationary under the
able and secure procedure to detect TTFs during the machine presence of STTFs, while it rotates at the rotor speed for RTTFs.
startup. Accordingly, it can be concluded that the RMF distortion arising
This article presents a flux-based invasive method to detect from RTTFs is sensed identically by all SCs (similar distortion
TTFs during the startup period (variable frequency) by measur- is observable by all SCs), while the RMF deformation due to
ing the air-gap flux distortion through some search coils (SCs) STTF is more observable by the SC located in the faulty region
installed along the stator circumference. The voltage induced in than by the other SCs.
each SC is proportional to the magnetic flux in the related region. The RMF distortion due to a TTF is sensed by measuring
In healthy conditions, identical magnetic fluxes are seen by the the differential voltage associated to the induced voltages in

Authorized licensed use limited to: The University of Toronto. Downloaded on March 04,2023 at 06:29:30 UTC from IEEE Xplore. Restrictions apply.
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

AFRANDIDEH et al.: DETECTION OF TTFs IN THE STATOR AND ROTOR OF SYNCHRONOUS MACHINES DURING STARTUP 7487

can be found as
⎛ ⎞
⎜ ⎟
Ej (θmk , t) = ωe Ns ϕm cos ⎝ωe t − pθmk ⎠ (2)
     
Em θek

where Ej stands for the instantaneous value of the FC of the


Fig. 1. Stator winding arrangement (four coil groups) of phase B and induced voltage in the jth SC, with amplitude Em = ωe Ns ϕm
the corresponding SCs (left) and the SCs installed in the sample SG in healthy conditions [8].
(right).
The magnetic axes of the winding coil groups and the related
SCs are aligned. Also, each SC embraces entirely each CG of the
winding in each phase. In these conditions, the induced voltage
opposite SCs. As an example, the difference of the induced in each SC can be regarded as a portion of the internal voltage
voltages in SCB1 and SCB3 (ΔEB13 ) is a fingerprint of the flux of the corresponding coil group.
difference in the related regions (coil groups B1 and B3 in Fig. 1). The supply voltage, when the machine runs in the motoring
In other words, the difference of the induced voltages in dual mode, is applied to the series connection of the coil groups in
opposite SCs (ΔEs) can be considered as a suitable signature to each phase. Since they are identical, the voltage across them will
detect TTFs. However, there is an essential difference between be divided equally. So, the generated magnetic fluxes by all coil
the induced voltage components due to STTFs and RTTFs. groups in one phase of the machine are also identical. Taking this
STTFs affect the main component of the ΔEs (with frequency into account, identical magnetic fluxes (including the FC and any
f ), while RTTFs affect the f /p component of the ΔEs, where f time harmonics that may exist in the supply voltages) will be seen
and p are the fundamental frequency component of the induced by the SCs in each phase in healthy conditions, which results
voltages in the SCs and the number of pole-pairs of the SG, in identical induced voltages across them. Since the proposed
respectively. technique uses the differential of the induced voltages in the
In steady-state conditions, the aforementioned signatures for SC pairs, the related harmonics will be neutralized in the ΔEs,
the sample 4-pole, 1500 r/min generator appears as 50 and 25 similarly to the FC. Such conditions are also preserved in the
Hz components for STTFs and RTTFs, respectively. Neverthe- case of an unbalanced voltage source, showing that the proposed
less, during the startup period, the time-dependent frequency technique is insensitive to the power supply harmonics and/or
is initially zero at the starting moment and increases progres- unbalanced conditions.
sively, reaching the rated frequency when the rotor rotates at However, when a fault occurs, the variation of the magnetic
the synchronous speed. So, it becomes necessary to estimate the field along the air-gap circumference is not identical. For in-
frequency during this period in a continuous manner in order to stance if a TTF occurs in a one CG of the stator winding, the
obtain the f and f /p components of the ΔEs (CΔE f and CΔEf/p ) resultant magnetic flux crossing the related SC will be reduced
by using the discrete Fourier transform (DFT) to diagnose the because not only the number of effective turns in the faulty CG
faults and discriminate them. is reduced, but also because reverse ampere-turns are created by
the current flowing through the shorted turns. Thus, the fault will
B. Scientific Base of the Proposed Diagnostic Technique inevitably disturb the symmetrical form of the air gap RMF. In
Each stator phase winding of the test machine includes four such case, the induced voltages in the corresponding SCs cannot
coil groups that are series connected and each CG has three coils. be neutralized, leading to an increase of the related ΔE. In the
In the proposed technique, each CG of the stator is equipped with case of a TTF in the rotor winding, the mentioned magnetic field
a SC in the related magnetic axis. distortion will appear as a rotational one, which will sweep all
Considering an ideal field distribution for this machine, SCs SCs at different points in time. So, all SC pairs will see such
associated to each phase have to observe identical RMFs in faults.
healthy conditions, with the same amplitude and without any
phase shift. However, an electrical phase shift of 120° exists C. Frequency Estimation by Counting the
between the voltages induced in SCs associated to each phase, Reference Samples
as the magnetic axes of the windings are displaced by the same The induced voltages in the SCs are not pure sinusoidal
electrical angle. signals. They contain high-frequency switching and/or noise
By considering only the fundamental component (FC), the components, which cause incorrect frequency estimation, espe-
magnetic flux crossing each SC, can be written as cially during the startup period. As such, a low-pass filter with
a cutoff frequency higher than 50 Hz (e.g., 100 Hz) can be used
ϕ (θm , t) = ϕm sin (ωe t − pθm ) (1)
to eliminate/reduce such unwanted signal components.
where ϕm , ωe , θm = θe /p , and p are the amplitude of the mag- For the sample four-pole SG, two cycles of the induced
netic flux, the electrical angular supply frequency, the mechan- voltages in the SCs are required to calculate CΔE ΔE
f/p (i.e., Cf/2 ), at
ΔE
ical angular position of each SC, and the number of pole-pairs, each time-step. In such conditions, Cf can be calculated by a
respectively [8]. full-cycle DFT. Fig. 2 shows the filtered induced voltage in one of
Applying the Faraday’s law as Ns dϕ/dt, the induced voltage the SCs and the related sign function used to determine the zero
in the jth SCs (named Ej ) with Ns turns (five turns in this article) crossings in order to estimate the frequency f . When the polarity

