CUSTOMER INFORMATION
Company Name: Email:
TIM
Address: Circuit ID:
INCIDENT DETAILS
Incident: Date and Time Started:
DC 1 PACU 3 Water Overflow Alarm March 30, 2023, 0809H
Page Break
Description of Incident:
An alarm on PACU 3 has been detected by the BMS Monitoring System. Upon physical checking
of DCO personnel, the PACU indicates Water Overflow Alarm, the pond water level is high.
DC1 PACU 3
Timeline of Events:
March 30, 2023
At 0809H, an alarm occurred in DC1 PACU3 that was registered in BMS Monitoring System
At 0814H, DCO personnel went to DC1 PACU3 to check the equipment and noticed that PACU 8
had critical alarm “Water Overflow Alarm” display on the monitor, the drain pond water level is
high.
Contact Huawei for support to check the unit onsite.
At 09:01H, Huawei personnel came onsite to check the unit.
At 0956H, Huawei personnel are done unclogging the drainpipe and cleaning the overflown
water beneath the raised floor.
At 1200H, PACU is running in normal operation.
Action Taken:
HUAWEI:
Turned-off the PACU and checked the drainpipe for blockage.
Found accumulation of crystal minerals/particles at the entrance of the drainpipe.
Manually removing of blockage in drainpipe.
Cleaned drain pond using a rag to avoid accumulation.
Overflown water beneath the raised floor was wiped and cleaned using a rag.
Melisa Dimaano
Data Center Engineer
Noted By:
Robin Bernados
Operations Director