You are on page 1of 6

Downloaded from https://iranpaper.

ir
https://www.tarjomano.com https://www.tarjomano.com
The 9th Power Systems Protection & Control Conference (PSPC20 15)
January 14-15,20 15, AmirkabirUniversity of Technology,Tehran,Iran

Turn to Turn Fault Detection and Classification in


Stator Winding of Synchronous Generators Based on
Terminal Voltage Waveform Components

Mohammad Fayazi Farhad Haghjoo


Electrical Engineering Dept. Electrical Engineering Dept.
Shahid Beheshti University, Shahid Abbaspour Campus Shahid Beheshti University, Shahid Abbaspour Campus
Tehran/Iran Tehran/Iran
M fayazi69 @ace.sbu.ac.ir f haghjoo@sbu.ac.ir

Abstract- In this paper, a novel method is presented to detect reduction of EMF in the faulted phase, through the tertiary
and classify turn-turn faults (TTF) in stator winding of the winding of the voltage transformer connected to generator
synchronous generators on the basis of resulting harmonics winding terminals [I].
contents in the terminal voltage waveforms. Analytical results by
using Decision Tree (DT) show that this algorithm is practicable
Whereas the above schemes cannot detect weak faults (such
using only the first harmonic of residual voltage and only two as single tum-tum ones), other methods had been proposed to
harmonic component values. Simulations in Maxwell software achieve this goal,on the basis of consider a model for the stator
are done using Fuji's technical documents and data sheets of an winding, to analyze internal faults in synchronous generators.
actual salient pole synchronous generator (one unit of an Iran's The first literature [3 ],which had been proposed by Park,is the
hydroelectric power plants) and all of related parameters (such well-known dqO model that a sinusoidal distribution is assumed
as B-H curve, unsymmetrical air gap and pole saliency, slot-teeth for machine winding. Using such model, only the fundamental
effect, and so on) are considered to obtain a comprehensive component is recognized and all higher space harmonics
model, without any simplifier assumption. produced by the machine windings are neglected. However,
when a TTF occurs in the machine, the winding distribution is
Keywords- Synchronous Generator, Turn-Turn Fault, no longer sinusoidal and significant space harmonics will be
Detection, Classification, Harmonic Components, Decision Tree. produced in the air-gap magnetic field. Due to the
inconvenience of the dqO model for internal faults modeling,
I. INTRODUCTION other models were generally derived in the phase domain [4 -
9 ], where the voltage and flux linkage equations were directly
Considering the importance of synchronous generators
developed in the fixed phase reference. These fault models
protection due to their essential role in the power system,
assume that the ratio between the winding inductances is
different algorithms to detect TTFs in stator winding of
proportional to the ratio between the effective numbers of
synchronous generators are presented and studied.
winding turns. However, this can be acceptable when the
The best general form of stator protection from phase-to­ windings are concentrated or a pure sinusoidal distribution of
phase and phase to ground is provided by an instantaneous magneto motive force (MMF) exists in the air gap.
longitudinal percentage biased differential relay. TTFs on the
A synchronous machine model has been presented in [10 -
same phase of the stator winding does not disturb the balance
16] to analyze internal faults based on the modified winding
between the currents in the neutral and the termination CTs,
function theory using machine electrical parameters. Although
and then this type of faults cannot be detected by such
all space harmonics generated by the windings were accounted
protective scheme,while it is possible by transverse differential
by this model, assumption of sinusoidal distribution is not
protection when the generator has (only) two windings per
realistic for large salient pole synchronous generators.
phase [1].
The combined winding function theory and direct phase
In the case of a stator winding with two or more branches
quantities to simulate internal faults in the synchronous
connected in parallel for each phase, it is preferable to apply a
machines were used in [17-19 ], where only the odd space
circulating or a differential current for the TTF detection.
harmonics are included in the calculation of the winding
During TTFs on the windings with parallel branches, the
inductances, while the faulty windings can produce some
current distribution in those branches is changed and the
harmonics and even fractional sub-harmonics.
current circulating between those branches is used for the fault
registration in current differential method [2]. Another model had been presented [18] to simulate
synchronous machine by a multi-loop circuit formed by coils
Generators having single winding per phase or those
that are moving relative to each other. The calculation of the
generators whose parallel windings are not accessible can be
loop inductance is however based on coil-to-coil approach.
protected by using zero component of voltage caused by