Authorized licensed use limited to: The University of Toronto. Downloaded on March 04,2023 at 06:29:30 UTC from IEEE Xplore. Restrictions apply.
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

7488 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 68, NO. 8, AUGUST 2021

detection of two cycles from startup, because it needs to count the


first three zcs. Indeed the obtained signal will not be necessarily
started from a zero crossing point and the first two-cycle window
is accessible after detecting the third zero crossing point as
f = fs /( zc(3)−zc(1)
2 ) . After this process, once the next zc is
detected, the frequency will be updated using the second and
fourth zcs, and this process will continue. Indeed, after the
detection of a new zc, the updated values for the CΔE f and CΔE
f/2
components can be obtained, which means one point of these
criteria in each cycle. In other words, a delay time exists between
any two sequential cycles, and this delay time will gradually
reduce as the speed of the machine increases, reaching 20 ms at
the rated frequency, i.e., rated speed.
Fig. 2. Induced voltage in a SC (top), the related sign function, and
the updating of the frequency by measuring the samples in a two-cycle E. Determination of Thresholds for STTF and
window (down).
RTTF Detection
Two threshold values (Th) must be established to discriminate
of the induced voltage in a specified SC changes from negative to the healthy condition from the faulty ones. Such thresholds (ThS
positive, it is considered a zero crossing (zc) of the signal. The for STTFs and ThR for RTTFs) can be set as fixed values for all
number of samples N between two sequential zero crossings frequencies or variable ones with some frequency-dependent
determines the frequency f = N ×T 1
= fNs , where T and fs are criteria. The imposition of fixed values for the thresholds is
the sampling period and sampling frequency, respectively. a simpler process, being the one adopted in this article. In
Such logic can be realized through the sign function (sgn) by this way, CΔEf and CΔE
f/2 are obtained for all ΔEs during the
the following statements: startup period of the healthy machine. The maximum value of
all of them (individually for CΔE
f and CΔE
f/2 ) considering a time
If sgn(Ex [n − 2]) = − 1 and sgn(Ex [n]) = +1 window from the starting instant up to the rated speed/frequency,
⇒ zc (k) = n − 1. (3) and using a safety margin of 20%, allows to obtain adequate
threshold values, as
Indeed, while the polarity of the filtered E changes from ⎧  
⎨ ThS = 1.2 × Max C ΔEs
negative to positive in the nth sample, the related sample in  f  . (7)
that moment is considered as the new (kth) zero crossing. In this ⎩ ThR = 1.2 × Max C ΔEs
f /2
way, the data window will be updated cycle by cycle, so that one
cycle comes out of the data window and a new cycle enters into When the value of CΔE
f exceeds ThS or CΔE
f/2 exceeds ThR , an
it, as shown in Fig. 2. Therefore, the frequency is calculated as indication of a STTF or RTTF condition is issued, respectively.
follow:
F. TTF Detection and Discrimination
zc (k) − zc (k − 2)
f = fs / k = 3, 4, 5, . . . (4)
2 As described in [8] and [46], the consequences of a STTF can
be listed as:
where zc(k), fs and f represent the kth zero crossing, the
1) decrease of the stator ampere-turns amplitude in the faulty
sampling frequency, and the estimated frequency, respectively.
coil due to the bypass of the shorted turns and the reduc-
It should be mentioned that the number of samples per one
tion of the remaining healthy turns;
cycle (N) is calculated based on a two-cycle data window with
2) creation of a reverse ampere-turn in the shorted turns of
(zc(k) − zc(k − 2))/2 elements.
the faulty coil;
The CΔEs
f and CΔEs
f/2 components of the induced voltage can 3) compensation of the reverse current flowing in the shorted
be calculated using the DFT as follows:
turns by the remaining healthy ones in the faulty coil,
zc(k) similar to a transformer.
f  2πf
CfΔEs = ΔEs (m) e−j fs m
(5) It can be concluded that STTFs will manifest themselves by
fs a reduction of the RMF in the faulty area. On the other hand,
m = zc(k−2)+1