9 78-1-4 799 -8157-1/15/$3 \.00 ©20 15 IEEE 36


Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

Therefore, it is very difficult to apply TTF to this model, II. MODELIN G OF SYNCHRONOUS GENERATOR
especially for large machines with a lot of coils in stator. Other
To generate the request signal waveforms, a hydroelectric
technique for partitioning stator winding had been proposed in
synchronous generator (designed by Fuji's Company) is
[20 ],which the air-gap space harmonics were neglected.
selected and simulated using Maxwell software. This generator
Numerical algorithms to measure harmonics or statistical is operating now in one of Iran's powerhouses with the
value are other proposed methods to detect failures in the stator specifications listed in Table I. A section of this generator (with
windings. For example, in [21] the Principal Component details) in Maxwell software is shown in Fig. 1.
Analysis (PCA) had been used to detect stator winding faults.
This method cannot detect weak TTFs or faults near the neutral TABLE I. SPECIFICATIONS OF THE SIMULATED SALIENT POLE
point. Another protective method, which uses the 3th harmonic SYNCHRONOUS GENERATOR
voltage in the neutral point and stator terminations [22], not
Stator Inner
only cannot exhibit high sensitivity, but also the related setting 4500 300 MVA Rating
Diameter (mm)
changes in a wide range while the operating condition varies. Stator Outer Voltage Rating
5770 18
Diameter (mm) (kV)
TTFs create some distortions in the air gap flux
Stator Height Current Rating
configuration and reduce and deform the induced voltage 3041 9642
(mm) (A)
waveform in the same phase. Also, some distortions can be Nominal Power
180 Number of Slots 0.9
induced in the other phase voltage waveforms, simultaneously. Factor
This voltage reduction and distortion value depends on the Two Layer 500 Rotation Speed
Winding Type
number and location of the faulty turns. Therefore, in contrary Stator Bars (rpm)
to what has been said in various references, three phases of the 3 Number of Phases 50 Frequency (Hz)
generator cannot be considered as separated ones, and whose Number of Parallel Nominal Excit.
3 230
interactions cannot be neglected. Circuits Voltage (V)
Nominal Excit.
13 Winding Pitch 2157
To simulate the aforementioned dependencies, presented Current (A)
simulations in this paper are done using FEM algorithm in 20 Turns/Circuit 12 Number of Poles
Maxwell software, with considering the effect of the following Rotor Outer
10392/500 Grounding TTR 4398
items: Diameter (mm)
Shaft Outer
Ground Resistance 2300
Diameter (mm)
1.98 at Secondary Side
Y Poles saliency and air gap irregularity; Air Gap Length
(Ohm) 51
Y Magnetic nonlinear characteristic (Core saturation); (mm)

Y Stator edge (slot-teeth);


Y Mutual inductance of the phases;
Y Air gap flux distortion and its effect on other phases
and windings.

Moreover, not only bars dimensions but also even


insulation between them are modeled based on manufacturer's
(Fuji) technical document plans and data sheets,and so, no any
important parameter is neglected in these simulations.
Therefore, it can be claimed that against the mentioned models
(that had been attempted to fmd a compact and simple model to
simulate the faulty machine treatment), a comprehensive and
precised model is presented in this paper, without any
simplification.

In this paper, various TTFs are detected and classified


based on appeared distortions in the three phase terminal
voltage waveforms (the generated harmonic components).
These voltage waveforms are available through the installed PT
Fig. I. A section of the simulated synchronous generator.
at the generator terminals.

Since detection algorithms based on the fewer input


III. SIMULATION OF TTFS
parameters are preferred to others, DT algorithm is applied to
extract the best harmonic components (obtained by DFT In this section, various TTFs are simulated on the
process) to detect and classify the TTFs (determination of the machine's FEM model to generate distorted voltage
faulty phase and the number of shorted turns). waveforms. Generator works in no load condition, and all of
the simulated TTFs are selected on the basis of actual location
of the bars installed in the stator slots. Indeed, if two bars
installed in one slot belong to a branch of a phase, a TTF can
be occurred between them; otherwise it is impossible to form

37
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

such fault. Number of the possible TTFs in one branch/phase in Table III shows and compares some of harmonic contents
the stator winding is listed in Table [I. The three phase voltage for above-mentioned cases, while Fig. 3 shows them,
waveforms for some sample cases are shown in Fig. 2. individually, during above TTFs. The normal condition is
shown by'NC'.
As shown,the apparent voltage drop in the faulty phase and
voltage distortion in other phases caused by a single TTF is It is an important property in these simulations that the
very small, so that the related deformations can only be results of occurrence a specific TTF on various paralleled
observed by using an digital signal processing algorithm, such branches in each phase are identical. Also the effect of
as OFT or wavelet transform (WT). Increasing number of occurrence a TTF in phase U on healthy adjacent phase V (it
shorted turns results in a rising in the related distortions,so that can be shown by UF-7VH) is exactly similar to VF-7WH or
their deformations are more detectable. WF-7UH• Reversely, UF-7WH, WF-7VH and VF-7UH are the
same, too. This is because of the exact symmetrical and
Since, harmonic components of three phase voltage
balanced distribution of the three phase bars along the stator
waveforms (single phase and cumulative results as U+V+W
circumference. Therefore, it is possible to train DT with the
that can be considered as the output of an open delta connected
proper shifted data,to detect and classify TTFs in other phases.
PTs) are used to detect TTFs,the percentage of the 2nd up to the
Also,TTFs on other parallel circuits in each phase (where these
7th harmonic components (related to the flrst fundamental part)
parallel circuits are located sequentially along the stator
are extracted to train DT. It is noticeable that only a few of
circumference by a 1200 shifting) result in similar outputs.
them are required and used, whenever OT trains and chooses
Then, using the mentioned simulations (totally 60 times), DT
its discrimination criteria.
can access to any TTF data that can be happened.

10.00 10.00

_ 5.00 5.00

� 0.00 0.00

-5.00 -5.00

-10.00 -10.00

TIme [ms]

10.00 10.00

5.00 5.00
� �
� E a.DO

0.00

� :g
·5.00 -5.00

·10.00

1.500

10.00 10.00

I
5.00 5.00

� �
8, 0.00
"
:g
/ g, 0.00
g

}�
·5 00 ..s.00

-10.00 ·10.00
.... _._ ..,/ ....
1.450 1.460 1.470 1.480 1.490 1.500 1.450 1.460 1.470 1.480 1.490 1.500
�� ��
Fig 2. Generated terminal voltage waveforms for a) Normal no load condition, b) Case'S', c) Case'D', d) Case 'T', e) Case'Qd', f) Case'Qn'.

TABLE II. NUMBER OF POSSIBLE TTFs


As case studies, some TTFs on the first branch of phase U
are simulated,as follows: TTF type Number of Possible Cases

Single TTF 20
o Single TTF on the [5t tum (Case'S'),
o Double TTF on the 15t up to 2nd turns (Case'D'), Double TTF 16

o Triple TTF on the 15t up to 3rd turns (Case'T'), Triple TTF 12


o Quadruple TTF on the 15t up to 4th turns (Case'Qd'), Quadruple TTF 8
o Quintuple TTF on the I st up to 5th turns (Case'Qn').
Quintuple TTF 4

38
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

Total 60
.... Uh3/Uhl % "Vh3/Vhl % ..... Wh3!Whl %
10--
TABLE III. VARIATION OF HARMONICS RELATIONS AND THE FIRST

f���;;�;�;;�����������
HARMONIC COMPONENT OF THE RESIDUAL VOLTAGE (SUMMATION OF THREE 8
PHASE VOLTAGES ) IN VARIOUS CASES

-
6

The First Harmonic

Ij +---
Phase h3/hl h4/hl
010 0/0 of Residual Voltage
lI+V+W
-
U 5.710 82e-6
NC V 5.710 82e-6 650e-6 case 'NC' case '5' case '0' case T' case 'Qd' case 'Qn'
W 5.710 82e-6
U 6.380 0.407 .... Uh4!Uhl % "Vh4/Vhl % _Wh4!Whl %
Case S V 6.358 0.227 0.281 1.6 r
W 6.370 0.113 ------------------=-.c---
1.4 +L-
U 6.741 0.713
1.2
Case D V 6.945 0.486 0.5425
W 7.059 0.123
U 6.996 0.836 0.8 +-------------,=--__...-_o;;;�
;::;o ----
Case T V 7.538 0.790 0.9096 0.6 .-------7"''''--�.-£--''"''_=_--
W 7.697 0.067
0.4 +------1"--:7'''''------------'''-
- -
U 7.323 0.753
Case Qd V 8.179 1.145 1.107
W 8.293 0.058
U 7.918 0.443 case 'NC' case'S' case '0' case T' case 'Qd' case 'Qn'

Case Qn V 8.812 1.488 1.26


.... Fund. Compo (U+V+W) (kV)
W 8.839 0.222
1.4.,-----
1.2 .J.--------------------:-:;;;�=-
;;ifO' -
[v. EXTRACTION THE ApPROPRIATE HARMONIC COMPONENTS