zc(k)
under the presence of RTTFs, only the number of active turns
f  πf of the field winding will be reduced, and these turns will not
CfΔEs
/2 = ΔEs (m) e−j fs m . (6)
fs generate any reverse ampere turns. Indeed, the RMF reduction
m = zc(k−2)+1
due to the RTTF in the faulty pole creates an insignificant effect
on the RMF in comparison with a STTF.
D. TTF Detection Technique During Startup
Fig. 3 shows the flowchart of the proposed algorithm to
Initially, the desired components (CΔE
f and CΔE
f/p ) can be detect various TTFs, and discriminate STTFs from RTTFs and
extracted from the ΔEs using the DFT algorithm after the determine the faulty region of STTF during the startup period. As

Authorized licensed use limited to: The University of Toronto. Downloaded on March 04,2023 at 06:29:30 UTC from IEEE Xplore. Restrictions apply.
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

AFRANDIDEH et al.: DETECTION OF TTFs IN THE STATOR AND ROTOR OF SYNCHRONOUS MACHINES DURING STARTUP 7489

Fig. 4. Two-dimension FEM of the sample SG: location of faults (top)


and SCs installed in the stator slots (down).

TABLE I
TECHNICAL SPECIFICATIONS OF THE SAMPLE SG

Fig. 3. Flowchart of the proposed algorithm to detect various TTFs,


discriminate them and identify the faulty region for STTFs.

shown, the filtered analog signals are converted to digital signals TABLE II
using an analog to digital converter (ADC), being one of these DEDICATED SLOTS IN THE SAMPLE SG STATOR FOR COIL GROUPS (CGS)
AND THE RELATED SCS
signals used to estimate the frequency. After the detection of each
zero-crossing point and the estimation of the frequency, CΔE f
and CΔE f/2 are calculated by a full-cycle DFT for the frequencies
f and f /p (f /2 for the four-pole machine in this article),
respectively. Indeed, two cycles of the induced voltage in each
SC will be used to obtain CΔE f/2 , since the sin–cosine filters of
the DFT need to cover two cycles of the signal to obtain the
component at the frequency f /2. After this procedure, CΔE f
and CΔE f/2 will be compared with the related threshold levels,
which are determined when the machine is in healthy conditions.
CΔE
f being higher than ThS or CΔE f/2 being higher than ThR are SG is modeled using a 2-D finite-element model (FEM). Other
fingerprints of STTFs or RTTFs in the machine, respectively. specifications of the machine are listed in Table I.
If a STTF is detected, the maximum ΔE (e.g., ΔExij orig- Fig. 4 shows the model of this machine in Ansoft Maxwell
inated by the induced voltages in SCi and SCj of phase x) v16 environment. The modeled STTF and RTTF regions and
identifies the faulty coil candidates (e.g., ith and jth coils) in the location of the five-turn SCs installed in the stator slots are
the affected phase, and the SC with the lowest induced voltage shown in this figure, too. Although the SC pitch can be chosen
level (CΔE f ) identifies the faulty coil in that phase. identical to the winding pitch (six slots in the test machine), it was
In the case of RTTFs, the faulty region rotates at the rotor selected wider than that so that each SC encompasses entirely
speed. Therefore, all SCs will sense the distortion of the RMF the related coil group. In fact, the final results are insensitive to
as CΔEf/2 is higher than ThR for all differential voltages. this parameter, because the differentials of the induced voltages
across the SCs are used. However, if the SC pitch is selected
smaller than the winding pitch, the resultant FC of the induced
III. IMPLEMENTATION OF THE PROPOSED ALGORITHM voltage in each SC will be reduced. The specified slots for the
USING 2-D FEM
coils (each CG includes three coils) and SCs for the three phases
To verify the performance of the proposed algorithm and its are listed in Table II. For example, the SC of the first CG of phase
capability to detect TTFs, a 380-V, 8-kW, four-pole salient pole A is mounted in slots number 1 and 9.

Authorized licensed use limited to: The University of Toronto. Downloaded on March 04,2023 at 06:29:30 UTC from IEEE Xplore. Restrictions apply.
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

7490 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 68, NO. 8, AUGUST 2021

Fig. 6. Pictures and schematic diagram of the created taps in the coils
of the fourth CG of the phase B and in one pole of the field winding.