To obtain the useful hannonic components to detect and O.B


classify TTFs, DT algorithm is applied to various TTFs
0.6 +------,�-
hannonic components and the healthy terminal voltage
waveforms. The best components values will be selected by 0.4 +-------=-,,£--

DT at the highest decision branches as the main classifier 0.2


criteria,while 70% of the data are used to train DT and 30% of O +-���---�--�---�--�--__,
them are employed to test it. DT behavior to achieve such case 'NC' case'S' case '0' case T' case 'Qd' case 'Qn'

detector and classifier is shown in Fig. 4 , as a flowchart. As


shown, the third and fourth harmonics of individual phase Fig 3. Variations of the third (top) and fourth (mid) harmonic components and
voltage waveforms and the first harmonic of the residual the first harmonic of the residual voltage (down) during various cases related
voltage (U+V+W) are selected by DT to do this task. to normal condition

� All of possible TTFs can be detected with accuracy


V. ANALYSIS OF RESULTS
[ 00%,
The results of the proposed algorithm performance for the
� The number of shorted turns can be classified with
simulated TTFs detection and classification in the stator
winding of synchronous generator are summarized in Table IV. accuracy about 100%
This table shows that: � The related faulty phases can be detennined by
accuracy about 99%.

Finally,a total accuracy of 99 .64% is obtained by DT.

TABLE IY. THE ACCURACY OF THE PROPOSED METHOD FOR THE


INTERTURN FAULTS DETECTION AND CLASSIFICATION IN THE STATOR WINDING
OF SYNCHRONOUS GENERATOR

Obtained Train Test


Cumulative
Accuracy for (133 samples) (51 Samples)
Fault Detection 100% 100% 100%
Phase Detection 100% 96.07% 98.91%
TTFs Classific. 100% 100% 100%
Total Performance Accuracy 99.64%

39
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

VI. CONCLUSIONS In the presented simulations, all of the machine parameters,


such as magnetic hysteresis, core saturation, slot-teeth effect,
In this paper,an analytical method is proposed to detect and
winding distribution, poles saliency and air gap irregularity,
classify TTFs in synchronous generators based on some
magnetic nonlinearity (core saturation), stator edge (slot-teeth),
harmonic components of the terminal voltage waveforms. To
bars dimensions and even insulation between them flux
achieve this aim, an actual 300MVA, 18 kV, 12 poles
hydroelectric synchronous generator is simulated using FEM in
distortion and its effect on other phases and windin s are �
considered, through the FEM algorithm in Maxwell software,
Maxwell software, and DT is employed to extract the
based on Fuji's technical documents, plans and data sheets.
significant and proper harmonic components. It is shown that
Theref�re, it can be claimed that a comprehensive and precised
using only the third and forth harmonic components of
model IS presented and used to TTFs simulations.
individual terminal voltage waveforms (available from terminal
PTs) and the fundamental component of residual voltage
waveform,not only all of TTFs in stator winding are detectable
but also the related phases can be determined by accuracy
about 99%. Also, the number of shorted turns can be
determined completely.

U_Waveform
V_Waveform
W_Wavefonn
Nonnal condition(NC)
0
SingleTTF
0
Calculate
hl(U+V+W)
DoubleTTF
0
(h3!hl)U%
(h3!hl)V%
TripleTTF
Q
(h3!hl)W%
(h4!hl)U%
(h4!hl)V%
QuadrupleTTF
0
(h4!hl)W%
QuintupleTTF
e