Fig. 5. Variation of CΔE


f and CΔE f/2
versus frequency for the simulated
SG in healthy conditions (first row), with a STTF of 5 shorted turns in Fig. 7. Experimental test rig.
phase B (second row) and with a RTTF of 20 shorted turns (third row).

of the proposed technique in real conditions. Several taps are


Fig. 5 shows the evolution of CΔE f and CΔEf/2 for all ΔEs
available in the fourth CG of phase B of the stator windings of
during the startup period of the SG in healthy conditions, and this machine to create various STTFs with different number of
for a STTF with 5 shorted turns in phase B (STTF5B) and a shorted turns (see Fig. 6). Through such taps, artificial TTFs can
RTTF with 20 shorted turns (RTTF20). As can be seen, both be created involving 0.75% up to 25% of the total number of
CΔE
f and CΔE
f/2 for all ΔEs are zero during the startup period
turns of phase B. In addition, taps were also made available
in the healthy condition. Therefore, the threshold value for in a rotor pole winding to create RTTFs with 10 up to 70
detecting STTFs and RTTFs would be exactly zero for an ideal shorted turns (1.5% up to 10% of the whole field winding).
machine (ThS = 0 and ThR = 0). In the face of STTFs, CΔE f
The induced voltages in the SCs are captured by a portable
for some ΔEs will increase with the frequency, and the highest data acquisition module (Advantech card USB-4711A) with a
increase is seen at the rated frequency (CΔE f/2 for all ΔEs are
sampling frequency of 2 kHz, as shown in Fig. 7. The sample
unchanged). Among all differential voltages, ΔEB24 is higher SG has been run in a healthy condition and also with different
than the other ones for all frequencies, meaning that the second STTFs and RTTFs. The induced voltages in the SCs were stored
and fourth coil groups of phase B are the faulty candidates. By during the startup period of the SG and the proposed diagnostic
comparing the induced voltages in SC2 and SC4 in phase B, method implemented using MATLAB. The obtained results are
the actual faulty CG can be identified. For the simulated RTTF, described in the following sections.
CΔE
f/2 of all ΔEs increases with the frequency, while Cf
ΔE
of all
ΔEs remains unchanged. Therefore, it can be concluded that B. Healthy Condition
the proposed technique acts as a secure method to detect both Fig. 8 shows the induced voltages in the SCs (Es), ΔEs, and
types of TTFs and is able to discriminate STTFs from RTTFs the related CΔE and CΔE
f f/2 during the startup of the sample SG in
as well. healthy conditions. The acceleration time of the SG has been set
at 5 s to reach the rated speed, by using an inverter-fed induction
IV. EXPERIMENTAL RESULTS motor as a prime-mover. In such conditions, the threshold values
for fault detection can be obtained. Since the sample SG does
A. Experimental Setup not have an ideal construction, the maximum values of CΔE f
The sample four-pole, 380-V, 8-kW salient pole SG with the and CΔE f/2 are not negligible and the threshold values were set as
specifications in Table I was tested to verify the performance Ths = 0.38 V and ThR = 0.028 V in real conditions.

Authorized licensed use limited to: The University of Toronto. Downloaded on March 04,2023 at 06:29:30 UTC from IEEE Xplore. Restrictions apply.
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

AFRANDIDEH et al.: DETECTION OF TTFs IN THE STATOR AND ROTOR OF SYNCHRONOUS MACHINES DURING STARTUP 7491

Fig. 8. Induced voltages in the SCs (first column), ΔEs (second column), CΔE f (third column), CΔE
f/2
(fourth column), and a zoomed version of the
related signals (bottom) for the sample SG in healthy condition during startup.

EB2
Fig. 9. CΔE
f (first column), CΔE
f/2
(second column), and DFT of the induced voltages in the SCs installed in the candidate faulty coils (Cf and
E
Cf B4 ) (third column) in the face of STTF with five (top) and ten (down) shorted turns in the fourth CG of phase B.

C. STTF Condition observed in ΔEB24 . Since the induced voltage in EB4 is lower
than in EB2 , CGB4 is the faulty coil group.
Fig. 9 shows CΔE
f , CΔE
f/2 ,
and the induced voltages in the
As seen in Fig. 9, a STTF with more shorted-turns increases
candidate faulty coils in the face of STTFs with five and ten
CΔE and clarifies the faulty region with a higher resolution.
shorted turns. As can be seen clearly, the STTF increases CΔEf
f
Moreover, from the security viewpoint, a STTF does not trigger
significantly for all frequencies, while the highest increase is

Authorized licensed use limited to: The University of Toronto. Downloaded on March 04,2023 at 06:29:30 UTC from IEEE Xplore. Restrictions apply.
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

7492 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 68, NO. 8, AUGUST 2021

Fig. 11. Induced voltage in a SC (left) and the related filtered signal
(right) in steady state.

machine is started as a motor fed by a SFC. Threshold levels are


determined in a similar manner to Section B. STTFs are created
manually at about t = 2 s during the starting period (predefined
as 5 s in these tests).
As can be seen, the values of CΔE
f are lower than Ths before
the fault occurrence, while they exceed the related threshold
value after a STTF occurrence.
Similar to the previous cases, the highest ΔE and the min-
imum induced voltage in the related SCs determine the faulty
phase and the related faulty coil group. It can also be seen that
CΔE
f/2 in both cases does not trigger the indication of a RTTF,
demonstrating the fault discriminating ability of the proposed
diagnostic technique. It should be highlighted that just one or
two ΔEs will exceed the ThR at the instant when the STTF was
Fig. 10. CΔEf (first column) and CΔE (fourth column) under the pres-
f/2
ence of RTTFs with 10 (first row), 20 (second row), and 70 (third row)
imposed, but for a true indication of a RTTF, all ΔEs have to
shorted turns. exceed the corresponding threshold value.
In the case of traction drives or similar applications, where
the drive operates in a closed loop [47], the motor supply
the RTTF detection criterion, i.e., CΔE currents are sampled at a much higher sampling rate than the
f/2 does not exceed the
corresponding threshold value. one used in this work. In those cases, the diagnostic technique
proposed in this article can still rely on a system with a rela-
D. RTTF Condition tively low-sampling frequency by considering the use of analog
low-pass filters inserted between the SCs and the acquisition
Fig. 10 shows CΔE f and CΔE
f/2 in the face of RTTFs with hardware. Such filters will remove unwanted high-frequency
10, 20, and 70 shorted turns. As can be seen, RTTFs increase harmonics and avoid the aliasing effect at the same time. The
CΔE
f/2 significantly for all ΔEs along the entire frequency range. other option is to sample the induced voltages in the SCs at the
Also, it can be seen that RTTFs with a higher number of same sampling frequency used by the control system and then
shorted turns increase identically all CΔE
f/2 . Moreover, from the apply digital low-pass filters, although this option imposes an
security viewpoint, RTTFs do not trigger a STTF detection cri- additional burden in terms of memory usage by the diagnostic
terion. In fact, CΔE
f never exceeds the corresponding threshold system.
value.

E. STTF Detection in a SFC-Fed Synchronous Motor F. Sensitivity to the Number of Shorted Turns
To start the machine as a synchronous motor, it must be fed To evaluate the sensitivity of the proposed technique to the
by a static frequency converter (SFC), which starts by imposing number of shorted turns in the stator and rotor windings, some
a supply voltage of low frequency to the motor, reaching the additional experimental results are shown in Fig. 13. As seen, a
rated frequency value during a predetermined time interval. STTF or RTTF, with a specific number of shorted turns, can
In this case, the high-frequency switching pulses caused by be detected more easily at a higher frequency (speed). This
the inverter have to be eliminated and this can be done us- happens because more severe STTFs or RTTFs lead to higher
ing analog low-pass filters. Fig. 11 shows the induced volt- CΔE
f or CΔE
f/2 , respectively. In fact, there is an approximate
age in one SC and the related filtered version, which clearly linear relationship between the fault indexes and the number
shows the necessity of using such filtering circuits at the SCs of shorted turns and frequency. For instance, CΔE f almost dou-
outputs. bles (for STTF5 ) when the frequency is changed from 20 to
Fig. 12 shows CΔE
f and CΔE
f/2 in healthy conditions and in the
40 Hz. A similar behavior can also be seen in the case of
presence of STTFs with five and ten shorted turns, when the RTTFs.

Authorized licensed use limited to: The University of Toronto. Downloaded on March 04,2023 at 06:29:30 UTC from IEEE Xplore. Restrictions apply.
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

AFRANDIDEH et al.: DETECTION OF TTFs IN THE STATOR AND ROTOR OF SYNCHRONOUS MACHINES DURING STARTUP 7493

EB2
Fig. 12. CΔE
f (first column), CΔE
f/2
(second column), and DFT of the induced voltages in the SCs installed in the candidate faulty coils (Cf and
E
Cf B4 )(third column) in healthy condition (first row) and in the presence of STTFs with five (second row) and ten (third row) shorted turns in the
fourth CG of phase B when the machine starts as a motor fed by a variable frequency converter.

The performance of the proposed technique was verified by


simulation and experimental results. In addition, the perfor-
mance and security of this method were proven for the sample
machine when it operated as a generator and motor (fed by a
SFC).
The experimental results demonstrated that the proposed
method was capable of detecting and discriminating TTFs in the
rotor involving 1.5% of the number of turns per pole of the field
winding, and in stator involving 3% of the number of turns of the
Fig. 13. CΔE
f for ΔEB24 during STTF occurrence (left) and CΔE f/2
for
stator winding of the sample machine. Furthermore, this method
average of ΔEs during RTTFs (right) for three different frequencies: 20,
30, and 40 Hz. was able to identify the faulty region in the stator windings
during the startup period.
V. CONCLUSION
A flux-based technique was proposed in this article to detect REFERENCES
and discriminate stator and rotor TTFs during the startup period [1] IEEE Recommended Practice for the Design of Reliable Industrial and
of synchronous machines, using the induced voltages in some Commercial Power Systems, IEEE Standard 493, 2007.
SCs mounted along the circumference of the machine air-gap. [2] G. Klempner and I. Kerszenbaum, Handbook of Large Turbo-Generator
Operation and Maintenance, vol. 38. Hoboken, NJ, USA: Wiley,
The rotor speed (and accordingly the frequency) was estimated 2011.
using the induced voltage in one of the search coils. The DFT [3] G. C. Stone, E. A. Boulter, I. Culbert, and H. Dhirani, Electrical Insulation
was used to extract the f and f /p components of the air-gap for Rotating Machines: Design, Evaluation, Aging, Testing, and Repair,
vol. 21. Hoboken, NJ, USA: Wiley, 2004.
flux distortion, which was obtainable through the difference of [4] M. Šašić, B. Lloyd, and A. Elez, “Finite element analysis of turbine
the induced voltages in corresponding SCs that have identical generator rotor winding shorted turns,” IEEE Trans. Energy Convers.,
values in healthy conditions. vol. 27, no. 4, pp. 930–937, Dec. 2012.