Fig 4. Flowchart of DT operation

REFERENCES

40
Downloaded from https://iranpaper.ir
https://www.tarjomano.com https://www.tarjomano.com

[1] Power System Protection and switchgear, B. Ravindranath, M. Chander, [20] M. Rahnama, 1. Nazarzadeh, "Synchronous Machine Modeling and
2005,new age international (P) limited publishers. IEEE International Conference
Analysis for Internal Faults Detection",
[2] ABB Lecture, "Generator and Transformer Protection", 3'd Edition, on Electric Machines and Drives(IEMDC '07), Vol. 2, p.p. 997-1002,
1998. 2007.
[3] P. H. Park, "Two reaction theory of synchronous machine", AlEE [21] N. Yadaiah, N. Ravi, "Statistical Method for Fault Detection in
Transaction,vol. 48,p.p. 716-730,Jul. 1929. Synchronous Generators",International Conference on Computer
Communication and Informatics (ICCCI-2012),p.p. 1-4,Jan 2012.
[4] K. W. Louie, "A New Accurate Phase-Domain Synchronous Generator
Canadian Conference on Electrical and
Model for Transient Simulation", [22] A. B. Dehkordi, D. S. Ouellette, P. A. Forsyth, "Protection testing of a
Computer Engineering(CCECE '06),p.p. 2245-2248,2006. 100% stator ground fault using a phase domain synchronous machine
model in real time", 10th lET International Conference on
[5] D. D. S. Muthumuni,P. G. McLaren,E. Dirks,"Internal fault simulation
Developments in Power System Protection(DPSP 2010), p.p. 1-5, April
in synchronous machines",in: Canadian Conference On Electrical and
2010.
Computer Engineering,Vol. 2,p.p. 1202-1206,May 2000.
[6] A. I. Megahed, O. P. Malik, "Simulation of internal faults in
synchronous generators",IEEE Transactions on Energy Conversion,
Vol. 14,p.p. 1306-1311,Dec 1999.
[7] A. I. Megahed, O. P. Malik, "Synchronous Generator Internal Fault
Computation and Experimental lEE proceeding
Verification",
Generation, Transmission and Distribution, Vol. 145, p.p. 604-610,
1998.
[8] P. Subramaniam and O. P. Malik, "Digital simulation of a synchronous
generator in direct phase quantities", lEE Proceeding of the institution
Electrical Engineers,Vol. 118,p.p. 153-160,Jan 1971.
[9] D. D. S. Muthumuni, P. G. McLaren, E. Dirks and V. Pathirana, "A
synchronous machine model to analyze internal faults",Thirty-sixth lAS
annual Industry Applications Conference,Vol. 3,p.p. 1595-1600,2001.
[10] X. Tu, L. Dessaint, M. E. Kahel, A. O. Barry, "A New Model of
Synchronous Machine Internal Faults Based on Winding Distribution",
IEEE Transaction on Industrial Electronics, vol. 53, no. 6, p.p. 1818-
1828,Dec 2006.
[II] S. Hemmati, S. Shokri, S. A. Saied, "Modeling and simulation of
internal short circuit faults in large hydro generators with wave
Windings", International Conference on Power Engineering, Energy and
Electrical Drives(POWERENG),p.p. 1-6,2011.
[12] A. B. Dehkordi, A. M. Gole, T. L. Maguire, P. Nitti, "A Real-Time
Model for Testing Stator-Ground Fault Protection Schemes of
Synchronous machines", International Conference on Power Systems
Transients (IPST2009),Japan,June 2009.
[13] A. Sinha, D. N. Vishwakarma, R. K. Srivastava, "Modeling and
Simulation of Internal Faults in Salient-pole Synchronous Generators
with Wave Windings", Department of Electrical Engineering, Institute of
Technology, India, Electric Power Components and systems, Vol. 37,
p.p. 100-114,Dec 2009.
[14] X. Tu, A. L. Dessaint, M. EI. Kahel and A. Barry, "Modeling and
experimental validation of internal faults in salient pole synchronous
machines including space harmonics", 8th International Conference on
Modeling and Simulation of Electric Machines,Converters and Systems,
Vol. 71,p.p. 425-439,June 2006.
[15] A. Sinha, D. N. Vishwakarma, R. K. Srivastava, "Modeling and real
time simulation of internal faults in turbogenerators", Department of
Electrical Engineering, Institute of Technology, India, Electric Power
Components and systems,Vol. 37,No. 9,p.p. 957-969,Aug 2009.
[16] X. Tu, L. Dessaint, N. Fallati, B. D. KeIper, "Modeling and Real-Time
Simulation of Internal Faults in Synchronous Generators With ParaUel­
Connected Windings", IEEE Transaction on Industrial Electronics, vol.
54,no. 3,p.p. 1400 - 1409,June 2007.
[17] H. Jiang,R. Aggarwal, G. Weller, S. Ball, L. Denning,"A new approach
to synchronous generator internal fault simulation using combined
Ninth International
winding function theory and direct phase quantities",
Conference on Electrical Machines and Drives, No. 468, p.p. 105-111,
1999.
[18] X. H. Wang, Y. G. Sun, B. Ouyang, W. 1. Wang, Z. Q. Zhu and D.
Howe, "Transient behavior of salient-pole synchronous machine with
stator winding faults", lEE proceedings Electric Power Applications.
Vol. 149,p.p. 143-151,2002.
[19] P. Le-Huy, C. Larose and F. Giguere, "Flexible Phase-Domain
Synchronous-Machine Model with Internal Fault for Protection Relay
Testing and related Real-Time Implementation Issues", International
Conference on Power Systems Transients(IPST2011), Netherlands, June
2011.

41

You might also like