Authorized licensed use limited to: The University of Toronto. Downloaded on March 04,2023 at 06:29:30 UTC from IEEE Xplore. Restrictions apply.
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

7494 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 68, NO. 8, AUGUST 2021

[5] Z. Zhou, Y. Wang, W. Guo, B. Li, and J. Mao, “Fault identification of [26] P. Neti and S. Nandi, “Stator interturn fault detection of synchronous ma-
turbine generator rotor system based on spectrum monitor and analysis,” chines using field current and rotor search-coil voltage signature analysis,”
in Proc. Asia-Pacific Power Energy Eng. Conf., 2011, pp. 1–5. IEEE Trans. Ind Appl., vol. 45, no. 3, pp. 911–920, May-Jun. 2009.
[6] H. Ma and L. Pu, “Fault diagnosis based on ANN for turn-to-turn short [27] M. Cuevas, R. Romary, J.-P. Lecointe, and T. Jacq, “Non-invasive detection
circuit of synchronous generator rotor windings,” J. Electromagn. Anal. of rotor short-circuit fault in synchronous machines by analysis of stray
Appl., vol. 3, pp. 187–191, 2009. magnetic field and frame vibrations,” IEEE Trans. Magn., vol. 52, no. 7,
[7] L. Wang, Y. Li, and J. Li, “Diagnosis of inter-turn short circuit of syn- Jul. 2016, Art. no. 8105304.
chronous generator rotor winding based on volterra kernel identification,” [28] J. S. Hsu and J. Stein, “Shaft signals of salient-pole synchronous machines
Energies, vol. 11, 2018, Art. no. 2524. for eccentricity and shorted-field-coil detections,” IEEE Trans. Energy
[8] H. Dehghan, F. Haghjoo, and S. M. A. Cruz, “A flux-based differential Convers., vol. 9, no. 3, pp. 572–578, Sep. 1994.
technique for turn-to-turn fault detection and defective region identifica- [29] W. Yucai and L. Yonggang, “Diagnosis of short circuit faults within
tion in line-connected and inverter-fed induction motors,” IEEE Trans. turbogenerator excitation winding based on the expected electromotive
Energy Convers., vol. 33, no. 4, pp. 1876–1885, Dec. 2018. force method,” IEEE Trans. Energy Convers., vol. 31, no. 2, pp. 706–713,
[9] Y. Bai, S. Wang, A. Zhang, X. Wang, and J. Mao, “A novel concept of Jun. 2016.
permanent magnet synchronous generators with automatic turn-to-turn [30] W. Yucai and L. Yonggang, “Diagnosis of rotor winding interturn short-
short-circuit fault-tolerance capability,” IEEE Trans. Energy Convers., circuit in turbine generators using virtual power,” IEEE Trans. Energy
vol. 34, no. 1, pp. 98–108, Mar. 2018. Convers., vol. 30, no. 1, pp. 183–188, Mar. 2015.
[10] P. Arumugam, T. Hamiti, C. Brunson, and C. Gerada, “Analysis of vertical [31] M. Cuevas, R. Romary, J.-P. Lecointe, F. Morganti, and T. Jacq, “Noninva-
strip wound fault-tolerant permanent magnet synchronous machines,” sive detection of winding short-circuit faults in salient pole synchronous
IEEE Trans. Ind. Electron., vol. 61, no. 3, pp. 1158–1168, Mar. 2013. machine with squirrel-cage damper,” IEEE Trans. Ind Appl., vol. 54, no.
[11] P. Arumugam, T. Hamiti, and C. Gerada, “Analytical modeling of a 6, pp. 5988–5997, Nov.-Dec. 2018.
vertically distributed winding configuration for fault tolerant permanent [32] M. Irhoumah, R. Pusca, E. Lefevre, D. Mercier, R. Romary, and C.
magnet machines to suppress inter-turn short circuit current limiting,” in Demian, “Information fusion with belief functions for detection of in-
Proc. IEEE Int. Elect. Mach. Drives Conf., 2011, pp. 371–376. terturn short-circuit faults in electrical machines using external flux
[12] P. Arumugam, T. Hamiti, and C. Gerada, “Modeling of different wind- sensors,” IEEE Trans. Ind. Electron., vol. 65, no. 3, pp. 2642–2652,
ing configurations for fault-tolerant permanent magnet machines to re- Mar. 2018.
strain interturn short-circuit current,” IEEE Trans. Energy Convers., [33] L. Hao, Y. Sun, A. Qiu, and X. Wang, “Steady-state calculation and online
vol. 27, no. 2, pp. 351–361, Jun. 2012. monitoring of interturn short circuit of field windings in synchronous
[13] A. Doorwar, B. Bhalja, and O. P. Malik, “A new internal fault detection and machines,” IEEE Trans. Energy Convers., vol. 27, no. 1, pp. 128–138,
classification technique for synchronous generator,” IEEE Trans. Power Mar. 2011.
Del., vol. 34, no. 2, pp. 739–749, Apr. 2018. [34] D. R. Albright, “Interturn short-circuit detector for turbine-generator rotor
[14] S. M. A. Cruz and A. J. M. Cardoso, “Stator winding fault diagnosis in windings,” IEEE Trans. Power App. Syst., vol. PAS-90, no. 2, pp. 478–483,
three-phase synchronous and asynchronous motors, by the extended Park’s Mar. 1971.
vector approach,” IEEE Trans. Ind Appl., vol. 37, no. 5, pp. 1227–1233, [35] M. Sasic, G. C. Stone, J. Stein, and C. Stinson, “Detecting turn shorts in
Sep./Oct. 2001. rotor windings: A new test using magnetic flux monitoring,” IEEE Ind.
[15] M. A. Mazzoletti, G. R. Bossio, C. H. De Angelo, and D. R. Espinoza- Appl. Mag., vol. 19, no. 2, pp. 63–69, Mar.-Apr. 2012.
Trejo, “A model-based strategy for interturn short-circuit fault diagnosis [36] W. Yucai, M. Minghan, and L. Yonggang, “A new detection coil capable
in PMSM,” IEEE Trans. Ind. Electron., vol. 64, no. 9, pp. 7218–7228, of performing online diagnosis of excitation winding short-circuits in
Sep. 2017. steam-turbine generators,” IEEE Trans. Energy Convers., vol. 33, no. 1,
[16] S. Nadarajan, S. K. Panda, B. Bhangu, and A. K. Gupta, “Online model- pp. 106–115, Mar. 2017.
based condition monitoring for brushless wound-field synchronous gen- [37] W. Yucai, M. Qianqian, and C. Bochong, “Fault diagnosis of rotor wind-
erator to detect and diagnose stator windings turn-to-turn shorts using ing inter-turn short circuit for sensorless synchronous generator through
extended Kalman filter,” IEEE Trans. Ind. Electron., vol. 63, no. 5, screw,” IET Elect. Power Appl., vol. 11, no. 8, pp. 1475–1482, Sep. 2017.
pp. 3228–3241, May 2016. [38] IEEE Guide for Control of Hydroelectric Power Plants, IEEE Std 1010-
[17] C. Wang, X. Liu, and Z. Chen, “Incipient stator insulation fault detection of 2006, Aug. 2006.
permanent magnet synchronous wind generators based on Hilbert–Huang [39] B. Li, Z. Duan, X. Wang, and J. Wu, “Loss-of-excitation analysis and
transformation,” IEEE Trans. Magn., vol. 50, no. 11, pp. 1–4, Nov. 2014. protection for pumped-storage machines during starting,” IET Renewable
[18] N. Yassa and M. Rachek, “Modeling and detecting the stator winding inter Power Gener., vol. 10, pp. 71–78, 2016.
turn fault of permanent magnet synchronous motors using stator current [40] U. Karaagac, J. Mahseredjian, and S. Dennetière, “Modeling and simu-
signature analysis,” Math. Comput. Simul., vol. 167, pp. 325–339, 2018. lation of the startup of a pumped storage power plant unit,” in Proc. Int.
[19] J.-C. Urresty, J.-R. Riba, and L. Romeral, “Application of the zero- Conf. Power Syst. Transients, Kyoto, Japan, Jun. 3–6, 2009, pp. 1–7.
sequence voltage component to detect stator winding inter-turn faults in [41] D. N. Konidaris, “Investigation of back-to-back starting of pumped storage
PMSMs,” Elect. Power Syst. Res., vol. 89, pp. 38–44, 2012. hydraulic generating units,” IEEE Trans. Energy Convers., vol. 17, no. 2,
[20] M. van der Geest, H. Polinder, J. A. Ferreira, A. Veltman, J. J. Wolmarans, pp. 273–278, Jun. 2002.
and N. Tsiara, “Analysis and neutral voltage-based detection of interturn [42] F. Haghjoo, M. Mostafaei, and M. Mohammadzadeh, “A novel flux-based
faults in high-speed permanent-magnet machines with parallel strands,” protection scheme for power transformers,” in Proc. 9th Power Syst.
IEEE Trans. Ind. Electron., vol. 62, no. 6, pp. 3862–3873, Jun. 2015. Protection Control Conf., 2015, pp. 25–30.
[21] J. Arellano-Padilla, M. Sumner, and C. Gerada, “Winding condition mon- [43] M. Mostafaei and F. Haghjoo, “Flux-based turn-to-turn fault protec-
itoring scheme for a permanent magnet machine using high-frequency tion for power transformers,” IET Gener., Transmiss. Distrib., vol. 10,
injection,” IET Elect. Power Appl., vol. 5, pp. 89–99, 2011. pp. 1154–1163, 2016.
[22] S. Nadarajan, S. K. Panda, B. Bhangu, and A. K. Gupta, “Hybrid model [44] M. F. Cabanas et al., “A new online method based on leakage flux
for wound-rotor synchronous generator to detect and diagnose turn-to-turn analysis for the early detection and location of insulating failures in power
short-circuit fault in stator windings,” IEEE Trans. Ind. Electron., vol. 62, transformers: Application to remote condition monitoring,” IEEE Trans.
no. 3, pp. 1888–1900, Mar. 2015. Power Del., vol. 22, no. 3, pp. 1591–1602, Jul. 2007.
[23] T. Ghanbari and A. Farjah, “A magnetic leakage flux-based approach [45] S. Hajiaghasi, K. Abbaszade, and H. Paidarnia, “A new method for mod-
for fault diagnosis in electrical machines,” IEEE Sens. J., vol. 14, no. eling and analyzing the increments of leakage flux in power transformer
9, pp. 2981–2988, Sep. 2014. in inter-turn fault condition,” in Proc. 28th Int. Power Syst. Conf., Tehran,
[24] Y. Da, X. Shi, and M. Krishnamurthy, “A new approach to fault diagnostics Iran, 2013, pp. 14–48.
for permanent magnet synchronous machines using electromagnetic signa- [46] Y. Soleimani, S. M. A. Cruz, and F. Haghjoo, “Broken rotor bar de-
ture analysis,” IEEE Trans. Power Electron., vol. 28, no. 8, pp. 4104–4112, tection in induction motors based on air-gap rotational magnetic field
Aug. 2013. measurement,” IEEE Trans. Instrum. Meas., vol. 68, no. 8, pp. 2916–2925,
[25] H. Yaghobi, K. Ansari, and H. R. Mashhadi, “Stator turn-to-turn fault Aug. 2018.
detection of synchronous generator using total harmonic distortion (THD) [47] H. Chen and B. Jiang, “A review of fault detection and diagnosis for the
analyzing of magnetic flux linkage,” Iranian J. Sci. Technol. Trans. Elect. traction system in high-speed trains,” IEEE Trans. Intell. Transp. Syst.,
Eng., vol. 37, pp. 161–182, 2013. vol. 21, no. 2, pp. 450–465, Feb. 2019.

Authorized licensed use limited to: The University of Toronto. Downloaded on March 04,2023 at 06:29:30 UTC from IEEE Xplore. Restrictions apply.
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

AFRANDIDEH et al.: DETECTION OF TTFs IN THE STATOR AND ROTOR OF SYNCHRONOUS MACHINES DURING STARTUP 7495

Saeed Afrandideh received the B.Sc. degree Sérgio Cruz (Senior Member, IEEE) received
in electrical engineering from Shahid Chamran the E.E. diploma, and the M.Sc. and Dr.Eng.
University, Rasht, Iran, in 2016, and the M.Sc. degrees in electrical engineering from the Uni-
degree in electrical engineering from the De- versity of Coimbra, Coimbra, Portugal, in 1994,
partment of Electrical Engineering, Abbaspour 1999, and 2004, respectively.
School of Engineering, Shahid Beheshti Univer- He has been with the University of Coim-
sity, Tehran, Iran, in 2019. bra, Department of Electrical and Computer En-
His current research interests include rotating gineering, where he is currently an Associate
electrical machines protection by using digital Professor and the Director of the Electric Ma-
signal processing. chines Laboratory. His teaching and research
interests include power transformers, rotating
electric machines, electric drives, and power electronic converters, with
special emphasis on fault diagnosis, fault tolerance, and digital control.

Farhad Haghjoo (Senior Member, IEEE) re-


ceived the B.Sc. degree in electrical engineer-
ing from the Isfahan University of Technology,
Isfahan, Iran, in 1991, the M.Sc. degree in elec-
trical engineering from the University of Tehran,
Tehran, Iran, in 1994, and the Ph.D. degree in Mostafa Eshaghi Milasi received the B.Sc.
electrical engineering from the Iran University of degree in electrical engineering from Islamic
Science and Technology, Tehran, in 2010. Azad University, Najaf Abad, Iran, in 2016, and
He is currently an Associate Professor and the M.Sc. degree in electrical engineering from
the Director of the HV/MV Equipments Protec- the Department of Electrical Engineering, Ab-
tion Research Laboratory (HV/MV EPRL), De- baspour School of Engineering, Shahid Be-
partment of Electrical Engineering, Abbaspour School of Engineering, heshti University, Tehran, Iran, in 2019.
Shahid Beheshti University, Tehran. His main research interests include His main research interests include digital sig-
application of digital signal processing for online condition monitoring, nal processing and rotating electrical machines
fault diagnosis, and online protection of HV/MV equipments. protection.

Authorized licensed use limited to: The University of Toronto. Downloaded on March 04,2023 at 06:29:30 UTC from IEEE Xplore. Restrictions apply.

You might also like